The minimum cross-sectional area (csa) of main protective bonding conductors is governed by Reg 544.1.1. The rule differs depending on whether PME (TN-C-S) or non-PME earthing applies:
Table 54.8 — PME main bonding conductor sizing
Minimum main bonding conductor vs the supply PEN (neutral) conductor — BS 7671 Reg 544.1.2
Supply PEN (Cu equiv)
Min main bonding
≤ 35 mm²
10 mm²
over 35 up to 50 mm²
16 mm²
over 50 up to 95 mm²
25 mm²
over 95 up to 150 mm²
35 mm²
over 150 mm²
50 mm²
Most UK domestic PME supplies use a 16–25 mm² PEN, so 10 mm² is the standard main bonding size. Non-PME (TN-S/TT): at least half the earthing-conductor csa, minimum 6 mm² (Reg 544.1.1).
- Non-PME supplies (TN-S, TT) — the bonding conductor must be at least half the csa of the earthing conductor of the installation, subject to a minimum of 6mm² and a maximum of 25mm² copper-equivalent (Reg 544.1.1).
- PME / TN-C-S supplies — the bonding conductor is selected against the PEN conductor of the supply using Table 54.8: PEN ≤35mm² → 10mm²; PEN >35mm² up to 50mm² → 16mm²; PEN >50mm² up to 95mm² → 25mm² (Reg 544.1.2 / Table 54.8).
Most UK domestic properties are supplied on PME (TN-C-S) with a PEN conductor of 16mm² or 25mm², so 10mm² is the standard main bonding conductor size. The 6mm² minimum is the absolute floor and applies only to non-PME installations with a small earthing conductor — where in doubt, 10mm² should always be used.
- Typical domestic PME supply (PEN ≤35mm²) — a standard 100A single-phase domestic TN-C-S supply uses a PEN conductor of 16mm² or 25mm². Table 54.8 (Reg 544.1.1) requires a minimum 10mm² main bonding conductor for these supplies. This is the most common bonding conductor size for domestic properties in the UK.
- Larger PME supplies (PEN >35mm² up to 50mm²) — where the network PEN conductor exceeds 35mm² (common for larger commercial premises or upgraded domestic supplies), Table 54.8 requires 16mm² main bonding conductors. Using 10mm² in this situation would be undersized and is typically flagged C2 on an EICR.
- Non-PME supplies (TN-S, TT) and the 6mm² minimum — on non-PME supplies the bonding conductor is sized at half the csa of the earthing conductor, with a floor of 6mm² copper. This applies only to TN-S or TT installations; the overwhelming majority of UK properties are PME (TN-C-S) and so use Table 54.8. Never specify 6mm² on a standard PME domestic supply: it will typically be flagged C2 on the next EICR.
- Older installations with 6mm² — many older properties have 6mm² main bonding conductors installed to a previous edition's minimum. On a standard PME (TN-C-S) supply, Reg 544.1.1 / Table 54.8 requires 10mm² where the PEN conductor is ≤35mm². A 6mm² conductor on such a supply is undersized and is commonly observed as a C2 during EICRs.