WIRING GUIDE

UK Earthing Systems Guide: TN-S, TN-C-S and TT Explained

A complete practical guide to earthing systems used in UK electrical installations — TN-S, TN-C-S (PME) and TT explained with BS 7671 requirements, PME limitations, EV charging earthing, outbuilding supplies, and earth loop impedance differences between systems.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1The earthing system type determines how fault current returns to the source and directly affects earth loop impedance, disconnection times, and the type of protective measures required.
  • 2TN-S systems have separate neutral (N) and protective earth (PE) conductors throughout — typically found in older properties served by concentric wiring or properties with a separate earth terminal at the cut-out.
  • 3TN-C-S (PME) systems combine N and PE in the network (PEN conductor) and split them at the consumer's installation — the most common system in the UK, supplied by the DNO's PME terminal.
  • 4TT systems use a local earth electrode — required for outbuildings, caravans, marinas, and any installation where the PME earth terminal is not available or suitable.
  • 5PME earthing must not be extended to outbuildings, caravans, static caravans, or locations accessible to livestock due to the risk of dangerous touch voltages under open-circuit neutral conditions.
  • 6EV charge points require specific earthing considerations — TN-C-S supplies need a PME earth electrode system or PME earthing prohibition check; TT supplies may require an earth electrode at the charge point.
01 · Wiring Guide

What Is an Earthing System?

An earthing system is the arrangement by which the electrical installation is connected to earth (the general mass of the earth) to ensure that exposed metallic parts of equipment and the installation are maintained at earth potential under fault conditions. Earthing provides a low-impedance path for fault current to flow, enabling protective devices (MCBs, fuses, RCDs) to operate and disconnect the supply before dangerous voltages or temperatures develop.

  • Protection against electric shock — if a live conductor contacts exposed metalwork (a fault to earth), the earthing system ensures fault current flows via the protective conductor rather than through a person who touches the metalwork. The fault current is high enough to operate the protective device quickly.
  • Protection against fire — by ensuring rapid disconnection of earth faults, the earthing system limits the duration and magnitude of arcing that could ignite surrounding materials.
  • BS 7671 classification — BS 7671 18th Edition classifies earthing systems using a two or three-letter code based on IEC 60364 standards. The letters describe the relationship between the supply source and earth, and the relationship between the installation's exposed conductive parts and earth.

The three earthing system types used in UK public electricity supply installations are TN-S, TN-C-S, and TT. Each has different characteristics affecting earth loop impedance, the types of protective measures required, and restrictions on where the earthing arrangement can be extended.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Wiring Guide

TN-S — Separate Neutral and Protective Conductors

In a TN-S system, the supply source (transformer) has one point directly earthed, and the exposed conductive parts of the installation are connected to that earth point via a protective conductor (PE) that is entirely separate from the neutral conductor (N). The two conductors are separate throughout the entire network.

  • Where it is found — TN-S is increasingly rare in new UK installations. It is typically found in older properties served by concentric wiring (where the outer sheath of the service cable acts as the PE), in properties with an armoured service cable where the armouring is used as the PE, and in some industrial and commercial installations with dedicated earth conductors.
  • Identification — at the DNO cut-out, a TN-S supply will have separate earth and neutral terminals. The earth terminal is connected to the cable's metallic sheath or armour rather than the neutral conductor. The neutral and earth are not bonded together at the cut-out.
  • Earth loop impedance — TN-S systems typically have Zs values in the range of 0.1 to 0.8 ohms at the consumer's installation, depending on the cable length and cross-sectional area. This relatively low impedance means MCBs and fuses can reliably clear earth faults within the required disconnection times.
  • Degradation risk — in concentric wiring systems, the outer sheath (PE conductor) can corrode over time. This is an important inspection point during EICRs on older properties — a corroded sheath increases Zs and may compromise the effectiveness of overcurrent device tripping under fault conditions.
03 · Wiring Guide

TN-C-S — PME (Protective Multiple Earthing)

In a TN-C-S system, the neutral and protective earth are combined as a single PEN (Protective Earth and Neutral) conductor in the distribution network. At the consumer's installation, the PEN conductor is split into separate N and PE conductors. This arrangement is called Protective Multiple Earthing (PME) and is by far the most common earthing system for new domestic connections in the UK.

  • DNO PME terminal — the DNO provides a combined N/E terminal at the cut-out, usually labelled "PME Earth Terminal" or marked with the combined N/PE symbol. The installation's main earthing terminal and the neutral are both connected to this terminal and bonded together within the installation.
  • Low earth loop impedance — TN-C-S systems typically have Zs values of 0.1 to 0.6 ohms, similar to TN-S. This allows MCBs and fuses to clear earth faults reliably. RCDs are required for additional protection on specified circuits (socket outlets, etc.) but are not the primary means of earth-fault disconnection.
  • Open-circuit neutral risk — the critical limitation of PME is that if the PEN conductor breaks upstream of the consumer, the consumer's earth terminal can rise to line voltage. Everything connected to the installation's earth — exposed metalwork, bonded pipework — becomes live relative to true earth. This is the reason for the restrictions on extending PME to certain locations.
04 · Wiring Guide

TT — Earth Electrode System

In a TT system, the installation's earth is provided by a local earth electrode (typically a copper earth rod driven into the ground) that is entirely independent of the DNO's neutral. The supply source is earthed at the substation, but the consumer's installation has no metallic connection to that earth — fault current must return via the soil.

  • Where it is required — TT is required for outbuildings (separate structures), caravans, static caravans, caravan parks, marinas, agricultural premises, and any location where PME earthing is prohibited or the DNO cannot provide an earth terminal. Some rural properties on overhead supply lines may also have TT systems.
  • High earth loop impedance — because fault current returns via soil rather than a metallic conductor, Zs values on TT systems are typically 20 to 200 ohms or higher, depending on soil type, moisture content, and electrode design. At these impedances, overcurrent devices (MCBs) cannot operate within the required disconnection times — RCD protection is mandatory on TT systems for this reason.
  • Earth electrode testing — the earth electrode resistance must be measured during installation and at each EICR. The electrode resistance (Ra) in ohms multiplied by the RCD rating (IΔn) in amps must not exceed 50V, per BS 7671. For a 30mA RCD: Ra × 0.03 ≤ 50, meaning Ra must not exceed approximately 1,667 ohms — achievable with a well-installed electrode, though lower is always better.
  • No bonding to main building's earth — where a TT outbuilding is fed from a TN-C-S main building, the supply cable must have no metallic armour or screen connected to the main building's earth. An SWA cable's armouring must be isolated at the outbuilding end, or an XLPE/LSF cable in plastic conduit used.
05 · Wiring Guide

PME Conditions and Limitations

The Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR) and BS 7671 both place restrictions on where PME earthing can and cannot be extended. These limitations exist because of the open-circuit neutral risk inherent in TN-C-S systems.

  • Outbuildings — PME earthing must not be extended to a structure that is a separate building from the main installation. Even a detached garage requires a TT supply or an alternative protective measure. This is one of the most commonly misunderstood requirements in domestic electrical work.
  • Caravans and mobile homes — PME earthing is prohibited for caravan supplies. Static caravans and touring caravans require TT supplies with RCD protection. The caravan industry standard (BS EN 60309 / BS 7671 Part 7) reflects this requirement.
  • Livestock locations — agricultural premises where livestock have access to earthed metalwork must not use PME earthing. Animals are more susceptible to electric shock than humans (lower body resistance, multiple contact points) and may receive dangerous touch voltages under PME open-neutral conditions.
  • Marinas and boatyards — shore supply to boats must use TT or isolation transformer supplies. Extending PME to marina pontoons creates stray current corrosion and touch-voltage risks.
06 · Wiring Guide

Earthing Systems and EV Charging

EV charge points have specific earthing requirements that depend on the installation's earthing system. BS 7671 18th Edition and the IET Code of Practice for Electric Vehicle Charging Equipment Installation both address these requirements in detail.

  • TN-C-S (PME) supplies — an earth electrode must be installed at the charge point location, bonded to the charge point's earth terminal, to provide a combined PME/electrode earthing arrangement. This limits the touch voltage to a safe level if the neutral is lost. Alternatively, charge points with integral protective measures against loss-of-earth (including automatic disconnection) may be used without an additional electrode, subject to the device's documentation.
  • TT supplies — the charge point must be on the TT earth system. A Type A or Type B RCD must protect the charge point circuit. The earth electrode resistance must be verified to ensure the RCD trip condition (Ra × IΔn ≤ 50V) is met.
  • RCD type for EV circuits — EV charge point circuits require a Type A or Type B RCD (not Type AC) because the charging electronics can produce pulsating DC residual currents that Type AC RCDs cannot detect reliably.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · Wiring Guide

Outbuildings, Caravans and TT Earthing

Supplying a separate outbuilding (garden office, garage, workshop, studio) is one of the most common domestic electrical jobs that requires a TT earthing system. Getting the earthing arrangement wrong is one of the most common and dangerous errors in this type of work.

  • Earth rod installation — the earth rod should be driven vertically into the ground to a sufficient depth to achieve adequate electrode resistance (typically 1.2m or more, with multiple rods or horizontal electrodes where soil resistance is high). The rod must be accessible for testing.
  • Supply cable selection — use a cable with no metallic sheath or armour connected to the main building's earth terminal. An unarmoured cable in a protective conduit, or an SWA cable with the armouring isolated at the outbuilding end, are both acceptable. Never connect SWA armouring to both the main building's PME earth and the outbuilding's TT earth.
  • RCD protection mandatory — all circuits in TT outbuildings must be protected by RCDs because the high earth loop impedance prevents MCBs from clearing earth faults within required times. An RCCB or RCBOs at the outbuilding distribution board is essential.
  • Certification — an outbuilding supply installation is notifiable work requiring an Electrical Installation Certificate (EIC). The test results must include electrode resistance measurement, Zs for each circuit, and RCD test results.
08 · Wiring Guide

Earth Loop Impedance Differences Between Systems

Earth loop impedance (Zs) is the total impedance of the fault current loop and is fundamental to determining whether protective devices will operate within the required disconnection time under fault conditions. The earthing system has a major influence on Zs.

  • TN-S and TN-C-S — Zs is typically 0.1 to 1.0 ohm for final circuits. Low Zs means high fault current, which reliably trips MCBs within 0.4 seconds (for circuits up to 32A) or 5 seconds (for distribution circuits). RCDs are not needed as the primary means of disconnection, but are required for additional protection on specified circuit types.
  • TT systems — Zs is typically 20 to 200 ohms or more. At these impedances, a phase-to-earth fault would produce only 1.2 to 12 amperes of fault current — far below the trip threshold of any MCB or fuse. RCDs are therefore the primary means of disconnection in TT systems.
  • Impact on EICR assessment — measured Zs values must be compared against the maximum Zs values in BS 7671 Appendix 3 for the specific protective device. A TT system's Zs values will always appear extremely high in absolute terms but are acceptable because RCD protection is confirmed to operate correctly at those impedances.
09 · Wiring Guide

Identifying the Earthing System on Site

Correctly identifying the earthing system is an essential step before carrying out any electrical installation work or EICR. Misidentifying the earthing system can lead to incorrect protective measures being specified.

  • Check the cut-out and meter — the supply head (cut-out) and meter cabinet usually show the earthing arrangement. A clearly labelled PME terminal indicates TN-C-S. A separate earth terminal connected to cable sheath or armour indicates TN-S. No DNO earth terminal indicates TT.
  • Contact the DNO — for certainty, contact the Distribution Network Operator (Western Power Distribution, UK Power Networks, Northern Powergrid, etc.) and request confirmation of the earthing system for the specific address. This is the most reliable method and is particularly important for commercial installations.
  • Check previous certificates — the earthing system should be recorded on previous EICRs and EICs for the property. However, always verify physically — the system may have changed or been recorded incorrectly.
10 · Wiring Guide

For Electricians: Earthing System Documentation

The earthing system must be correctly identified and documented on the EICR and EIC. Errors in earthing system identification are among the most consequential mistakes on electrical certificates, as they affect the interpretation of all Zs measurements and the assessment of protective device adequacy.

Record Earthing System on Certificate

The earthing system type (TN-S, TN-C-S, TT) must be recorded on the EIC or EICR, along with the method of earthing (DNO terminal, earth electrode, etc.) and the measured earth electrode resistance where applicable. Use the Elec-Mate app to complete all sections correctly with built-in guidance.

Complete EICRs and EICs with correct earthing system

Join 1,000+ UK electricians using Elec-Mate for on-site EICR and EIC completion. Built-in guidance for earthing system identification, AI board scanning…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About UK Earthing Systems

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Complete Earthing Documentation Correctly on Your Phone

Join 1,000+ UK electricians using Elec-Mate for on-site EICR and EIC completion with correct earthing system documentation, AI board scanning, and instant PDF export. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy