BS 7671 Compliant

Circuit Breaker Sizing Calculator — Select the Right MCB Every Time

Enter the design current, cable type, and installation conditions. The calculator selects the correct MCB rating, verifies the Ib ≤ In ≤ Iz coordination requirement, and confirms the cable is adequately protected to BS 7671. No more guesswork on protective device selection.

MCB SelectionIb ≤ In ≤ Iz CheckCable CoordinationType B, C & D

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Circuit Breaker Selector

Find the right protective device for your circuit — BS 7671 compliant

A
Ω

Leave blank to skip Zs check

Ib ≤ In ≤ Iz

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1The fundamental BS 7671 coordination rule is Ib ≤ In ≤ Iz — the design current must not exceed the MCB rating, which must not exceed the cable current carrying capacity.
  • 2Type B MCBs trip at 3-5 times rated current and are used for resistive loads such as socket outlets, lighting, and immersion heaters.
  • 3Type C MCBs trip at 5-10 times rated current and are suitable for circuits with moderate inrush current such as motors, fluorescent lighting, and small transformers.
  • 4Type D MCBs trip at 10-20 times rated current and are used for high inrush loads such as X-ray machines, large motors, and welding equipment.
  • 5The I2 ≤ 1.45 x Iz condition must also be satisfied — the fusing current of the MCB must not exceed 1.45 times the cable current carrying capacity to prevent overheating.

What Is Circuit Breaker Sizing?

Circuit breaker sizing is the process of selecting a miniature circuit breaker (MCB) with the correct nominal current rating and trip curve for a given circuit. The MCB must be large enough to carry the normal load current without nuisance tripping, yet small enough to protect the cable from overcurrent and to disconnect the supply rapidly under fault conditions.

BS 7671:2018+A4:2026 sets out the requirements for overload protection in Section 432 and Chapter 43 (Section 433). Note that A4:2026 deleted the former Regulation 433.1 sub-regulation; practitioners must consult the restructured provisions in Chapter 43 for the current overload protection requirements. The protective device must satisfy two fundamental conditions: the nominal rating (In) must be at least equal to the design current (Ib) of the circuit, and the cable's current carrying capacity (Iz) must be at least equal to the nominal rating. This ensures the cable is never subjected to a sustained current above its safe operating limit.

Selecting the wrong MCB rating can lead to two types of problems. If the MCB is too small, it will trip under normal load conditions, causing disruption to the circuit and the equipment it supplies. If the MCB is too large, it will fail to protect the cable from overload, allowing sustained currents that exceed the cable's thermal rating — leading to insulation degradation, overheating, and potentially fire. The cable sizing calculator and circuit breaker sizing calculator work together to ensure both components are correctly matched.

Size Your MCB in Seconds

Enter the design current and cable details. The calculator recommends the correct MCB rating, verifies Ib ≤ In ≤ Iz…

Try it free for 7 days
Download on the App StoreGet it on Google Play

The Ib ≤ In ≤ Iz Rule Explained

The most fundamental coordination requirement in BS 7671 is expressed by the inequality Ib ≤ In ≤ Iz. This simple rule governs the relationship between the load, the protective device, and the cable:

Ib ≤ In — Device must carry the load

The design current (Ib) must not exceed the nominal rating (In) of the protective device. If Ib is 28A, the MCB must be at least 32A.

In ≤ Iz — Cable must carry the device rating

The nominal rating of the protective device must not exceed the current carrying capacity (Iz) of the cable after applying correction factors. A 32A MCB requires a cable with Iz of at least 32A.

There is also a second condition that must be checked: I2 ≤ 1.45 x Iz, where I2 is the current causing effective operation of the protective device. For MCBs to BS EN 60898, I2 = 1.45 x In, which means this condition is automatically satisfied when In ≤ Iz. However, for BS 3036 semi-enclosed fuses, I2 can be up to 2 x In, which is why the Cf factor of 0.725 must be applied to ensure the cable is adequately protected.

The Elec-Mate calculator checks both conditions automatically and flags any circuits where the coordination requirements are not met.

MCB Trip Curves: Type B, C, and D

MCBs have two protection mechanisms: a thermal element for overload protection (which responds to sustained overcurrents) and a magnetic element for short circuit protection (which responds to high fault currents). The trip curve defines the magnetic tripping threshold — the instantaneous current at which the MCB trips immediately.

Type B

3-5 x In

Trips magnetically at 3-5 times the rated current. Used for resistive loads: socket outlets, lighting, immersion heaters, storage heaters.

Type C

5-10 x In

Trips magnetically at 5-10 times the rated current. Used for moderate inrush loads: motors, fluorescent lighting, small transformers, air conditioning.

Type D

10-20 x In

Trips magnetically at 10-20 times the rated current. Used for very high inrush: large motors, X-ray machines, welding equipment, UPS systems.

In UK domestic installations, Type B MCBs are used for virtually all circuits. Type C is reserved for circuits supplying equipment with significant inrush current. Using a Type C where a Type B would suffice means the MCB requires a higher fault current to trip magnetically, which affects the maximum permitted earth fault loop impedance and the disconnection time verification.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

Cable and MCB Coordination

Correct coordination between the MCB and the cable is essential for safety. The MCB must protect the cable from both sustained overload and short circuit fault current. For overload protection, the Ib ≤ In ≤ Iz rule ensures the cable is never subjected to a continuous current above its rating.

For short circuit protection, the cable must be able to withstand the thermal effects of the fault current for the time it takes the MCB to disconnect. This is verified using the adiabatic equation from BS 7671 Regulation 434:

S ≥ √(I²t) / k

Where S is the minimum conductor CSA, I²t is the energy let-through of the MCB (from manufacturer data), and k is a constant for the conductor and insulation type (115 for copper/PVC, 143 for copper/XLPE). If the installed cable CSA is greater than or equal to S, the cable is adequately protected.

k = 115 applies to copper conductors incorporated in a PVC cable at 70°C initial temperature (BS 7671 Table 54.3); k = 143 applies to a separately run insulated copper conductor not incorporated in a cable at 30°C initial temperature (BS 7671 Table 54.2).

In practice, for most domestic circuits, the standard cable sizes (1.5mm², 2.5mm², 4mm², 6mm², 10mm²) easily satisfy the adiabatic equation when protected by standard MCB ratings. The check becomes more critical on long cable runs, circuits with high prospective fault current, or where the cable CSA has been minimised. The adiabatic equation calculator in Elec-Mate performs this verification automatically.

MCB Sizing with Full Cable Coordination

The circuit breaker calculator checks Ib ≤ In ≤ Iz, verifies the adiabatic equation, and confirms disconnection times — all in one calculation.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Common MCB Ratings and Typical Uses

Standard MCB ratings follow a preferred range defined in BS EN 60898: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, and 63A. The rating you select depends on the design current of the circuit. Common domestic and commercial applications include:

  • 6A Type B: Lighting circuits (domestic and commercial), small fixed loads.
  • 16A Type B: Immersion heaters, towel rails, small radial circuits, outdoor sockets.
  • 20A Type B: Radial socket circuits (up to 50m² floor area), water heaters, dedicated appliance circuits.
  • 32A Type B: Ring final circuits, electric cookers up to 7kW, large shower circuits.
  • 40A Type B: Electric cookers over 7kW, large instantaneous electric showers (9-10.5kW).
  • 32A Type C: EV charger circuits (7kW single-phase), air source heat pumps. Note: where the EVSE may produce smooth DC fault currents, BS 7671 Regulation 551.4.3.3.2 requires the installer to consider a Type B RCD — a standard Type AC or Type A RCD will not detect smooth DC residual currents.

The Elec-Mate calculator suggests the appropriate MCB rating based on the design current you enter, and recommends the correct trip curve based on the load type. It also flags situations where the next standard rating up may be needed — for example, when the design current is very close to a standard rating and there is a risk of nuisance tripping under normal operating conditions.

How to Size a Circuit Breaker

Five steps to select the correct MCB rating and type for any circuit to BS 7671.

1

Calculate the design current (Ib)

Determine the maximum sustained current the circuit will carry. For resistive loads, Ib = Power / Voltage. For motor loads, use the full load current from the manufacturer. For discharge lighting, multiply lamp wattage by 1.8.

2

Select the MCB rating (In)

Choose the next standard MCB rating equal to or greater than the design current. Standard ratings are 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, and 63A. Ensure In ≥ Ib.

3

Select the MCB type (B, C, or D)

Choose Type B for resistive loads (sockets, lighting, heaters), Type C for moderate inrush loads (motors, fluorescent lighting), or Type D for high inrush loads (welding, X-ray, large motors).

4

Verify cable coordination

Check that the cable current carrying capacity (Iz) after applying correction factors is at least equal to the MCB rating (In). If Iz < In, increase the cable size until the coordination requirement is met.

5

Check the I2 condition

Verify that I2 ≤ 1.45 x Iz, where I2 is the fusing current of the MCB. For MCBs to BS EN 60898, I2 = 1.45 x In, so this is automatically satisfied when In ≤ Iz.

Circuit Breaker Sizing Features

Everything you need to select the right MCB for any circuit, with full BS 7671 coordination checks.

Automatic MCB Selection

Enter the design current and load type. The calculator recommends the correct MCB rating and trip curve…

Ib ≤ In ≤ Iz Verification

Automatically checks the fundamental coordination requirement. Flags any circuit where the MCB rating exceeds the cable capacity or is below the design…

Type B, C, and D Selection

Recommends the appropriate trip curve based on the load characteristics. Explains why each type is selected and the implications for disconnection time.

Cable Coordination Check

Verifies the cable is adequately protected by the selected MCB. Checks both overload (Ib ≤ In ≤ Iz) and short circuit (adiabatic equation) protection.

BS 7671:2018+A4:2026 Data

All standard MCB ratings, trip curves, and coordination requirements from the current edition of BS 7671 including Amendment 4.

Works Offline on Site

Size circuit breakers anywhere with no internet connection. All MCB data and cable tables are stored locally on your device.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size circuit breakers with confidence

Join 1,000+ UK electricians using Elec-Mate for MCB selection and cable coordination. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy