DC EARTHING GUIDE

AC vs DC Earthing: Type B RCDs, Solar PV and EV Charging Requirements

Type A RCDs cannot detect smooth DC fault currents from three phase EV chargers and solar PV systems. BS 7671 Regulation 411.3.3 and Table 7.3(ii) require Type B RCDs where DC fault currents may occur. This guide explains the difference, when Type B is required, and how to earth DC circuits correctly.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1AC earthing follows the standard BS 7671 requirements for protective earthing, bonding, and residual current device selection. Type AC RCDs detect sinusoidal (AC) residual currents; Type A RCDs detect both AC and pulsating DC residual currents.
  • 2DC circuits from solar PV, battery storage, and EV chargers can produce smooth DC fault currents that Type A RCDs cannot detect. BS 7671 Regulation 411.3.3 and Table 7.3(ii) require Type B RCDs where smooth DC fault currents may occur.
  • 3A Type B RCD detects AC, pulsating DC, and smooth DC residual currents. It is required for EV charging equipment connected to a supply that could produce DC fault currents — typically EVSE with three phase rectification or DC-coupled systems.
  • 4Solar PV systems in the UK are typically IT earthing systems on the DC side — the DC conductors are ungrounded (not connected to earth). A ground fault on the DC side is detected by insulation monitoring and isolation monitoring devices, not by standard RCDs.
  • 5The protective earth (PE) conductor must be continuous on both the AC and DC sides of any installation. For solar PV, the mounting structure and inverter enclosure must be bonded to the installation earth via the PE conductor.
01 · DC Earthing Guide

AC vs DC Earthing: Solar PV, Battery Storage, and EV Charging

The rapid growth of solar PV, battery storage, and electric vehicle charging has introduced DC circuits into domestic and commercial electrical installations that were previously purely AC. DC circuits require different earthing, bonding, and protective device considerations to AC circuits — and the wrong protective device selection can leave a DC fault completely undetected.

The critical distinction is the type of residual current that a fault can produce. Standard Type AC and Type A RCDs are designed for AC and pulsating DC fault currents. They cannot detect smooth DC fault currents — which can occur in three phase EV chargers, solar PV inverters, and DC-coupled battery storage systems. BS 7671:2018+A4:2026 Regulation 411.3.3 and Table 7.3(ii) require Type B RCDs where smooth DC fault currents may occur.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · DC Earthing Guide

AC Earthing: Standard Requirements

AC earthing for standard electrical installations follows the requirements set out in BS 7671 Chapters 41 and 54. The earthing system (TN-S, TN-C-S, or TT) determines the available earth fault loop impedance and the type of protective device required. For AC circuits, the RCD types in common use are:

  • Type AC: Detects sinusoidal AC residual currents only. Used in older installations. Not suitable for circuits supplying equipment with electronic power supplies (switching chargers, variable speed drives). Being phased out of new installations.
  • Type A: Detects sinusoidal AC and pulsating DC residual currents. Suitable for most domestic and commercial circuits, including those supplying appliances with single phase rectifiers (washing machines, fridges, computers). Standard for new UK domestic consumer units.
  • Type B: Detects all residual current types including smooth DC. Required for three phase EV chargers, specific solar PV configurations, and systems that can produce smooth DC fault currents (BS 7671 Regulation 411.3.3 and Table 7.3(ii)).
03 · DC Earthing Guide

DC Earthing: Solar PV and Energy Storage Systems

DC circuits from solar PV and battery storage are typically ungrounded (IT earthing system) on the DC side. This means the DC positive and negative conductors are not connected to earth. This is different from AC earthing, where the neutral is earthed at the transformer.

DC IT Earthing System Characteristics

  • • DC positive (+) and DC negative (−) conductors are isolated from earth
  • • A single DC insulation fault does not immediately cause a dangerous fault current
  • • Inverter monitors insulation resistance between DC conductors and frame (earth)
  • • Insulation monitoring device (IMD) triggers alarm if insulation resistance falls below threshold
  • • A second fault on the opposite conductor creates a hazardous fault path
  • • DC ground fault current interrupters (GFCI) provide current protection

The metallic components of the DC installation (panel mounting structure, inverter enclosure, DC cable trunking) must be bonded to the installation protective earth via the PE conductor of the AC supply cable and additional bonding conductors where required. This bonding does not ground the DC conductors — it ensures that metal parts are at earth potential to prevent shock hazard from accidental contact.

04 · DC Earthing Guide

Type B RCD Requirement for DC Fault Currents

BS 7671 Regulation 411.3.3 states that where a circuit includes equipment that can produce DC residual currents that might impair the operation of a Type AC or Type A RCD, a Type B RCD must be used, or a Type A RCD with additional DC fault current detection provided by the equipment itself.

Why Type A RCDs Fail on DC Faults

A smooth DC fault current (from three phase rectification) passes through the toroidal core of a Type A RCD without causing any magnetic imbalance — the DC field is constant, not alternating, so the RCD core does not detect it. The RCD will not trip. A person in contact with the fault current path on the DC side will receive an electric shock that the RCD cannot interrupt.

Type B RCDs use additional sensing windings and a DC-sensitive measuring circuit to detect both AC and smooth DC residual currents, triggering the relay within the specified 300ms (or 40ms for 30mA instantaneous trip).

BS 7671 Table 7.3(ii) (in the EV charging section, Appendix 7) identifies where Type B RCDs are required for EV charging applications. The same principle applies to other DC-generating equipment — always check Table 7.3(ii) and the equipment manufacturer's installation manual for the specific RCD type requirement.

05 · DC Earthing Guide

EV Charging and DC Earthing Requirements

EV charging equipment (EVSE — Electric Vehicle Supply Equipment) has specific earthing and RCD requirements under BS 7671 Section 722. The requirements depend on the charger type and power level:

  • Single phase 7.4kW (Mode 3): Type A RCD with additional DC fault current protection (IEC 62955 compliant RDC device), or Type B RCD. Many 7.4kW chargers include certified DC ELSP — verify before omitting external Type B RCD.
  • Three phase 22kW (Mode 3): Type B RCD required. Three phase rectification in the vehicle on-board charger can produce smooth DC fault currents. Some chargers include integral Type B protection — verify.
  • DC rapid chargers (Mode 4): The charger-to-vehicle connection is DC. The AC supply to the charger cabinet requires Type B RCD protection or integral DC protection certified to IEC 62955.

PME earthing considerations for EV chargers are addressed in BS 7671 Regulation 722.411.4.1 — EV charging equipment connected to a PME supply must have additional protective measures to guard against the PEN conductor break risk. Many charger manufacturers include a PEN conductor monitoring device in their products for this purpose.

Complete EV charging installation certificates on your phone

Elec-Mate's EIC app includes fields for EV charging circuit details, RCD type, earthing system, and DNO notification.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · DC Earthing Guide

Solar PV: DC Side Earthing and Bonding

Solar PV systems require careful attention to both the DC side (panels and inverter DC input) and the AC side (inverter output to consumer unit). Key requirements:

  • Panel mounting structure: Must be bonded to the installation earth via a protective bonding conductor. The bonding conductor must be sized in accordance with BS 7671 Table 54.7 and the inverter installation manual. Typically 4mm² or 6mm² copper.
  • Inverter enclosure: The PE terminal of the inverter must be connected to the installation earth. This connection is made via the PE conductor of the AC supply cable from the inverter to the consumer unit.
  • DC cable insulation: DC cables must be double insulated or individually insulated and sheathed. The DC cable insulation resistance must be verified during commissioning. Damaged DC cable insulation is a significant fire risk — DC arc faults are sustained, unlike AC arcs which self-extinguish at each current zero crossing.
07 · DC Earthing Guide

PE Conductor for DC Circuits

The protective earth (PE) conductor must be continuous throughout both the AC and DC sides of a solar PV or battery storage installation. For DC circuits:

  • DC cables do not normally include a PE conductor — the DC conductors are ungrounded in the IT system. The PE for equipment enclosures is provided by separate bonding conductors.
  • The inverter PE terminal connects the inverter enclosure to the installation earth via the PE in the AC supply cable. This must be verified by continuity testing during commissioning.
  • PE conductor size for DC bonding: follow BS 7671 Table 54.7, with the minimum size determined by the fault current that may flow through the conductor under fault conditions.
08 · DC Earthing Guide

For Electricians: DC Earthing Compliance in Practice

DC earthing and RCD selection for solar PV and EV chargers are among the most complex areas of BS 7671 for domestic electricians. The consequences of incorrect RCD selection — particularly using a Type A RCD where a Type B is required — can leave a DC fault completely undetected and uninterrupted. Always check the specific equipment installation manual for the required RCD type and earthing configuration before commencing the installation.

Complete solar PV and EV charging certificates on your phone

Elec-Mate's Solar PV and EIC certificate apps capture all required details: RCD type, earthing system, insulation resistance test results…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions: AC vs DC Earthing

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Certify Solar PV and EV Charging Installations

Elec-Mate's Solar PV and EIC apps capture all earthing details, RCD specifications, and test results for compliant certification. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy