INSTALLATION GUIDE

Granny Annex Electrical Installation: Complete Wiring Guide for UK Electricians

Everything you need to know about wiring a granny annex — separate supply vs sub-main, consumer unit design, kitchen and bathroom circuits, heating, fire separation, Building Control approval, and realistic 2026 pricing from £3,000 to £8,000.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

18 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1A granny annex is a self-contained dwelling unit and requires its own consumer unit with full RCD protection. The decision between a separate metered supply from the DNO and a sub-main from the main house depends on the annex status (independent dwelling vs ancillary accommodation).
  • 2The electrical installation must comply with BS 7671 in full, including all special location requirements for bathrooms (Section 701) and kitchens. The annex is effectively a complete domestic installation in miniature.
  • 3Building Control approval is required for the annex construction. The electrical work is notifiable under Part P. Fire separation between the annex and the main house (if attached) requires fire-stopping of all cable penetrations.
  • 4Meter considerations are significant: if the annex is intended as a separate dwelling (for rental or sale), it needs its own electricity meter and a separate DNO connection. If it is ancillary to the main house (for a family member), it can be supplied from the main house.
  • 5Budget £3,000 to £8,000 for the electrical installation depending on the annex size, specification, and whether a new DNO connection is required. The electrical package for a well-specified one-bedroom annex is typically £4,000 to £6,000.
01 · Installation Guide

Granny Annex Electrical Installation: Complete Guide

Granny annexes — self-contained living spaces built in the garden or attached to the main house — are one of the fastest-growing areas of domestic construction in the UK. They provide independent accommodation for elderly relatives, adult children, or rental income, and they require a complete electrical installation equivalent to a small flat or bungalow.

Unlike a shed or garage conversion, a granny annex typically includes a kitchen, bathroom, living area, and bedroom. This means the electrical installation must cover every aspect of domestic wiring: general power and lighting, cooking circuits, bathroom special location requirements, heating, hot water, smoke detection, and potentially a separate metered supply.

This guide covers the complete electrical installation process from supply design through to certification, with practical guidance on the decisions that affect cost and complexity.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Supply Options: Separate Meter vs Extension of Main

The most important design decision for an annex electrical installation is the supply arrangement. There are two options:

Sub-Main from the House

The annex is supplied via a sub-main cable from the house consumer unit or a dedicated switch-fuse adjacent to the meter. This is the simpler and cheaper option. It is appropriate when the annex is ancillary to the main house (used by a family member, not separately metered or billed). The sub-main cable must be sized for the annex maximum demand — typically 16.0mm² or 25.0mm² SWA for a one-bedroom annex. The annex electricity cost is included in the main house bill.

Separate DNO Connection

The annex has its own electricity meter and a separate connection from the Distribution Network Operator (DNO). This is required when the annex is a separate dwelling (for rental, sale, or independent occupancy). The DNO installs a new service cable, cut-out, and meter. The electrician provides the meter tails and consumer unit. Lead time is typically 6 to 12 weeks. Cost is £500 to £2,000+ depending on the distance from the existing network and any excavation required.

Check the planning conditions for the annex — they often specify whether the annex is ancillary (tied to the main house) or independent. This determines the supply arrangement, Council Tax liability, and whether a separate meter is required.

03 · Installation Guide

Consumer Unit Design

The annex requires its own consumer unit with full RCD protection. A typical one-bedroom annex needs 8 to 12 ways:

  • Lighting circuits (x2) — separate circuits for bedrooms/living area and kitchen/bathroom. 6A MCB/RCBO, 1.0mm² or 1.5mm² twin and earth.
  • Socket circuits (x2) — one for the living area and bedroom, one for the kitchen. 32A ring final circuit or 20A radial in 2.5mm².
  • Cooker circuit — 32A or 45A radial in 6.0mm² or 10.0mm², depending on the cooker rating.
  • Shower circuit — if an electric shower is specified, 40A to 50A radial in 10.0mm². Consider the total demand — an electric shower on a sub-main may require a larger sub-main cable.
  • Heating circuit — dedicated circuit for panel heaters, underfloor heating, or heat pump. Size depends on heating type and load.
  • Immersion heater — 16A radial in 2.5mm² if the hot water is provided by an immersion heater in a cylinder.
  • Smoke detection — dedicated circuit or fed from the lighting circuit depending on the alarm type and Building Control preference.
  • Spare ways (x2 minimum) — always provide spare ways for future additions (EV charger, additional appliances, external lighting).

An RCBO board is the recommended approach — it provides individual RCD and overcurrent protection for each circuit without the risk of one fault tripping unrelated circuits. This is particularly important in a self-contained dwelling where losing all power to a fault on one circuit affects an elderly or vulnerable occupant.

04 · Installation Guide

Kitchen Circuits

The annex kitchen requires the same electrical provision as a kitchen in a house:

  • Cooker circuit — a dedicated radial circuit for the cooker. For a standard domestic electric cooker, 32A in 6.0mm² is usually adequate (applying diversity). For a large range cooker, 45A in 10.0mm² may be needed.
  • Socket outlets — worktop sockets must be at least 300mm above the worktop surface. Provide a minimum of 4 double sockets above the worktop for small appliances. No sockets within the zone directly above the hob.
  • Dedicated appliance points — fused spurs or dedicated sockets for washing machine, dishwasher, fridge-freezer, and boiler (if an electric combi-boiler is used).
  • Extract fan — a cooker hood or extract fan is required in kitchens for Part F ventilation compliance. Wire from a fused spur (3A or 5A).
05 · Installation Guide

Bathroom Circuits (Section 701)

The annex bathroom is a special location under BS 7671 Section 701. The key requirements are:

  • Zoning — Zone 0 (inside the bath/shower tray), Zone 1 (above the bath/shower to 2.25m height), Zone 2 (0.6m horizontal from Zone 1), and outside zones. Equipment must be rated for the zone in which it is installed.
  • IP ratings — minimum IPX7 in Zone 0, IPX4 in Zone 1, IPX4 in Zone 2. Light fittings in Zone 1 must be rated IPX4 and suitable for the zone.
  • Socket outlets — no sockets permitted in Zones 0, 1, or 2. Sockets must be at least 3m horizontal from Zone 1, or supplied via a shaver supply unit conforming to BS EN 61558-2-5.
  • RCD protection — all circuits in the bathroom must have 30mA RCD protection. No exceptions.
  • Supplementary bonding — supplementary bonding may be omitted if the protective device disconnection times are met (verified by measurement) and all circuits are RCD protected. Otherwise, bond all simultaneously accessible extraneous-conductive-parts and exposed-conductive-parts.

For an electric shower, the pull-cord switch must be outside Zone 1 (typically ceiling- mounted outside the shower area). The shower circuit requires a dedicated MCB/RCBO sized for the shower unit rating — typically 40A to 50A for a 9kW to 10.8kW electric shower.

06 · Installation Guide

Heating and Hot Water

Annexes need their own heating and hot water system. The electrical requirements depend on the system chosen:

  • Electric panel heaters — the simplest option. Wall-mounted heaters (1kW to 2kW each) on a dedicated radial circuit per room or a shared circuit. Modern smart heaters with individual room thermostats are popular for annexes.
  • Electric underfloor heating — excellent for annexes built on a new concrete slab. Install heating mats under the floor finish with zone thermostats. Requires dedicated circuits (typically one per room, 16A to 20A each).
  • Air source heat pump — increasingly common in new-build annexes for Part L compliance. The electrician provides the outdoor unit supply (typically 20A to 32A), indoor unit wiring, and controls. A separate circuit for the heat pump is essential.
  • Hot water — if the annex has its own hot water cylinder, provide a dedicated 16A circuit for the immersion heater. If using an electric combi-boiler or instantaneous water heater, the supply requirements vary by unit — check the manufacturer data.
07 · Installation Guide

Fire Separation and Smoke Detection

Fire safety in an annex has direct implications for the electrical installation:

  • Fire separation (attached annex) — if the annex is attached to the main house, a 30-minute fire-rated wall is required between the two. All cable penetrations must be fire-stopped with intumescent sealant or fire collars. The sub-main cable entry is a common point that must be fire-stopped.
  • Smoke and heat detection — mains-powered interconnected alarms with battery backup. Install smoke alarms in the hallway/circulation area, living room, and bedroom. Install a heat alarm in the kitchen (smoke alarms are unsuitable in kitchens due to cooking fumes). All alarms must be interconnected so they all sound when any one is triggered.
  • Emergency lighting — not typically required for a domestic annex, but consider a maintained emergency bulkhead at the entrance for elderly or disabled occupants who may need illuminated escape during a power failure.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
08 · Installation Guide

Building Control and Part P

The annex requires full Building Regulations approval. The electrical work is notifiable under Part P and must be either:

  • Self-certified — by a registered electrician (NICEIC, NAPIT, ELECSA, etc.) who submits the EIC to Building Control via their competent person scheme. This is the standard approach.
  • Building Control notification — if the electrician is not registered, the homeowner must apply to Building Control before work starts. Building Control will inspect the work at first fix and final fix stages and charge an inspection fee.

Building Control will want to see the Electrical Installation Certificate (EIC) as part of the overall sign-off. The EIC must cover all circuits in the annex and the sub-main (if applicable). Ensure the certificate is completed before the Building Control final inspection.

09 · Installation Guide

Testing and Certification

The annex installation must be fully tested and an EIC issued. The testing scope covers every circuit in the annex:

  • Continuity of protective conductors on all circuits
  • Ring final circuit continuity (if ring circuits are used)
  • Insulation resistance on all circuits (500V DC, minimum 1 megohm)
  • Polarity at every termination point
  • Earth electrode resistance (if TT earthing with earth rod)
  • Earth fault loop impedance (Zs) on every circuit
  • RCD operation on all RCD/RCBO protected circuits
  • Prospective fault current at the annex consumer unit origin
  • Functional testing of smoke/heat alarms, heating controls, and extract fans
10 · Installation Guide

Tools and Materials Checklist

Tools Required

  • Insulated screwdriver set
  • Torque screwdriver
  • SWA cable cutters and gland kit
  • Drill and bits (masonry, wood, hole saws)
  • Cable detector and fish tape
  • Cable strippers and cutters
  • Crimping tool and ferrule kit
  • Multimeter and continuity tester
  • Insulation resistance tester (500V)
  • Earth fault loop impedance tester
  • Earth electrode resistance tester
  • RCD tester
  • Shovel or mini-digger (if trenching for sub-main)

Materials Required

  • SWA cable for sub-main (16.0mm² to 25.0mm²)
  • Consumer unit (8 to 12 way RCBO board)
  • Twin and earth cable (1.0mm², 1.5mm², 2.5mm², 6.0mm², 10.0mm²)
  • Metal back boxes and dry-lining boxes
  • Socket outlets, switches, dimmers
  • LED downlights and bathroom-rated fittings (IPX4)
  • Cooker switch and connection unit
  • Shower pull-cord switch (45A/50A)
  • Interconnected mains smoke/heat alarms
  • Intumescent fire-stop sealant
  • Earth rod and clamp (if TT arrangement)
  • Underground ducting and warning tape
  • SWA glands
  • Heating equipment (heaters, UFH mats, thermostats)
11 · Installation Guide

Typical Costs (2026 UK Pricing)

Annex electrical installation costs depend on the size, specification, and supply arrangement:

  • Studio annex (open plan, no kitchen) — lighting, sockets, heating, shower circuit, smoke detection: £3,000 to £4,000.
  • One-bedroom annex (standard spec) — full kitchen, bathroom, living area, bedroom, heating: £4,000 to £6,000.
  • Two-bedroom annex (high spec) — two bathrooms, large kitchen, UFH, air source heat pump feed, data cabling: £6,000 to £8,000.
  • Add-ons — new DNO connection: £500 to £2,000+. Earth rod installation: £80 to £150. Sub-main trench (per metre): £15 to £30. EV charger circuit: £300 to £600. Data cabling (Cat6 per point): £80 to £150.
12 · Installation Guide

For Electricians: Annex Installations Are Premium Work

Annex electrical installations are the highest-value domestic job type after full house rewires. A typical one-bedroom annex is worth £4,000 to £6,000 for the electrical package alone, and the work spans 3 to 5 days over a 4 to 8 week build programme. These are premium customers building substantial extensions — they value quality, professionalism, and certification.

Professional Quoting

Price the complete annex electrical package with Elec-Mate's quoting app. Sub-main, consumer unit, all circuits, heating, testing, and certification — all itemised with your margins. A professional PDF quote wins the job against competitors who send a text message with a single number.

EIC on Your Phone

Complete the Electrical Installation Certificate on site. AI board scanning captures every RCBO in seconds. Voice test entry for the schedule of results. Instant PDF export for Building Control sign-off.

Quote, install, and certify annex electrics

Join 1,000+ UK electricians using Elec-Mate for professional quoting, cable sizing, and on-site EIC certification.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Annex Electrical Installation

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Quote and Certify Annex Installations on Your Phone

Join 1,000+ UK electricians using Elec-Mate for professional quoting, cable sizing, and on-site EIC certificates for annex installations. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy