There is no such thing as “the rating of 10 mm² SWA”. The tabulated value depends on the cable standard, the reference method, and then the correction factors for your site. Work through it in that order.
Step 1 — pick the right reference method
Appendix 4 defines the installation conditions each column of a rating table assumes. Getting D1 and D2 the wrong way round is a common and expensive error: burying direct dissipates heat better than a duct, so D2 carries the higher rating.
| Reference Method | Condition | Assumed by the table |
|---|
| C | Clipped direct to a surface | 30 °C ambient air (Table 4B1) |
| D1 | Multicore armoured cable in conduit or cable ducting in the ground | 100 mm duct, 20 °C ground, soil 2.5 K·m/W, laid at 0.7 m |
| D2 | Multicore armoured cable direct in the ground | 20 °C ground, soil 2.5 K·m/W, laid at 0.7 m |
| E | Multicore cable in free air | Heat dissipation unimpeded, clearance at least 0.3 × cable diameter |
Appendix 4 notes that D1 and D2 values are based on conservative installation parameters. Where the actual ground thermal resistance, ground ambient temperature and cable depth are known, the cable manufacturer or the ERA 69-30 series may support a smaller cable.
Step 2 — read Iz from the table that matches the cable
Do not carry a number across from another table. For 90 °C thermosetting armoured cable to BS 5467 or BS 6724, multicore ratings are in Table 4E4A and voltage drop in Table 4E4B. For 70 °C thermoplastic armoured cable, the equivalents are Tables 4D4A and 4D4B. Aluminium conductor cables use the 4J series.
Indicative only. The figures below are rough magnitudes for copper multicore armoured cable, given so you can sanity-check a design — they are not a substitute for reading the value out of the correct Appendix 4 table for the cable you are installing.
| Size | Buried (approx.) | Clipped direct (approx.) | Typical application |
|---|
| 4 mm² 2-core | 44 A | 36 A | Small sub-feeds, garden supplies |
| 10 mm² 2-core | 73 A | 61 A | Cooker circuits, moderate sub-mains |
| 25 mm² 4-core | 130 A | — | Three-phase sub-mains to distribution boards |
| 95 mm² 4-core | 265 A | — | Large three-phase distribution feeds |
Step 3 — apply the correction factors
Each factor has its own symbol and its own table. Applying the wrong one — or an invented “installation method multiplier” on top of a tabulated column — is how cables end up undersized.
| Factor | What it corrects for | Table |
|---|
| Ca | Ambient air temperature other than 30 °C | 4B1 |
| Ca | Ambient ground temperature other than 20 °C | 4B2 |
| Cs | Soil thermal resistivity other than 2.5 K·m/W, cables buried direct or in underground conduit | 4B3 |
| Cd | Depth of laying other than 0.7 m, direct buried cables and cables in buried ducts | 4B4 |
| Cg | Grouping — more than one circuit buried directly in the ground | 4C2 |
| Cg | Grouping — more than one circuit in ducts buried in the ground | 4C3 |
Two further factors catch people out on buried SWA. Under Regulation 433.1.203, for direct buried cables and cables in buried ducts, condition (c) of Regulation 433.1.1 is satisfied where the rated current of the protective device does not exceed 0.9 times the current-carrying capacity of the lowest rated conductor — an effective 0.9 factor on Iz. And under Regulation 433.1.202, where the protective device is a semi-enclosed fuse to BS 3036, the factor is 0.725.
Step 4 — check voltage drop
Appendix 4, Section 6.4 and Table 4Ab give the voltage drop between the origin of an installation and any load point, expressed against the nominal voltage.
| Supply | Lighting | Other uses |
|---|
| Low voltage installation supplied directly from a public low voltage distribution system | 3% | 5% |
| Low voltage installation supplied from a private LV supply | 6% | 8% |
On a private LV supply the voltage drop within each final circuit should still not exceed the 3% and 5% figures. SWA runs are often long, and Table 4Ab allows for that: where the wiring systems of the installation are longer than 100 m, the values above may be increased by 0.005% per metre beyond 100 m, without that increase being greater than 0.5%. The calculated voltage drop should include any effects due to harmonic currents.