EMERGING TECHNOLOGY

Air Source Heat Pump Electrical Installation: UK Electrician Guide

Every air source heat pump needs electrical work. This guide covers supply requirements, circuit sizing, outdoor unit cable routing, controller wiring, backup immersion circuits, MCS certification, BUS grant implications, and typical costs of £500 to £1,500.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

16 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Most domestic air source heat pumps draw 3 to 6kW and run on a single-phase supply with a dedicated 20A or 32A circuit from the consumer unit. Larger systems (above 8kW) or properties with existing high electrical demand may require a three-phase supply upgrade.
  • 2The outdoor unit requires UV-resistant, weather-rated cable (typically SWA or armoured) run from the consumer unit to the external mounting position. Cable sizing must account for the compressor starting current, which can be 3 to 5 times the running current.
  • 3A dedicated MCB or RCBO is required for the heat pump circuit. Type C MCBs are typically specified to accommodate the compressor inrush current without nuisance tripping.
  • 4MCS (Microgeneration Certification Scheme) certification is mandatory for the installer if the homeowner wants to claim the Boiler Upgrade Scheme (BUS) grant of up to £7,500.
  • 5Typical electrical installation costs for an ASHP range from £500 to £1,500, covering the dedicated circuit, outdoor cable run, controller wiring, backup immersion circuit, and certification.
01 · Emerging Technology

Air Source Heat Pump Electrical Installation: What Electricians Need to Know

Air source heat pumps (ASHPs) are the leading low-carbon heating technology in the UK. With the government phasing out new gas boiler installations and providing grants of up to £7,500 through the Boiler Upgrade Scheme, ASHP installations are growing rapidly — and every one of them needs electrical work.

The electrical scope of an ASHP installation typically includes a dedicated circuit from the consumer unit to the outdoor unit, cable routing through the property, a local isolator adjacent to the outdoor unit, controller wiring, and often a backup immersion heater circuit. This is distinct from the heating and plumbing work (which is carried out by the MCS-certified heating installer) and represents a significant revenue stream for electricians.

This guide covers the electrical supply requirements, circuit design, cable routing, controller wiring, regulations, MCS considerations, and typical costs.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Emerging Technology

Electrical Supply Requirements: Single Phase vs Three Phase

The first consideration is whether the existing electrical supply can accommodate the heat pump. Most domestic ASHPs draw 3 to 6kW at full load, which equates to 13 to 26A on a single-phase 230V supply.

Single Phase (Most Homes)

Suitable for ASHPs up to approximately 8kW. The existing single-phase supply must have sufficient spare capacity — check the main fuse rating (typically 60A, 80A, or 100A) and the peak demand of the existing installation. A 5kW ASHP on a 100A supply with moderate existing demand is straightforward. On a 60A supply with an electric shower and EV charger already installed, a supply upgrade may be needed.

Three Phase (Larger Systems)

Required for larger ASHPs (above 8 to 10kW) and for properties where the single-phase supply cannot accommodate the additional load. Three-phase ASHPs distribute the load across three phases, reducing the current per phase. A three-phase supply upgrade involves a DNO application and can take 8 to 16 weeks. Factor this into the project timeline and quote the supply upgrade separately.

Always carry out a maximum demand assessment during the site survey to confirm the existing supply is adequate. If the supply needs upgrading, inform the customer early — it adds cost and time to the project.

03 · Emerging Technology

Circuit Design and Sizing

The heat pump outdoor unit requires a dedicated radial circuit from the consumer unit. The circuit design must account for:

  • Full load current — the manufacturer specifies the full load current (FLC) for the compressor and any integrated electric heaters. A typical 5kW single-phase ASHP draws 20 to 22A at full load.
  • Starting current — compressor inrush current is typically 3 to 5 times the FLC. This determines the MCB type (Type C recommended) and influences cable sizing if the cable run is long.
  • Cable sizing — size the cable for the FLC, applying correction factors for ambient temperature, grouping, and installation method per BS 7671 Appendix 4. A typical 5kW ASHP on a 15m cable run requires 4.0mm or 6.0mm SWA. Check voltage drop does not exceed 5% (or the manufacturer specified maximum).
  • MCB/RCBO selection — Type C MCB or RCBO, rated to suit the cable and the manufacturer specification. Typically 20A or 32A for domestic ASHPs. Type A RCD protection is normally sufficient unless the manufacturer specifies Type B.
  • Local isolator — a switched isolator must be installed adjacent to the outdoor unit (within sight, typically within 2m) to allow safe servicing. The isolator must be lockable and rated for the full load current.

Use the cable sizing calculator to determine the correct cable size for the specific installation, accounting for all relevant correction factors and voltage drop.

04 · Emerging Technology

Outdoor Unit Cable Routing

The cable route from the consumer unit to the outdoor heat pump unit is often the most labour-intensive part of the electrical installation. Planning the route during the site survey avoids surprises on installation day.

  • Cable type — SWA (Steel Wire Armoured) cable is the standard choice for runs that pass through external walls or are exposed externally. The armour provides mechanical protection and the cable is UV-resistant. For short runs entirely within the building, standard twin and earth in conduit may be acceptable.
  • Wall penetrations — core through external walls with a slight downward slope to prevent water ingress. Seal the penetration with fire-rated intumescent sealant. Use a gland on the SWA cable at the outdoor unit isolator.
  • Minimum cable lengths — some ASHP manufacturers specify a minimum interconnection cable length (to provide a minimum circuit impedance for the compressor soft-start). Check the installation manual — running a shorter cable than specified can cause compressor protection trips.
  • Segregation — keep the power cable separated from any communications or control cables by at least 50mm (or as specified by the manufacturer) to avoid electromagnetic interference.
05 · Emerging Technology

Controller and Zone Wiring

Most ASHP systems include a controller that manages heating zones, hot water production, and weather compensation. The controller wiring is typically low-voltage signal cabling, but the electrician must connect it correctly.

  • Room thermostat — wired or wireless connection to the ASHP controller. If replacing an existing boiler, the existing thermostat wiring may be reusable. Wireless thermostats avoid new cable runs.
  • Zone valves — motorised zone valves (typically 230V) control the flow of hot water to different heating zones. The electrician wires the zone valves to the ASHP controller wiring centre. Follow the manufacturer wiring diagram exactly — incorrect zone valve wiring is one of the most common commissioning faults.
  • Outdoor temperature sensor — mounted on a north-facing wall (shaded from direct sunlight) and wired back to the controller. This enables weather compensation — the system adjusts the flow temperature based on the outdoor temperature for maximum efficiency. The sensor cable is typically 2-core signal cable.
  • Flow sensor — some systems require a flow temperature sensor on the heating flow pipe, wired to the controller. This is a low-voltage connection.
06 · Emerging Technology

Backup Immersion Heater Circuit

Most ASHP systems heat domestic hot water via a hot water cylinder. A backup immersion heater is installed in the cylinder to provide hot water if the heat pump is off (for servicing) or during periods of extreme cold when the heat pump alone cannot maintain the required water temperature.

  • Immersion heater rating — standard domestic immersion heaters are 3kW (13A at 230V). Some cylinders have two immersion heaters — an upper (for quick boost) and a lower (for full cylinder heating). Each requires its own circuit if they can operate simultaneously, or a single circuit if interlocked.
  • Dedicated circuit — a 16A or 20A MCB with 2.5mm twin and earth cable is the standard arrangement for a 3kW immersion heater. The circuit must include a local switched fused connection unit (FCU) or double-pole switch adjacent to the cylinder.
  • Timer control — the immersion heater is typically controlled by the ASHP controller (which energises it only when the heat pump cannot meet demand) or by a separate time clock. If the customer has a smart tariff, the immersion heater can be scheduled to run during off-peak hours for additional savings.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · Emerging Technology

MCS Certification and the Boiler Upgrade Scheme (BUS) Grant

The Boiler Upgrade Scheme (BUS) provides a government grant of up to £7,500 towards the cost of an air source heat pump installation. This grant has made ASHPs financially competitive with gas boilers and is driving the growth in installations.

  • MCS certification required — the lead installer must be MCS-certified to access the BUS grant. MCS covers the design, installation, and commissioning of the heat pump system. Electricians working as subcontractors to an MCS-certified heating installer do not need their own MCS certification for the electrical work, but the work must comply with BS 7671 and be certificated.
  • EPC requirement — the property must have a valid Energy Performance Certificate (EPC) with no outstanding loft or cavity wall insulation recommendations (or evidence that insulation is not feasible). The EPC must be in place before the BUS application.
  • Documentation — the MCS installer must provide a heat loss calculation, system design, commissioning record, and handover documentation. The electrician's EIC is part of this documentation package.

If you are considering becoming an MCS-certified ASHP installer (rather than just the electrical subcontractor), you need training in heat pump system design and installation, plus MCS registration via a certification body such as NICEIC, NAPIT, or Elmhurst.

08 · Emerging Technology

Regulations and Standards

The electrical installation for an air source heat pump must comply with BS 7671:2018+A4:2026 and the manufacturer installation manual. Key regulations from the RAG intelligence include:

  • Regulation 542.1.3 — covers earthing arrangements for electric heating systems and heat pumps, including protective bonding, RCD selection and discrimination, avoidance of nuisance trips, and verification of earth continuity.
  • Regulation 710.415.2.1 — addresses residual currents from electric heating equipment (including heat pumps) returning via protective conductors, with implications for main protective bonding conductor sizing and RCD coordination.
  • Regulation 704.537 — requires local service isolators for heating circuits and heat pumps to permit safe servicing without isolating unrelated circuits.
  • Regulation 512.1.3 — electric heating controls, thermostats, and motorised valves must match the declared frequency rating to ensure accurate control and safe operation with heat pumps.
  • Regulation 753.522.1.3 — in plant rooms, consider increased ambient temperatures from heat pumps and compressors when specifying cables and control wiring.

The installation is notifiable under Part P of the Building Regulations (new circuit from the consumer unit). Notify through your competent person scheme (NICEIC, NAPIT, etc.) or via Building Control.

09 · Emerging Technology

Typical Electrical Costs: £500 to £1,500

The electrical installation cost varies depending on the complexity of the cable route, the distance from the consumer unit to the outdoor unit, and whether the consumer unit needs modification.

  • Simple installation (£500 to £800) — consumer unit adjacent to the outdoor unit location, short cable run (under 10m), no consumer unit upgrade needed, no immersion heater circuit. Straightforward SWA run through one wall.
  • Standard installation (£800 to £1,200) — 10 to 20m cable run, one or two wall penetrations, local isolator, backup immersion heater circuit, zone valve wiring, and controller connections. This is the most common scope for a domestic ASHP.
  • Complex installation (£1,200 to £1,500+) — long cable run (20m+), consumer unit upgrade or additional ways needed, multiple zone valve circuits, external cable routing with SWA and glands, three-phase connection, or supply capacity issues requiring DNO application.

These costs are for the electrical work only — the heat pump unit, cylinder, pipework, and plumbing are separate. When quoting, itemise the electrical scope clearly so the MCS installer and homeowner can see exactly what is included.

Quote ASHP electrical work accurately

Elec-Mate's quoting app lets you itemise dedicated circuits, SWA cable runs, isolators, immersion circuits, and controller wiring.

Try it free for 7 days
Download on the App StoreGet it on Google Play
10 · Emerging Technology

For Electricians: Growing Your Heat Pump Business

Air source heat pump installations are one of the fastest-growing segments of domestic electrical work. Every ASHP needs electrical work, and the typical value of £500 to £1,500 per installation makes it a reliable revenue stream — particularly when you build relationships with MCS-certified heating installers who subcontract the electrical work.

Cable Sizing Calculator

Size the dedicated ASHP circuit with the cable sizing calculator. Account for compressor starting current, cable run length, and installation method. Get it right on the survey.

Quoting App

Price ASHP electrical work with Elec-Mate's quoting app. Dedicated circuit, SWA, isolator, immersion, controller wiring — all itemised.

EIC Certificate on Your Phone

Complete the Electrical Installation Certificate for the ASHP circuits on site. AI board scanning, voice test entry, and instant PDF export for the MCS documentation package.

Quote, install, and certify heat pump electrical work

Join 1,000+ UK electricians using Elec-Mate for cable sizing, professional quoting, and on-site EIC certification.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Heat Pump Electrical Installation

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size Cables and Certify Heat Pump Installations on Your Phone

Join 1,000+ UK electricians using Elec-Mate for cable sizing, professional quoting, and on-site EIC certificates for heat pump installations. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy