BS 7671 GUIDE

Cable Sizing Guide BS 7671
How to Size Cables

Cable sizing to BS 7671 follows a five-step process: determine the design current, select the protective device, apply correction factors, choose the cable from Appendix 4, and verify voltage drop. This guide covers every step with worked examples, reference methods, and the adiabatic check.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

18 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

How do you size a cable to BS 7671?

Five steps: (1) calculate the design current Ib; (2) select a protective device with In ≥ Ib; (3) apply the correction factors — ambient (Ca), grouping (Cg), thermal insulation (Ci) and BS 3036 fuse (Cf) — so the tabulated rating It ≥ In ÷ (Ca×Cg×Ci×Cf); (4) choose a cable whose current-carrying capacity from the Appendix 4 table for the correct reference method meets that figure; (5) verify voltage drop is within limits (3% for lighting, 5% for other uses per Appendix 4) and run the adiabatic check on the CPC (Reg 543.1.3).

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Cable sizing follows 5 steps: design current (Ib), protective device (In), correction factors (Ca, Cg, Ci, Cf), tabulated current (It = In / correction factors), and voltage drop check.
  • 2Correction factors account for ambient temperature (Ca from Table 4B1), grouping (Cg from Table 4C1), thermal insulation (Ci = 0.5 if fully enclosed, 0.89 one side), and BS 3036 fuses (Cf = 0.725).
  • 3The reference method (A through G) determines the current-carrying capacity of the cable — Method A (enclosed in insulated wall) has the lowest ratings, while Method G (spaced from a surface) has the highest.
  • 4After selecting the cable, verify voltage drop using mV/A/m values from Appendix 4: maximum 3% for lighting (6.9V) and 5% for other circuits (11.5V) from a 230V supply.
  • 5Elec-Mate's cable sizing calculator handles all 5 steps automatically — enter your load, conditions, and cable run, and get the correct cable size with voltage drop and fault current verification.
01 · BS 7671 Guide

Cable Sizing to BS 7671 — Overview

Correct cable sizing is one of the most fundamental design tasks in electrical installation. A cable that is too small will overheat under load, potentially causing a fire or damaging the insulation. A cable that is too large wastes material and money. BS 7671:2018+A4:2026 provides a systematic process for selecting the correct cable size based on the load, the installation conditions, and the protective device.

The process uses the current-carrying capacity tables in Appendix 4 of BS 7671, combined with correction factors that account for the specific installation conditions. The result is a cable that can safely carry the design current under the worst-case conditions it will encounter, while keeping the voltage drop within acceptable limits.

While the process can be done manually using the tables in the brown book, it involves multiple lookups and calculations that are easy to get wrong. This is why many electricians use a cable sizing calculator — and why Elec-Mate has built every Appendix 4 table and correction factor into its cable sizing calculator.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Guide

The 5-Step Cable Sizing Process

1

Determine the Design Current (Ib)

The design current is the maximum current the cable must carry in normal service. For single-phase circuits: Ib = P / (V x cos phi). For three-phase circuits: Ib = P / (root 3 x VL x cos phi). For a resistive load (heaters, immersion, electric shower), the power factor is 1.0. For motors and fluorescent lighting, the power factor is typically 0.8-0.85. For domestic circuits with a fixed rating (e.g., 32A ring circuit, 20A radial), the design current is simply the expected maximum load.

2

Select the Protective Device (In)

Choose a protective device with a rated current In greater than or equal to Ib. Standard MCB ratings are 6, 10, 16, 20, 25, 32, 40, 50, and 63A. Standard RCBO ratings are the same. The protective device must also be appropriate for the load type: Type B for general circuits (trips at 3-5 times rated current), Type C for motor loads (5-10 times), and Type D for high inrush loads like transformers (10-20 times).

3

Apply Correction Factors and Calculate It

The correction factors account for conditions that reduce the cable's ability to dissipate heat. Divide the protective device rating by the product of all applicable correction factors to get the minimum tabulated current rating:

It = In / (Ca x Cg x Ci x Cf)

4

Select Cable from Appendix 4

Find the appropriate Appendix 4 table for the cable type and installation method (reference method). Select a cable with a tabulated current-carrying capacity Iz greater than or equal to It. This ensures the cable can carry the full load current even under the worst-case derating conditions.

5

Verify Voltage Drop

Calculate the voltage drop using VD = mV/A/m x Ib x L / 1000 and compare against the BS 7671 limits: 3% for lighting (6.9V from 230V) and 5% for other circuits (11.5V from 230V). If the voltage drop exceeds the limit, increase the cable size and recalculate.

All 5 Steps — Done in Seconds

Elec-Mate's cable sizing calculator handles the entire 5-step process. Enter the load, protective device, installation conditions…

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · BS 7671 Guide

Reference Methods (A to G)

The reference method describes how the cable is installed. This is critical because the installation method determines how effectively the cable can dissipate heat — and therefore its current-carrying capacity. A cable clipped directly to a surface (Method C) can dissipate heat much better than the same cable enclosed in an insulated wall (Method A), so it has a higher current rating.

Reference Methods

A

Enclosed in conduit in an insulated wall

Lowest ratings. The cable is surrounded by insulation on all sides, severely restricting heat dissipation. Common in domestic rewires where cables run through insulated stud walls.

B

Enclosed in conduit on a wall or in trunking

Slightly better than Method A as the conduit or trunking is mounted on a surface, allowing some heat dissipation from the exterior.

C

Clipped direct to a surface

Good heat dissipation. Cable is clipped directly to a wall, ceiling, or other surface. The most common method for domestic T&E cable clipped to joists in accessible locations.

D

Direct buried in the ground

Used for SWA cables buried in the ground. The thermal conductivity of the soil affects the rating. Common for supplies to outbuildings, garages, and EV chargers.

E

On perforated cable tray (horizontal)

Excellent heat dissipation with air circulation on all sides. High current ratings. Common in commercial and industrial installations.

F

On perforated cable tray (vertical)

Similar to Method E but mounted vertically. Slightly different ratings due to convection effects on vertical runs.

G

Spaced from a surface

Cable supported on brackets or cleats spaced away from the surface. Free air circulation gives the highest current ratings.

Important: If a cable run uses multiple installation methods along its route, you must use the worst-case (lowest rating) reference method for the entire cable length. For example, if a cable is clipped direct (Method C) for most of its run but passes through an insulated wall for 2 metres (Method A), the Method A rating applies.

04 · BS 7671 Guide

Correction Factor Tables

Four correction factors may apply to a cable sizing calculation. Each factor is a decimal less than or equal to 1.0 that increases the required tabulated current by reducing the divisor:

Ca — Ambient Temperature (Table 4B1)

The Appendix 4 current ratings assume an ambient temperature of 30C. If the ambient temperature is higher, the cable cannot dissipate heat as effectively, and the rating must be reduced.

Ambient TempCa (70C PVC)Ca (90C XLPE)
25C1.031.02
30C1.001.00
35C0.940.96
40C0.870.91
45C0.790.87
50C0.710.82

Cg — Grouping (Table 4C1)

When cables are grouped together, they heat each other up and cannot dissipate heat as effectively. The grouping factor depends on the number of circuits and the arrangement:

No. of CircuitsBunchedSingle Layer (Touching)
11.001.00
20.800.85
30.700.79
40.650.75
60.570.72
90.500.70

Ci — Thermal Insulation

Cables in contact with or enclosed in thermal insulation require significant derating. If the cable is totally surrounded by thermal insulation for more than 0.5 metres: Ci = 0.5 (a massive derating — the cable can carry only half its normal current). If the cable touches insulation on one side only: Ci = 0.89. This is one of the most commonly missed correction factors, particularly in loft spaces where insulation is being retrofitted around existing cables.

Cf — BS 3036 Semi-Enclosed Fuse Factor

If the circuit is protected by a BS 3036 semi-enclosed (rewirable) fuse, apply Cf = 0.725. This accounts for the higher fusing factor of rewirable fuses compared to MCBs. For MCBs, RCBOs, and BS 88 HRC fuses, Cf = 1.0 (no correction needed). BS 3036 fuses are rarely installed in new work but may still be encountered in existing installations.

Automatic Correction Factor Application

Enter the ambient temperature, number of grouped circuits, insulation conditions, and fuse type — Elec-Mate applies Ca, Cg, Ci, and Cf automatically.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · BS 7671 Guide

Worked Examples

Example 1: 32A Ring Final Circuit

Load: Domestic ring final circuit, design current 20A (typical mixed load)

Protective device: 32A Type B MCB

Conditions: Clipped direct (Method C), 30C ambient, not grouped, not in thermal insulation

Correction factors: Ca = 1.0, Cg = 1.0, Ci = 1.0, Cf = 1.0

It = 32 / (1.0 x 1.0 x 1.0 x 1.0) = 32A

From Table 4D5A (XLPE 90°C T&E), 2.5mm² clipped direct (Method C) has Iz = 30A per conductor. Since this is a ring circuit, both legs share the load, so 2.5mm² is adequate. Voltage drop for a 50m ring with 20A load: VD = (18 x 20 x 25) / 1000 = 9.0V (within 11.5V limit). Result: 2.5mm² T&E.

A4:2026 — AFDD (Reg 421.1.7): BS 7671:2018+A4:2026 Regulation 421.1.7 recommends the installation of arc fault detection devices (AFDDs) on AC final circuits of a fixed installation to mitigate the risk of fire from arc fault currents. For domestic ring final and radial circuits, consider AFDD requirements at the design stage. Note the wording is recommendatory rather than mandatory.

Example 2: 20A Radial Circuit (Kitchen)

Load: Kitchen socket radial, design current 18A

Protective device: 20A Type B RCBO

Conditions: Enclosed in insulated wall (Method A) for 3m, then clipped direct — use Method A (worst case), 30C ambient, grouped with 1 other circuit, not in thermal insulation

Correction factors: Ca = 1.0, Cg = 0.80, Ci = 1.0, Cf = 1.0

It = 20 / (1.0 x 0.80 x 1.0 x 1.0) = 25A

From Table 4D5A, 2.5mm2 T&E Method A has Iz = 20A — not enough. 4mm2 T&E Method A has Iz = 27A — sufficient (27 ≥ 25). Result: 4mm2 T&E.

Example 3: Lighting Circuit (Loft Space)

Load: First-floor lighting, design current 5A

Protective device: 6A Type B MCB

Conditions: Method C where clipped to joists, but touching loft insulation on one side for 6m. 35C in loft space. Grouped with 1 other circuit.

Correction factors: Ca = 0.94, Cg = 0.80, Ci = 0.89, Cf = 1.0

It = 6 / (0.94 x 0.80 x 0.89 x 1.0) = 6 / 0.669 = 8.97A

From Table 4D5A, 1.0mm² T&E Method C has Iz = 16A — sufficient. 1.5mm² also works with Iz = 20A. Voltage drop for 1.5mm² with 5A over 18m: VD = (29 x 5 x 18) / 1000 = 2.61V (within 6.9V lighting limit). Result: 1.5mm² T&E (standard for lighting).

A4:2026 — RCD on domestic lighting (Reg 411.3.4): BS 7671:2018+A4:2026 Regulation 411.3.4 requires that, within domestic (household) premises, AC final circuits supplying luminaires shall be provided with additional protection by an RCD with a rated residual operating current not exceeding 30 mA. A 6A MCB alone is no longer sufficient for a new domestic lighting circuit — an RCBO or RCD upstream is mandatory for compliance with A4:2026.

06 · BS 7671 Guide

Adiabatic Equation — Fault Current Check

After selecting the cable based on current-carrying capacity and voltage drop, there is one final check: verifying that the cable can withstand fault current without damage. This uses the adiabatic equation:

k2S2 ≥ I2t

k = Cable factor (115 for PVC/copper line conductor, 143 for PVC/copper CPC)

S = Cross-sectional area of the conductor in mm2

I = Prospective fault current in amps

t = Disconnection time of the protective device in seconds

If k2S2 is greater than or equal to I2t, the cable can withstand the fault current. If not, the cable must be upsized. In practice, this check rarely fails for domestic installations because the prospective fault current is relatively low and the disconnection times are fast. However, it is an essential check on commercial and industrial installations where fault levels can be significantly higher.

Site verification — Zs and the 0.8 factor: When verifying earth fault loop impedance (Zs) on site during initial verification, the measured value must satisfy Zs(measured) < 0.8 × the maximum tabulated Zs value. The 0.8 multiplier (per BS 7671 Reg 411.4.4 / 411.5.4 and Reg 253.0) accounts for the fact that conductor resistance increases with temperature — a cable at full load is hotter than at the ambient conditions when measured. Measured Zs values that pass at ambient but exceed 80% of the tabulated maximum will fail under load; always apply the 0.8 factor before recording compliance.

For more detail, see the adiabatic equation calculator guide.

70+ Calculators — All BS 7671 Based

Elec-Mate has 70+ electrical calculators including cable sizing, voltage drop, adiabatic equation, conduit fill, trunking fill, Zs lookup, diversity…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · BS 7671 Guide

Appendix 4 Tables Explained

Appendix 4 of BS 7671 contains the current-carrying capacity and voltage drop tables for all standard cable types and installation methods. Understanding which table to use is the first step in using them correctly.

Start with Table 4A2: Before reading any current-carrying capacity table, consult Table 4A2 (referenced in BS 7671 Reg 521.3 and Reg 125.8). Table 4A2 maps each physical installation method to the correct reference method and current-carrying capacity table — for example, T&E clipped direct maps to Reference Method C and Table 4D1A (PVC 70°C) or 4D5A (XLPE 90°C); singles in conduit on a wall map to Reference Method B and Table 4D4A. Selecting the wrong table — even with the right reference method — will give incorrect Iz values.

Main Appendix 4 Tables

  • Table 4D5A — PVC twin and earth and singles in conduit. The most commonly used table for domestic installations. Columns for Reference Methods A, B, and C.
  • Table 4D4A — Multicore 70C thermoplastic (LSF) cables. Used where low smoke and fume cables are required, such as public buildings and escape routes.
  • Table 4E4A — XLPE/LSF singles in conduit or trunking. Higher temperature rating (90C) gives higher current-carrying capacity than PVC equivalent.
  • Table 4B1 — Ambient temperature correction factors (Ca).
  • Table 4C1 — Grouping correction factors (Cg).

Each current-carrying capacity table has multiple columns corresponding to different reference methods. Ensure you read the correct column for your installation method. The voltage drop columns in each table provide the mV/A/m values for both single-phase and three-phase circuits.

How to Size a Cable — Step-by-Step

Follow this process to size any cable to BS 7671:2018+A4:2026 using the Appendix 4 tables and correction factors.

1

Calculate the design current

Determine the design current (Ib) from the load. For single-phase: Ib = P / (V x cos phi). For three-phase: Ib = P / (root 3 x VL x cos phi). For domestic circuits with known ratings (32A ring, 20A radial), use the expected maximum load current.

2

Select the protective device

Choose a protective device with rated current In greater than or equal to Ib. Standard MCB ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63A. Select the appropriate type: Type B for general, Type C for motors, Type D for high inrush loads.

3

Identify correction factors and calculate It

Determine the applicable correction factors: Ca (ambient temperature from Table 4B1), Cg (grouping from Table 4C1), Ci (thermal insulation — 0.5 if fully enclosed, 0.89 one side), and Cf (0.725 for BS 3036 fuses, 1.0 for MCBs). Calculate It = In / (Ca x Cg x Ci x Cf).

4

Select cable from Appendix 4

Find the correct Appendix 4 table for your cable type and installation method (reference method A through G). Select a cable with tabulated current-carrying capacity Iz greater than or equal to It. Use the worst-case reference method if the cable route includes multiple installation methods.

5

Verify voltage drop and fault current withstand

Calculate voltage drop: VD = mV/A/m x Ib x L / 1000. Compare against 3% for lighting (6.9V) or 5% for other circuits (11.5V from 230V). If voltage drop exceeds the limit, increase the cable size. Then check the adiabatic equation (k2S2 >= I2t) to verify the cable can withstand fault current. If both checks pass, the cable is correctly sized.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size Cables in Seconds, Not Minutes

Every Appendix 4 table and correction factor built in. Enter your load and conditions — get the right cable instantly. Plus voltage drop, adiabatic check, and 67 more calculators. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy