INSTALLATION GUIDE

Armoured Cable Installation UK: SWA Cable Guide

Everything electricians need to know about Steel Wire Armoured (SWA) cable — core configurations, which Appendix 4 table to read, correct gland termination for earth continuity, underground burial depths, IP ratings, and the mistakes that generate EICR observations.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

How do you connect armoured cable correctly?

Strip the outer sheath, fan and trim the armour square, then slide the shroud onto the cable first, followed by the back-nut and cone. Draw the cone under the armour with the back-nut so the wires are clamped firmly but not crushed. Fit an earth tag under the lock-nut and run a green/yellow tail to the enclosure earth bar. Do exactly the same at both ends — the armour is the circuit protective conductor.

BS 7671 Regulation 543.2.1(e) permits the armouring of a cable to be used as a protective conductor. Regulation 543.2.7 requires the earthing terminal of each accessory to be connected by a separate protective conductor to an earthing terminal in the associated box or enclosure where the CPC is formed by the armour.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Regulation 522.8.10: except where it runs in a conduit or duct giving equivalent protection against mechanical damage, a cable buried in the ground shall incorporate an earthed armour or metal sheath (or both) suitable for use as a protective conductor. SWA satisfies that on its own — no separate duct is required.
  2. 02Regulation 543.2.1(e) allows the armouring of a cable to be the circuit protective conductor, so the armour is earthed at both ends through the gland. Its cross-sectional area still has to satisfy Regulation 543.1.1 — calculated by the adiabatic equation of 543.1.3 or selected in accordance with 543.1.4.
  3. 03BS 7671 sets no general burial depth. Regulation 522.8.10 requires a sufficient depth to avoid damage from any reasonably foreseeable disturbance of the ground, and requires the location of buried cables to be marked by cable covers or a suitable marker tape.
  4. 042-core SWA uses the armour as the CPC. 3-core carries line, neutral and a dedicated earth core (or three lines in a delta circuit). 4-core carries three lines and a neutral with the armour as the CPC. 5-core adds a separate earth core.
  5. 05Read the current rating from the Appendix 4 table that matches the cable you are actually installing: Table 4E4A for 90 °C thermosetting (XLPE / LSZH) armoured cable to BS 5467 or BS 6724, Table 4D4A for 70 °C thermoplastic armoured cable. Reference Method D2 is direct in the ground; D1 is in a duct in the ground.
  6. 06Buried ratings assume 20 °C ground temperature, 0.7 m depth of laying and soil of 2.5 K·m/W. Apply Ca, Cg, Cs and Cd where site conditions differ — and note Regulation 433.1.203, under which overload protection of a buried cable is satisfied where In does not exceed 0.9 × Iz.
  7. 07Voltage drop: Appendix 4 Table 4Ab gives 3% for lighting and 5% for other uses, measured from the origin, on a low voltage installation supplied directly from a public distribution system.
  8. 08Always fit the gland shroud over the cable before fitting the gland body — once the gland is tightened onto the enclosure the shroud cannot be fitted retrospectively.

01 · Installation Guide

What is Steel Wire Armoured (SWA) Cable?

Steel Wire Armoured (SWA) cable is a multi-core power cable for fixed wiring where mechanical protection is required. It is the default choice for underground runs, external sub-mains between buildings, and industrial and commercial wiring exposed to accidental damage.

The construction is a copper or aluminium conductor, insulation on each core, a bedding layer, a layer of galvanised steel wires laid helically around the cable (the armour), and an outer sheath. The armour does two jobs: it takes the mechanical punishment, and when correctly terminated it acts as the circuit protective conductor for the circuit.

The regulation that puts SWA underground

Regulation 522.8.10 is the one that matters and it is worth reading in full. Except where installed in a conduit or duct which provides equivalent protection against mechanical damage, a cable buried in the ground shall incorporate an earthed armour or metal sheath or both, suitable for use as a protective conductor. The location of buried cables shall be marked by cable covers or a suitable marker tape. Buried cables, conduits and ducts shall be at a sufficient depth to avoid being damaged by any reasonably foreseeable disturbance of the ground.

That is why plain twin-and-earth in a garden trench fails an inspection and SWA does not. SWA already carries an earthed armour suitable for use as a protective conductor, so it needs no additional duct — only depth and marking.

Which British Standard is the cable made to?

The standard printed on the sheath decides which Appendix 4 rating table applies. BS 7671 Table 4A3 sets out the mapping.

Cable standardInsulationConductor operating temp.Appendix 4 tables
BS 5467Thermosetting (XLPE), armoured90 °C4E3 single-core, 4E4 multicore
BS 6724Thermosetting, armoured, low emission of smoke and corrosive gases90 °C4E3 single-core, 4E4 multicore
BS 6346 (withdrawn)PVC insulated, armoured70 °C4D3 single-core, 4D4 multicore

BS 6346 is retained in BS 7671 Table 4A3 for historical purposes only — the standard is withdrawn. New SWA bought in the UK today is normally BS 5467, or BS 6724 where a low smoke and fume cable is specified for escape routes and public buildings. Both are 90 °C thermosetting cables rated from Tables 4E3 and 4E4, not the 70 °C 4D tables.

Regulation 522.6.204(a) also names BS 5467 and BS 6724 among the cables accepted as incorporating an earthed metallic covering complying with the requirements for a protective conductor of the circuit concerned.

Install in accordance with BS 7671:2018+A4:2026 and the associated IET Guidance Notes.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Types and Core Configurations

The core count decides where the earth comes from. Get this wrong and either the CPC is undersized or you have paid for a core you never connect.

CoresConductorsCircuit protective conductorTypical use
2-coreLine, neutralArmourSingle-phase sub-mains to outbuildings, garden offices and garages
3-coreLine, neutral, earth — or three lines (delta)Dedicated earth core, armour in parallelSingle-phase runs needing a larger CPC than the armour gives; three-phase delta loads with no neutral
4-coreThree lines, neutralArmourThree-phase and neutral distribution — sub-mains, distribution boards, machinery
5-coreThree lines, neutral, earthDedicated earth core, armour in parallelThree-phase runs where a separate CPC is specified in addition to the armour

Whichever configuration you choose, the CPC has to satisfy Regulation 543.1.1 — either calculated with the adiabatic equation of Regulation 543.1.3, or selected in accordance with Regulation 543.1.4. Where the armour alone will not carry the prospective earth fault current for the disconnection time, move up to a cable with a dedicated earth core.

Conductor sizes run from 1.5 mm² up to 400 mm² and beyond. Aluminium conductor SWA is used for large distribution cables where copper would be prohibitively heavy and expensive; it is rated from the 4H and 4J series of tables rather than the 4D and 4E series.

03 · Installation Guide

Current Ratings and Cable Sizing

There is no such thing as “the rating of 10 mm² SWA”. The tabulated value depends on the cable standard, the reference method, and then the correction factors for your site. Work through it in that order.

Step 1 — pick the right reference method

Appendix 4 defines the installation conditions each column of a rating table assumes. Getting D1 and D2 the wrong way round is a common and expensive error: burying direct dissipates heat better than a duct, so D2 carries the higher rating.

Reference MethodConditionAssumed by the table
CClipped direct to a surface30 °C ambient air (Table 4B1)
D1Multicore armoured cable in conduit or cable ducting in the ground100 mm duct, 20 °C ground, soil 2.5 K·m/W, laid at 0.7 m
D2Multicore armoured cable direct in the ground20 °C ground, soil 2.5 K·m/W, laid at 0.7 m
EMulticore cable in free airHeat dissipation unimpeded, clearance at least 0.3 × cable diameter

Appendix 4 notes that D1 and D2 values are based on conservative installation parameters. Where the actual ground thermal resistance, ground ambient temperature and cable depth are known, the cable manufacturer or the ERA 69-30 series may support a smaller cable.

Step 2 — read Iz from the table that matches the cable

Do not carry a number across from another table. For 90 °C thermosetting armoured cable to BS 5467 or BS 6724, multicore ratings are in Table 4E4A and voltage drop in Table 4E4B. For 70 °C thermoplastic armoured cable, the equivalents are Tables 4D4A and 4D4B. Aluminium conductor cables use the 4J series.

Indicative only. The figures below are rough magnitudes for copper multicore armoured cable, given so you can sanity-check a design — they are not a substitute for reading the value out of the correct Appendix 4 table for the cable you are installing.

SizeBuried (approx.)Clipped direct (approx.)Typical application
4 mm² 2-core44 A36 ASmall sub-feeds, garden supplies
10 mm² 2-core73 A61 ACooker circuits, moderate sub-mains
25 mm² 4-core130 AThree-phase sub-mains to distribution boards
95 mm² 4-core265 ALarge three-phase distribution feeds

Step 3 — apply the correction factors

Each factor has its own symbol and its own table. Applying the wrong one — or an invented “installation method multiplier” on top of a tabulated column — is how cables end up undersized.

FactorWhat it corrects forTable
CaAmbient air temperature other than 30 °C4B1
CaAmbient ground temperature other than 20 °C4B2
CsSoil thermal resistivity other than 2.5 K·m/W, cables buried direct or in underground conduit4B3
CdDepth of laying other than 0.7 m, direct buried cables and cables in buried ducts4B4
CgGrouping — more than one circuit buried directly in the ground4C2
CgGrouping — more than one circuit in ducts buried in the ground4C3

Two further factors catch people out on buried SWA. Under Regulation 433.1.203, for direct buried cables and cables in buried ducts, condition (c) of Regulation 433.1.1 is satisfied where the rated current of the protective device does not exceed 0.9 times the current-carrying capacity of the lowest rated conductor — an effective 0.9 factor on Iz. And under Regulation 433.1.202, where the protective device is a semi-enclosed fuse to BS 3036, the factor is 0.725.

Step 4 — check voltage drop

Appendix 4, Section 6.4 and Table 4Ab give the voltage drop between the origin of an installation and any load point, expressed against the nominal voltage.

SupplyLightingOther uses
Low voltage installation supplied directly from a public low voltage distribution system3%5%
Low voltage installation supplied from a private LV supply6%8%

On a private LV supply the voltage drop within each final circuit should still not exceed the 3% and 5% figures. SWA runs are often long, and Table 4Ab allows for that: where the wiring systems of the installation are longer than 100 m, the values above may be increased by 0.005% per metre beyond 100 m, without that increase being greater than 0.5%. The calculated voltage drop should include any effects due to harmonic currents.

04 · Installation Guide

Stripping and Terminating SWA Cable

The gland is not just a cable entry. On a 2-core or 4-core cable it is the joint in the circuit protective conductor, so a poor termination is an earthing fault, not a cosmetic one.

  1. 1 — Measure and mark

    Measure the depth of the gland entry plus the length of armour the cone has to grip. Mark the outer sheath. Allow extra length inside the enclosure for dressing and connecting the cores.

  2. 2 — Remove the outer sheath

    Score around the sheath with a sharp knife without cutting into the armour, bend the cable to crack it, and pull the section off. An armoured cable stripping tool is safer and gives a cleaner cut.

  3. 3 — Dress the armour

    Fan out and straighten the steel wires, then cut them square to length with sharp side cutters. Uneven armour gives poor cone grip and a high-resistance earth path.

  4. 4 — Fit the shroud first

    Slide the shroud onto the cable before anything else. Once the gland is tightened onto the enclosure the shroud cannot be passed over it, and it cannot be retrofitted without stripping the termination back. This is the single most common SWA termination error on site.

  5. 5 — Fit the gland

    Slide the back-nut then the cone over the armour, taper facing the gland body. Feed the cable through the entry, then tighten the back-nut to draw the cone under the armour and clamp the wires. Firm, not crushed — over-tightening cuts the wires you are relying on.

  6. 6 — Make the earth connection

    Fit an earth tag between the gland body and the enclosure lock-nut and run a green/yellow conductor from the tag to the earth bar. Regulation 543.2.7: where the protective conductor is formed by the metal sheath or armour of a cable, the earthing terminal of each accessory shall be connected by a separate protective conductor to an earthing terminal incorporated in the associated box or other enclosure.

Verifying the termination

Prove continuity of the armour with a low-resistance ohmmeter from end to end, then measure earth fault loop impedance and compare it with the maximum for the protective device: Table 41.2 for fuses on a 0.4 s disconnection time, Table 41.3 for circuit-breakers, and Table 41.4 for fuses on a 5 s disconnection time.

Those tabulated values assume the conductor is at its normal operating temperature, and on site you are usually testing a cold cable. Appendix 3 gives the correction: the requirement is considered met where the measured loop impedance Zs(m) does not exceed 0.8 × (U₀ × Cmin / Ia) — that is, 0.8 times the tabulated limit, or equivalently multiply your measured Zs by 1.25 before comparing. For a low voltage supply given in accordance with the ESQCR, Cmin is 0.95. Appendix 3 also notes this is one method of correcting for temperature and others are not precluded.

05 · Installation Guide

Underground Burial Depth Requirements

Regulation 522.8.10 sets a performance requirement, not a number: buried cables, conduits and ducts shall be at a sufficient depth to avoid being damaged by any reasonably foreseeable disturbance of the ground. There is no general depth figure in BS 7671 for an ordinary domestic or commercial run — the depth has to be justified against the risk on that site.

Where BS 7671 does put a figure on it, it does so for particular locations. These are the depths the standard itself uses, and they are widely adopted as practical minima elsewhere.

LocationDepthStatusReference
Caravan and camping parks — distribution circuits0.6 mGenerally considered a minimum (NOTE). Alternatively install outside the pitch area where tent pegs or ground anchors may be driven708.521.7.2
Marinas — distribution cables0.5 mGenerally considered a minimum (NOTE)709.521.1.7
Agricultural premises — areas where vehicles and mobile agricultural machines operate0.6 mRequirement, with added mechanical protectionSection 705
Agricultural premises — arable or cultivated ground1 mRequirementSection 705

In each case the depth is only excused where additional mechanical protection is provided. In practice that means deeper under anything carrying vehicles than under a footpath or border, and deeper again where groundworks or machinery are foreseeable.

Remember the rating consequence as well as the safety one: Appendix 4 tabulates buried ratings at a depth of laying of 0.7 m. Bury shallower or deeper and Cd from Table 4B4 applies.

Marking and bedding

Regulation 522.8.10 requires the location of buried cables to be marked by cable covers or a suitable marker tape, and buried conduits and ducts to be suitably identified. That marking is the regulatory requirement — surface route marker posts and as-fitted drawings are sound practice that make the route traceable later, but they are not what 522.8.10 asks for and they do not replace tape or covers.

Lay the cable on fine sand or selected fill free from sharp stones, glass and debris, cover with further selected fill, then lay the warning tape or covers above it for the full run before backfilling.

PME / TN-C-S earthing when you feed an outbuilding

BS 7671 does not ban exporting a PME earth to an outbuilding, and the myth that it does causes as many bad installations as the practice itself. What it requires is that every extraneous-conductive-part in that building is main bonded, with the bonding conductor selected under Regulation 544.1.1 in accordance with the characteristics of the distribution circuit protective conductor for that particular building — not less than 6 mm², and need not exceed 25 mm² in copper. Where those parts cannot be reliably bonded, a TT arrangement with a local electrode is the correct answer and the exported earth must then be kept separate.

Two specifics worth knowing. On agricultural and horticultural premises, Regulation 705.411.4 NOTE 2 says the use of a PME earthing facility as the means of earthing is not recommended unless a metal grid is laid in the floor. And Regulation 709.411.4 records that the ESQCR prohibit connecting a PME earthing facility to any metalwork in a boat — though not to the installations of permanent buildings. Regulation 411.4.2 recommends an additional earth electrode at the main earthing terminal, but expressly excludes outbuildings of dwellings served by the installation from that recommendation.

Where minimum depth cannot be achieved — a shallow area of bedrock, for example — provide supplementary mechanical protection such as duct, tiles or concrete encasement, and record the route on as-fitted drawings retained for the life of the installation.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

06 · Installation Guide

IP Ratings for SWA Glands

The gland has to suit the environment it sits in. A gland with too low an IP rating lets moisture and dust into the termination, and the first thing to degrade is the earth path through the armour.

RatingProtectionWhere it is appropriate
IP54Dust protected, splashing waterIndoor locations with dust or occasional splash — garages, plant rooms. Not for outdoor or underground use
IP66Dust tight, powerful water jetsThe normal minimum for outdoor glands and cable entry into external enclosures
IP68Dust tight, continuous immersionEntries into pits, chambers and below-ground enclosures, and where cables pass through below-ground walls

The assembly is only as good as its weakest part: an IP68 gland in an IP66 enclosure gives you IP66. Match the gland to the enclosure rating or better, and choose the seal material — neoprene, EPDM or silicone — for the temperature and chemical exposure at that entry.

07 · Installation Guide

Common Mistakes in SWA Cable Installation

These are the SWA defects that turn up as observations on EICRs.

Five that keep recurring

  • Armour not earthed at one or both ends. The most dangerous of the set. An unearthed armour provides no fault protection and can become live if a conductor faults to it.
  • The wrong gland. A standard non-armoured gland grips only the outer sheath — no armour retention, no earth continuity, and nothing obvious to see from the outside.
  • Insufficient depth. Shallow cables are routinely struck during garden work and landscaping. Measure the depth and record it.
  • No cable covers or marker tape. Regulation 522.8.10 requires the location of buried cables to be marked by cable covers or a suitable marker tape. It is a requirement, not an optional extra.
  • Voltage drop not calculated over the real route length. SWA runs are long. Check the full length against Table 4Ab — 3% for lighting, 5% for other uses on a public LV supply.

08 · Installation Guide

For Electricians: Documenting SWA Installations

Certify every SWA installation with an Electrical Installation Certificate (EIC), or a Minor Electrical Installation Works Certificate where the work does not extend to a new circuit. Keep the cable sizing calculation and the as-fitted route drawing with the certificate — both are what a future inspector, and your own insurer, will ask for.

Certify on site

Use the Elec-Mate EIC certificate app to complete and issue the certificate before you leave. Record earth fault loop impedance, continuity of the armour, insulation resistance and the cable route description in the app, and send the PDF to the client on the spot.

Reviewed by Andrew Moore, founder of Elec-Mate. Content is grounded in BS 7671:2018+A4:2026 and the IET Guidance Notes series.

Frequently Asked Questions About SWA Armoured Cable Installation

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Certify SWA Cable Installations on Your Phone

Join 1,000+ UK electricians using Elec-Mate to complete Electrical Installation Certificates on site. Record test results, cable details, and route descriptions — instant PDF export. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy