INSTALLATION GUIDE

FP200 Gold Fire Resistant Cable: UK Installation Guide

Everything electricians need to know about FP200 Gold fire-resistant cable — BS 7629-1 compliance, 105°C temperature rating, correct clipping and support, BS 5839 and BS 5266 requirements, and how it compares to mineral insulated cable.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is FP200 Gold cable used for?

FP200 Gold is a fire-resistant cable used for life-safety circuits — fire alarm systems (to BS 5839) and emergency lighting (to BS 5266) — where the cable must keep working during a fire. It is manufactured to BS 7629-1, withstands around 105°C continuous operation, and is a lighter, easier-to-install alternative to mineral-insulated (MICC) cable. It must be clipped with fire-resistant fixings so it stays supported when exposed to fire.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1FP200 Gold is a fire-resistant cable compliant with BS 7629-1 / BS EN 50200, designed to maintain circuit integrity during a fire — powering fire alarm and emergency lighting systems when they are needed most.
  • 2FP200 Gold has a continuous operating temperature rating of 105°C and is designed to maintain circuit integrity at 930°C for a minimum of 30 minutes (BS 7629-1 standard).
  • 3BS 7671 Reg 560.8.1 requires fire-resistant wiring for safety services and lists four permitted routes — MICC, IEC 60331, BS EN 50200/BS 8434/BS 8491 cables (which FP200 Gold satisfies), and constructional protection.
  • 4BS 5839-1 (fire detection and alarm systems) and BS 5266-1 (emergency lighting) both require fire-resistant cabling — FP200 Gold satisfies these requirements for most building types.
  • 5Circuit integrity depends on the entire cable system. Fire-rated glands and termination enclosures are mandatory — using standard glands at entries or panels will void the fire performance of the installation.
  • 6OSG Reg 7.4.1 requires — not merely recommends — that fire alarm and emergency lighting circuits are segregated from other cables and from each other, in compliance with BS 5839-1 and BS 5266-1 respectively.
  • 7FP200 Gold must be installed using fire-resistant clips and fixings. Standard plastic cable clips will fail in a fire, defeating the purpose of using fire-resistant cable.
  • 8Unlike MICC (mineral insulated cable), FP200 Gold uses conventional twisted conductors in an enhanced insulation system and does not require specialist crimping tools or moisture-sensitive termination kits.
01 · Installation Guide

What is FP200 Gold Fire-Resistant Cable?

FP200 Gold is a fire-resistant electric cable manufactured by Prysmian, designed specifically for use in life-safety circuits that must continue to function during a fire. It is the UK's most widely installed fire-resistant cable for fire alarm systems, emergency lighting, and other circuits where circuit integrity in a fire is mandatory.

Unlike standard PVC-insulated cables, which fail rapidly in a fire, FP200 Gold is engineered with an enhanced insulation system comprising a layer of mica tape and glass fibre beneath the LSOH (Low Smoke, Zero Halogen) outer sheath. This construction allows the cable to maintain electrical continuity even while exposed to direct flame — keeping fire alarm sounders operating and emergency lighting illuminated during evacuation.

  • Circuit integrity under fire — designed to maintain circuit function at flame temperatures of 930°C for a minimum of 30 minutes per BS 7629-1.
  • Low smoke, zero halogen — the outer sheath produces minimal smoke and no corrosive halogen gases when burning, reducing toxic risk to occupants and fire crews.
  • Easy installation — terminated with conventional tools. No specialist crimping equipment required, unlike MICC cable.

FP200 Gold is available in single-core, 2-core, 3-core, and multi-core variants in conductor sizes from 1mm² to 4mm² for fire protection applications. The red outer sheath colour is conventional for fire alarm cabling in the UK, though cream or white sheath variants exist for use where red would be visually unacceptable.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Temperature Rating and BS 7629-1 Standard

FP200 Gold has a continuous operating temperature rating of 105°C — significantly higher than standard PVC cables rated at 70°C. More importantly, it is designed to maintain circuit integrity under direct fire exposure, which is the requirement tested under BS 7629-1.

  • BS 7629-1:2014 compliance — the standard specifies cable construction, testing methods, and performance criteria. Cables are tested at 930°C flame temperature whilst subjected to simultaneous water spray (simulating fire suppression) and mechanical shock.
  • 30-minute minimum integrity — the cable must maintain circuit continuity for at least 30 minutes under the BS 7629-1 fire test conditions. FP200 Gold is tested to maintain integrity beyond this minimum.
  • Voltage rating — FP200 Gold is rated at 300/500V, suitable for mains voltage fire alarm power supplies and low-voltage detection circuits.
  • CPR classification — BS 7671 Reg 527.1.3 (A4:2026) requires that cables satisfy CPR reaction-to-fire requirements in addition to their electrical requirements. FP200 Gold carries a Cca-s1b,d1,a1 classification under the Construction Products Regulation (EU 305/2011 as retained in UK law). Specifiers should note that BS 7671 Reg 253.0 (Note) confirms that in the UK, MHCLG has not exercised CPR powers to set mandatory minimum reaction-to-fire performance levels for cables in specific applications — so the Cca-s1b,d1,a1 rating is a specification and CPR labelling requirement rather than a BS 7671 mandatory minimum. Project specifications and procurement documents should call up the required CPR class explicitly.

Specifiers and system designers should verify that the cable selected for a project meets the required circuit integrity class (30, 60, or 90 minutes) and any additional project-specific fire engineering requirements. The 30-minute minimum of BS 7629-1 is the baseline — some specifications require 60 or 90 minutes.

03 · Installation Guide

BS 7671 Legal Requirements for Fire-Resistant Wiring

The legal obligation to use fire-resistant wiring for safety services comes from BS 7671 Chapter 56. Reg 560.5.1 requires that safety services are capable of operating during mains failure and fire conditions — which means the wiring itself must maintain circuit integrity throughout the fire event. Reg 560.8.1 specifies the wiring systems that satisfy this obligation.

Reg 560.8.1 — Four Permitted Wiring Systems for Safety Services

  • (a) Mineral insulated cable — complying with BS EN 60702-1 and BS EN 60702-2, also tested to BS EN 60332-1-2. This is MICC/Pyrotenax cable.
  • (b) Fire-resistant cables complying with IEC 60331-1, -2 or -3 — the IEC circuit-integrity test series, also tested to BS EN 60332-1-2.
  • (c) Fire-resistant cables complying with BS EN 50200, BS 8434 or BS 8491 — these are the test standards that BS 7629-1 cables such as FP200 Gold are assessed against. FP200 Gold satisfies this route.
  • (d) A wiring system maintaining the necessary fire and mechanical protection — for example, cables in concrete embedment or a fully fire-protected enclosure system.

BS 7629-1 is the underlying product standard for cables tested to route (c) — it is not itself named in Reg 560.8.1, which means IEC 60331 cables are an equally valid BS 7671 route. The selected wiring system must also meet the requirements of the relevant code of practice for the application (typically BS 5839-1 for fire alarms and BS 5266-1 for emergency lighting). Always confirm that the specific cable selected meets the correct test standard for the integrity class (30, 60, or 90 minutes) required by the system design.

04 · Installation Guide

Requirements Under BS 5839 and BS 5266

The two key standards requiring fire-resistant cabling in UK buildings are BS 5839-1 (fire detection and alarm systems) and BS 5266-1 (emergency lighting). Both standards are referenced in the Building Regulations Approved Documents and in insurers' requirements for commercial properties.

  • BS 5839-1:2017 (Fire Alarm Systems) — requires that all cables in a fire alarm system either comply with BS 7629-1 (enhanced fire protection cables such as FP200 Gold) or are mineral insulated copper sheathed (MICC) cables. This requirement applies to detector circuits, sounder circuits, power supplies, panel interconnects, and all associated wiring. Cables routed through areas of high fire risk must be especially carefully considered.
  • BS 5266-1:2016 (Emergency Lighting) — requires that cables serving escape route luminaires and open area emergency lighting be fire-resistant in buildings where the loss of the circuit in a fire could compromise safe evacuation. FP200 Gold satisfying BS 7629-1 meets this requirement. The standard also requires that cable routes are designed to minimise fire exposure and that multiple circuits are segregated.
  • Building Regulations Approved Document B — references both BS 5839-1 and BS 5266-1 as part of fire safety requirements for new and significantly altered buildings. Compliance with these standards is required for Building Regulations sign-off on commercial, institutional, and multi-occupancy residential buildings.

For domestic premises, fire alarm wiring is typically low-risk and standard cable may be acceptable for Grade D (mains-powered with battery backup) systems. However, for Grade A systems or any commercial or institutional building, FP200 Gold or equivalent is required. Always follow the current edition of BS 5839-1 and the specific project risk assessment.

05 · Installation Guide

Installation Requirements for FP200 Gold Cable

The purpose of FP200 Gold is to maintain circuit integrity during a fire. Installation method is critical — a fire-resistant cable poorly installed can fail before its rated time due to fixings falling away or the cable being exposed to greater fire load than accounted for in the design.

  • Fire-resistant fixings — use metal cable clips, steel saddles, or approved fire-resistant cable cleats. Standard white plastic cable clips melt at temperatures well below those in a building fire, releasing the cable. This is one of the most common installation errors found on fire alarm audits.
  • Support spacing — BS 5839-1 recommends support spacing in accordance with the cable manufacturer's data. For FP200 Gold, typical support spacing is 250mm horizontal and 400mm vertical on surface runs.
  • Route segregation — mandatory requirement — OSG Reg 7.4.1 requires that fire alarm and emergency lighting circuits are separated from other cables and from each other. Compliance with BS 5839-1 is required for fire alarm circuit segregation, and compliance with BS 5266-1 for emergency lighting circuit segregation. This is a compliance requirement, not a best-practice recommendation. Failure to segregate is a notifiable defect on inspection.
  • Fire stopping — all penetrations through fire-rated walls, floors, and ceilings must be fire stopped with an approved intumescent system. FP200 Gold must not be routed through penetrations that have not been properly fire stopped.
  • Minimum bend radius — the minimum bend radius for FP200 Gold is 6× the overall cable diameter for fixed wiring (8× during installation). Overbending can damage the mica tape layer and compromise fire performance.
  • Fire-rated glands and termination accessories are essential — fire performance depends on the complete cable system, not the cable alone. Glands at panel entries, junction box entries, and conduit entries must be fire-rated products specified by the manufacturer. Using standard cable glands at these points is one of the most common installation failures on fire alarm audits — it voids the circuit-integrity rating of the cable at the point of termination. Manufacturer-approved fire-rated termination assemblies must be used throughout.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £5.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Installation Guide

FP200 Gold vs MICC Cable: Choosing the Right Cable

Both FP200 Gold and Mineral Insulated Copper Clad (MICC) cable are accepted for fire-resistant applications under BS 5839-1 and BS 5266-1. Each has advantages and disadvantages for different applications.

  • FP200 Gold — easier installation — stripped with conventional tools, terminated in standard screw terminals, jointed in standard junction boxes. Lower installation labour cost. No specialist equipment required. Better suited to most fire alarm and emergency lighting installations.
  • MICC — greater fire resistance — mineral insulated cable can withstand significantly higher temperatures and longer fire exposure times than FP200 Gold. MICC is preferred for high-risk environments, power circuits in extreme conditions, and installations requiring 90-minute or greater circuit integrity.
  • Cost comparison — FP200 Gold is significantly cheaper per metre than MICC cable. MICC termination kits are expensive and require specialist tools. For standard fire alarm and emergency lighting circuits, FP200 Gold is the cost-effective choice. MICC is reserved for applications where its superior performance is genuinely required.
  • Flexibility — FP200 Gold is more flexible than MICC cable and easier to route in congested ceiling voids and riser ducts. MICC is stiffer and requires a bending former for larger sizes.

For most standard fire alarm and emergency lighting projects in commercial and residential buildings, FP200 Gold is the preferred choice. MICC is specified where extreme fire conditions are expected, such as generator room wiring, tunnel lighting, or power circuits in petrochemical facilities. See the MICC cable guide for full details on mineral insulated cable installation.

07 · Installation Guide

Clipping and Support Spacing for FP200 Gold

Correct clipping is essential for FP200 Gold installations. The clips must hold the cable in position throughout the duration of the fire so that the cable does not fall away from its intended route and expose unprotected lengths to the fire.

  • Horizontal runs — clip at maximum 250mm centres for 1.5mm² and 2.5mm² cable. Larger cables may allow slightly greater spacing — refer to the Prysmian FP200 Gold installation guide.
  • Vertical runs — clip at maximum 400mm centres. Gravity loading on a vertical run during a fire is greater than on a horizontal run, so vertical clips must grip the cable firmly.
  • Approved clip types — Prysmian's own FP200 Gold metal clips (red and white) are specifically tested and rated for use with FP200 Gold. Third-party metal clips and steel saddles are acceptable provided they are rated for the fire conditions.
  • Not acceptable — standard oval or round white PVC cable clips, nylon cable ties used as the sole fixing, and self-adhesive cable clips are all unacceptable for FP200 Gold and will fail in a fire.
08 · Installation Guide

For Electricians: Certifying Fire Alarm Wiring

Fire alarm and emergency lighting installations must be certified by a competent person familiar with BS 5839-1 and BS 5266-1. The certification must include evidence that fire-resistant cable complying with BS 7629-1 (or another BS 7671 Reg 560.8.1 permitted route) has been used and that fixings and glands are fire-rated.

Testing: BS 7671 IR test regime does not fully apply to fire alarm circuits

BS 7671 Reg 643.3.2 Note states that more specific testing requirements apply to fire detection and alarm system wiring — see BS 5839-1. The standard 500 V DC insulation resistance test regime in Table 64 is not a substitute for the commissioning tests required by BS 5839-1. Where stationary secondary batteries form part of the installation (e.g., emergency lighting battery packs or fire alarm panel batteries), Reg 560.11 requires that Chapter 57 (Stationary Secondary Batteries) is also complied with, and certificates should reference this compliance.

Issue Fire Alarm Certificates on Site

Use the Elec-Mate certificate app to complete and issue electrical certificates for fire alarm and emergency lighting installations on site. Record cable types, fixing methods, test results, and BS 5839-1 compliance details — generate the PDF before you leave.

Certify fire alarm wiring installations on your phone

Elec-Mate's certificate app lets you complete EICs and fire alarm installation certificates on site.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About FP200 Gold Fire-Resistant Cable

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Complete Fire Alarm Installation Certificates on Your Phone

Join 1,000+ UK electricians using Elec-Mate to certify fire alarm and emergency lighting installations on site. Record cable types, test results, and BS 5839-1 compliance — instant PDF export. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £5.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £5.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £5.99/mo after trial

Cookie Preferences

Manage your privacy settings

We use cookies to enhance your experience and analyse platform usage. Cookie Policy