INSTALLATION GUIDE

FP200 Gold Fire Resistant Cable: UK Installation Guide

Terminating, clipping and segregating FP200 Gold to BS 7671:2018+A4:2026 — the Reg 560.8.1 compliance routes, the one-hour default fire rating, support requirements under Reg 521.10.202, and how it compares to mineral insulated cable.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is FP200 Gold cable used for?

FP200 Gold is a fire-resistant cable to BS 7629-1 used for life-safety circuits — fire detection and alarm systems (BS 5839-1) and emergency lighting (BS 5266-1) — where the cable must keep working during a fire. It satisfies BS 7671 Reg 560.8.1(c), terminates with conventional tools rather than the crimping and sealing kit MICC needs, and must be supported on steel or copper clips so it does not collapse in a fire.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01FP200 Gold is a fire-resistant cable to BS 7629-1:2015+A1:2019 — the product specification for 300/500 V fire-resistant, screened, fixed-installation cables with low emission of smoke and corrosive gases.
  2. 02BS 7671 Reg 560.8 sets the fire rating: cables supplying safety circuits must achieve the time authorised by the building regulations or the relevant British Standard, or one hour where neither specifies a time.
  3. 03Reg 560.8.1 lists four permitted wiring systems for safety services. FP200 Gold sits under route (c) — cables meeting the test requirements of BS EN 50200, BS 8434 or BS 8491, and BS EN 60332-1-2.
  4. 04Reg 560.8.1 also requires the wiring system to be mounted and installed so that circuit integrity will not be impaired during a fire — which is what makes fire-rated glands and fixings part of the compliance, not an optional extra.
  5. 05Reg 521.10.202 requires wiring systems to be supported so they will not collapse prematurely in a fire, and its NOTE 3 rules out non-metallic clips or cable ties as the sole means of support. Steel or copper clips and saddles are the stated example.
  6. 06BS 5839-1:2025 (fire detection and alarm, non-domestic premises) and BS 5266-1:2025 (emergency lighting) are the codes of practice BS 7671 Regs 560.10 and 560.9 point to.
  7. 07The On-Site Guide 7.4.1 note states fire alarm and emergency lighting circuits must be separated from other cables and from each other, in compliance with BS 5839 and BS 5266 respectively.
  8. 08FP200 Gold terminates with conventional strippers and standard screw terminals — no crimping tools and no moisture-sealing kit, which is its main practical advantage over MICC.

01 · Installation Guide

FP200 Gold at a Glance

The figures below are the ones you need on site. Regulation numbers are BS 7671:2018+A4:2026 unless stated otherwise.

Product specificationBS 7629-1:2015+A1:2019 — 300/500 V fire-resistant, screened, fixed installation cables with low emission of smoke and corrosive gases (multicore)
Voltage rating300/500 V
BS 7671 routeReg 560.8.1(c) — tested to BS EN 50200, BS 8434 or BS 8491, plus BS EN 60332-1-2
Required fire durationReg 560.8 — the time authorised by the building regulations or the relevant British Standard; one hour where neither specifies one
Typical applicationsFire detection and alarm (BS 5839-1:2025), emergency lighting (BS 5266-1:2025)
Continuous conductor temperature105°C per the manufacturer's data — check the data sheet for the size and grade you are installing
TerminationConventional strippers and standard screw terminals; fire-rated gland at every enclosure entry
FixingsSteel or copper clips, saddles or ties (Reg 521.10.202 NOTE 4). Non-metallic clips and cable ties are precluded as the sole support (NOTE 3)
Typical clip spacing250mm horizontal, 400mm vertical per the manufacturer's installation data
Protected escape routesPermitted by Reg 422.2.1(a) as a cable meeting Reg 560.8.1. Appendix 13 gives the supporting guidance

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

What is FP200 Gold Fire-Resistant Cable?

FP200 Gold is a fire-resistant cable manufactured by Prysmian for fixed wiring in life-safety circuits that must continue to function during a fire. It is one of the most commonly specified fire-resistant cables in the UK for fire alarm systems and emergency lighting, largely because it installs and terminates with ordinary tools.

Unlike standard PVC-insulated cables, FP200 Gold uses an enhanced insulation system beneath a low smoke, zero halogen (LSZH) outer sheath. That construction is what lets the cable hold electrical continuity while exposed to flame — keeping sounders operating and escape route luminaires lit during evacuation.

It is available in 2-core, 3-core and multi-core variants in conductor sizes from 1mm² to 4mm² for fire protection work. Red sheath is the UK convention for fire alarm cabling, with white and cream variants where red is visually unacceptable.

What BS 7671 means by “low smoke, low halogen”

Reg 422.2.1 puts numbers on it for cables in protected escape routes: limited smoke production, a minimum of 60% light transmittance when tested to BS EN 61034-2, and limited halogen acid gas content not exceeding 0.5% when tested to BS EN 60754-1. Those two figures are the objective test of an LSZH claim.

03 · Installation Guide

BS 7629-1, the Fire Test Standards and CPR

Three separate things get conflated on data sheets, and it is worth keeping them apart: the cable specification, the fire test methods used to classify circuit integrity, and the reaction-to-fire requirements of the Construction Products Regulation.

StandardWhat it covers
BS 7629-1:2015+A1:2019The cable specification — 300/500 V fire-resistant, screened, fixed installation cables with low emission of smoke and corrosive gases, multicore. This is what FP200 Gold is made to. It is a product spec, not a fire test.
BS EN 50200:2015Method of test for resistance to fire of unprotected small cables for use in emergency circuits. Named in Reg 560.8.1(c).
BS 8434Methods of test for assessment of the fire integrity of electric cables. Named in Reg 560.8.1(c).
BS 8491:2008Method for assessment of fire integrity of large diameter power cables used as components of smoke and heat control systems and certain other active fire safety systems. Named in Reg 560.8.1(c).
BS EN 60332-1-2Flame propagation of a single vertical cable. Required alongside every one of routes (a), (b) and (c) of Reg 560.8.1.

Voltage and temperature

The 300/500 V rating in the BS 7629-1 title covers mains-voltage fire alarm power supplies and the extra-low voltage detection circuits that run alongside them. The manufacturer quotes a continuous conductor temperature of 105°C against 70°C for ordinary thermoplastic cable — take the figure from the data sheet for the size and grade you are actually installing, and remember Reg 526.1(e) requires the means of connection to be chosen so that the terminal temperature in normal service does not impair the insulation of the conductors connected to it.

CPR: what the label does and does not mean

Appendix 2, Item 17 of BS 7671 explains the position. The Construction Products Regulation is administered by the Ministry of Housing, Communities and Local Government (MHCLG) and empowers the UK to set performance levels for particular installations, but MHCLG has not exercised those powers in respect of reaction to fire for cables. The generic reaction-to-fire requirements for all cables sit in BS EN 50575. The NOTE to Reg 527.1.3 and NOTE 1 to Reg 422.2.1 both point readers to that item — and NOTE 1 to Reg 422.2.1 adds that there are no requirements in the CPR for the fire-resisting cables described in Reg 560.8.

So a Cca-s1b,d1,a1 declaration on an FP200 Gold reel is a manufacturer's CPR classification and labelling matter, not a BS 7671 minimum. If a project needs a specific CPR class, the specification and the purchase order have to call it up explicitly.

04 · Installation Guide

What BS 7671 Requires for Fire-Resistant Wiring

The obligation sits in Chapter 56, Safety Services. Reg 560.5.1 recognises that safety services may be required to operate at all relevant times, including during mains and local supply failure and through fire conditions. Where they are required to operate in fire conditions, Reg 560.5.2 requires two things: a source selected to maintain a supply of adequate duration, and all equipment provided — by construction or by erection — with fire-resisting protection of adequate duration.

Reg 560.8.1 — the four permitted wiring systems

(a)Mineral insulated cable systems complying with BS EN 60702-1 and BS EN 60702-2 and BS EN 60332-1-2 — MICC / Pyrotenax.
(b)Fire-resistant cables complying with IEC 60331-1, IEC 60331-2 or IEC 60331-3 and with BS EN 60332-1-2.
(c)Fire-resistant cables complying with the test requirements of BS EN 50200, BS 8434 or BS 8491, appropriate for the cable size, and with BS EN 60332-1-2. This is FP200 Gold's route.
(d)A wiring system maintaining the necessary fire and mechanical protection — NOTE 2 gives constructional enclosures, or wiring systems in separate fire compartments giving equivalent protection, as examples.

Reg 560.8.1 does not stop at the list. It goes on to require that the wiring system selected shall meet the requirements of the relevant code of practice for the application and shall be mounted and installed in such a way that the circuit integrity will not be impaired during a fire. That sentence is why glands, clips and penetrations are compliance items rather than finishing touches.

BS 7629-1 is not one of the four lettered routes, but it is not absent either: NOTE 1 to Reg 560.8.1 records that BS 5266, BS 5839 and BS 8519 specify cables to BS EN 60702-1, BS 7629-1, BS 7846 and BS 8592 (BS 5266 only) as suitable when appropriately selected for the application.

How long the cable has to survive

Reg 560.8 sets the duration: cables supplying safety circuits shall have a resistance to fire rating of either the time authorised by regulations for building elements, or by British Standards for the circuits, or one hour in the absence of such a regulation or standard. Confirm the declared classification of the cable and its accessories covers whatever duration the fire strategy calls for.

Other regulations that bite

422.2.1Only cables meeting Reg 560.8.1, bunched cables to the relevant part of BS EN 60332-3, or single cables in the listed non-flame-propagating containment may be installed in protected escape routes. Cables there must be as short as practicable and not within arm's reach unless protected against mechanical damage.
422.2.201Nothing may be installed in a firefighting shaft or protected stairway unless it is part of an essential fire safety or related safety system, general needs lighting, or socket-outlets for cleaning and maintenance.
422.6(b)In locations of national, commercial, industrial or public significance, cables with improved fire-resisting characteristics such as those to BS 7629-1, BS 7846 or BS 8592 are among the measures that may be considered.
560.9 / 560.10Emergency lighting systems shall comply with BS 5266-1, BS EN 1838 and BS EN 50172. Fire detection and fire alarm systems shall comply with the relevant parts of the BS 5839 series.
560.11Power and control cable systems required to maintain circuit integrity for life safety and firefighting applications shall comply with the relevant parts of BS 8519:2020.

05 · Installation Guide

Requirements Under BS 5839 and BS 5266

BS 7671 hands the detail to two codes of practice. Reg 560.10 requires fire detection and fire alarm systems to comply with the relevant parts of the BS 5839 series; Reg 560.9 requires emergency lighting systems to comply with BS 5266-1, BS EN 1838 and BS EN 50172. The current dated references in BS 7671 Appendix 1 are BS 5839-1:2025 and BS 5266-1:2025.

StandardScope and effect on cable choice
BS 5839-1:2025Design, installation, commissioning and maintenance of fire detection and fire alarm systems in non-domestic premises. Cables to BS EN 60702-1, BS 7629-1 or BS 7846 are the accepted types per NOTE 1 to Reg 560.8.1 — covering detection circuits, sounder circuits, power supplies and panel interconnects. System category (Category L or Category M) and the fire risk assessment set the extent of coverage.
BS 5266-1:2025Code of practice for the emergency lighting of premises. NOTE 1 to Reg 560.8.1 adds BS 8592 to the accepted cable list for BS 5266 work. Routes must be designed to minimise fire exposure and circuits separated from one another.
BS 8519:2020Selection and installation of fire-resistant power and control cable systems for life safety and firefighting applications. Reg 560.11 makes this the governing code for firefighting lifts, smoke control and similar systems.
Approved Document BEngland's Building Regulations fire safety guidance references the BS 5839 and BS 5266 series. Scotland and Northern Ireland have their own equivalent technical guidance.

For dwellings, the relevant part is the domestic part of the BS 5839 series rather than BS 5839-1, which covers non-domestic premises. Grade D domestic systems are commonly wired in standard cable; higher grades and any commercial or institutional building will call for fire-resistant cable. Work to the current edition of the applicable part and to the specific project risk assessment.

06 · Installation Guide

How to Terminate FP200 Gold Cable

FP200 Gold is terminated with conventional tools — that is its main practical advantage over MICC. There is no crimping tool, no pot, no sealing compound and no moisture window to work within. What does need care is the gland, the strip length and the screen.

Termination sequence

  1. Fit the gland first. Every enclosure entry — panel, sounder base, junction box, conduit box — takes a fire-rated gland specified by the cable manufacturer. Reg 560.8.1 requires the wiring system to be mounted and installed so that circuit integrity will not be impaired during a fire, and a standard gland at a panel entry defeats that at the one point the cable is most likely to be attacked.
  2. Strip only what you need. Take the LSZH outer sheath back to the minimum length the enclosure requires. Use a proper stripping tool and avoid nicking the insulation or the tape beneath it — damage there is invisible on a continuity test and only shows up in a fire.
  3. Terminate the conductors. Standard screw terminals are fine. Reg 526.1 requires every connection to give durable electrical continuity and adequate mechanical strength and protection, and Reg 526.1(e) requires the terminal temperature in normal service not to impair the insulation of the conductors connected to it.
  4. Deal with the screen. BS 7629-1 cables are screened. Where the design uses the screen or drain conductor as a circuit protective conductor, its cross-sectional area must satisfy Reg 543.1.3 — the adiabatic calculation, or a reference to BS 7454. Do not leave a screen floating at one end without checking what the system designer intended.
  5. Enclose and keep it accessible. Reg 526.5 requires every termination and joint in a live conductor to be made inside a suitable accessory, an equipment enclosure, or an enclosure formed with non-combustible building material. Reg 526.3 requires every connection to be accessible for inspection, testing and maintenance unless it falls into one of the listed exceptions.

The most common termination failure

Correct cable, correct clips, standard glands. Fire performance is a property of the whole cable system, not the drum it came off. If the gland, the enclosure and the fixings are not rated for the same duration as the cable, the circuit fails at the termination and the cable's classification counts for nothing.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

07 · Installation Guide

Clipping and Support Spacing

Support is a BS 7671 requirement in its own right. Reg 521.10.202 states that wiring systems shall be supported such that they will not be liable to premature collapse in the event of a fire, and it applies throughout the installation — not just in escape routes as the superseded Reg 521.11.201 did.

Reg 521.10.202What it says
NOTE 2Cables installed in or on steel cable containment systems are deemed to meet the regulation.
NOTE 3Precludes non-metallic cable clips or cable ties as the sole means of support where cables are clipped direct to exposed surfaces or suspended under cable tray, and non-metallic trunking as the sole support of the cables within it.
NOTE 4Suitably spaced steel or copper clips, saddles or ties are examples that meet the regulation.
NOTE 5The intent is to stop wiring systems collapsing and hindering evacuation or firefighter access. It is not intended to maintain circuit integrity for life safety or firefighting — that is Chapter 56 and the codes of practice BS 5266, BS 5839 and BS 8519.

That last note matters on fire alarm work. Meeting Reg 521.10.202 with steel clips is the floor, not the ceiling — the fixing also has to hold the cable in place for the duration the fire strategy requires, which is a manufacturer and BS 5839-1 question.

RunTypical maximum spacingWhy
Horizontal, 1.5mm² and 2.5mm²250mm centresKeeps unsupported spans short enough that a softened cable does not sag out of its designed route
Vertical400mm centresGravity loading on a vertical drop is higher, so each clip must grip rather than merely locate the cable

These are the manufacturer's typical figures for FP200 Gold — larger sizes and specific grades vary, so confirm against the current Prysmian installation data for the cable on the drum. Standard oval or round white PVC clips, nylon ties used as the sole fixing, and self-adhesive clips are all ruled out by Reg 521.10.202 NOTE 3.

Also on the list

Fire stop every penetration of a fire-rated wall, floor or ceiling with an approved system. Reg 422.2.202 is the related point: cables are only deemed to be outside a protected escape route where they are in a fire-resisting enclosure with a fire resistance at least equal to that of the compartment they pass through, or as specified by the fire engineer.

08 · Installation Guide

Fire Alarm Cable Segregation

Segregation comes from two directions. BS 7671 Reg 528.1 deals with the proximity of Band I and Band II circuits and sets out the conditions (a) to (f) under which they may share a wiring system — insulation to the highest voltage present, separate compartments, a partitioned tray, separate conduit or trunking, or an earthed metal screen of equivalent current-carrying capacity in a multicore cable. NOTE 2 to that regulation then points to BS 5266, BS 5839 and BS 8519 for separation and segregation in relation to safety services.

The IET On-Site Guide restates it plainly at 7.4.1: fire alarm and emergency lighting circuits must be separated from other cables and from each other, in compliance with BS 5839 and BS 5266 respectively. So a detection loop and an emergency lighting sub-main sharing an unpartitioned trunking is not acceptable simply because both cables are fire-rated.

What this means on site

  • Fire alarm circuits get their own containment, or a partitioned compartment within shared containment.
  • Emergency lighting circuits are separated from the fire alarm as well as from general wiring — “from each other” is explicit in the On-Site Guide note.
  • Where segregation is achieved by insulation rather than physical separation, Reg 528.1 requires every cable or conductor sharing the system to be insulated for the highest voltage present.
  • Segregation of Band I from Band II circuits is an item on the standard schedule of inspections, cited against Reg 528.1 — so it will be looked for on an EICR.

09 · Installation Guide

FP200 Gold vs MICC: Advantages and Disadvantages

Both are accepted by BS 7671 — MICC under Reg 560.8.1(a), FP200 Gold under Reg 560.8.1(c) — so the choice is practical rather than regulatory. The trade is installation speed against fire performance headroom.

 FP200 GoldMICC
BS 7671 route560.8.1(c) — BS EN 50200 / BS 8434 / BS 8491560.8.1(a) — BS EN 60702-1 and -2
TerminationConventional strippers, standard screw terminals, fire-rated glandsPot, seal and crimping tool; termination must be completed before moisture ingress
Labour costLower — no specialist kit, faster per terminationHigher — skilled terminations, more time per gland
Material costLower per metre; inexpensive accessoriesHigher per metre; termination kits add significantly
RoutingFlexible — suits congested ceiling voids and risersStiff; larger sizes need a bending former
Fire performance headroomAdequate for the great majority of alarm and emergency lighting circuitsHigher — the usual choice where the fire strategy demands extended duration or severe exposure
Mechanical damagePolymer sheath — needs protection where impact is likelyCopper sheath — inherently robust

For most fire alarm and emergency lighting projects in commercial and residential buildings FP200 Gold is the sensible choice. MICC earns its cost where the exposure is severe or the required duration is long — plant and generator rooms, tunnels, and firefighting systems under BS 8519. See the MICC cable guide for termination detail on mineral insulated cable.

10 · Installation Guide

For Electricians: Testing and Certifying Fire Alarm Wiring

Fire alarm and emergency lighting installations are certified by a competent person working to BS 5839-1 and BS 5266-1. The electrical certification should record that a cable meeting one of the Reg 560.8.1 routes has been used, and that the fixings, glands and penetrations support the duration the fire strategy requires.

Insulation resistance on fire alarm circuits

The NOTE to BS 7671 Reg 643.3.2 is explicit: more specific requirements are applicable for the wiring of fire detection and fire alarm systems in buildings — see BS 5839-1. The Table 64 regime (500 V DC and a minimum 1.0 MΩ for circuits up to and including 500 V) is the BS 7671 baseline, not a substitute for the commissioning tests BS 5839-1 calls for. Where connected equipment could influence or be damaged by the test, Reg 643.3.3 requires the Table 64 test before connection and then a 250 V DC test between live conductors and the protective conductor after connection, with a minimum of 1 MΩ.

A note on batteries

Chapter 57 (Stationary secondary batteries) is new at A4:2026, but Reg 570.1 excludes secondary batteries wholly within fire detection and fire alarm systems conforming to the BS 5839 series, and within emergency lighting conforming to the BS 5266 series. A standard panel battery or luminaire battery pack is therefore outside Chapter 57 — a separate battery installation supplying the wider system is not.

In the app

Certify fire alarm wiring installations on your phone

Record cable types, fixing methods, test results and BS 5839-1 compliance detail on site, then generate the PDF before you leave.

Frequently Asked Questions About FP200 Gold Fire-Resistant Cable

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Complete Fire Alarm Installation Certificates on Your Phone

Join 1,000+ UK electricians using Elec-Mate to certify fire alarm and emergency lighting installations on site. Record cable types, test results, and BS 5839-1 compliance — instant PDF export. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy