BS 7671 GUIDE

Voltage Drop Limits BS 7671
How to Calculate

Voltage drop is one of the five checks in the cable sizing process. BS 7671 Regulation 525.1 sets the maximum permitted voltage drop at 3% for lighting circuits and 5% for other circuits. This guide covers the limits, the formula, worked examples, and when voltage drop matters most.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

15 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1BS 7671 Regulation 525.1 limits voltage drop to 3% for lighting circuits (6.9V from a 230V supply) and 5% for all other circuits (11.5V from a 230V supply).
  • 2The formula is: VD = mV/A/m x Ib x L / 1000, where mV/A/m comes from the Appendix 4 tables, Ib is the design current in amps, and L is the cable length in metres.
  • 3Voltage drop matters most on long cable runs, lighting circuits (tighter 3% limit), high-current loads like showers and EV chargers, and motor loads where low voltage can prevent starting.
  • 4For three-phase 400V circuits, the limits are 12V for lighting (3%) and 20V for other circuits (5%), using three-phase mV/A/m values from Appendix 4.
  • 5Elec-Mate's voltage drop calculator does the calculation instantly — enter the cable type, length, and load, and get the result with a pass/fail indication against BS 7671 limits.
01 · BS 7671 Guide

What Is Voltage Drop?

Voltage drop is the reduction in voltage that occurs as electrical current flows through a cable. All cables have resistance, and that resistance causes a voltage loss between the supply end (the distribution board) and the load end (the socket, light, or appliance). The longer the cable, the higher the current, and the smaller the conductor — the greater the voltage drop.

Excessive voltage drop can cause problems. Lighting circuits may produce dim or flickering lights. Motor loads may fail to start or run inefficiently. Electronic equipment may malfunction or shut down. In extreme cases, equipment can be damaged. BS 7671 sets maximum voltage drop limits to ensure that the voltage at the load is high enough for equipment to operate correctly and safely.

Voltage drop is part of the cable sizing process. After selecting a cable based on its current-carrying capacity and correction factors, you must verify that the voltage drop across the cable length does not exceed the BS 7671 limits. If it does, you need to increase the cable size until the voltage drop is within limits.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Guide

BS 7671 Voltage Drop Limits (Regulation 525.1)

BS 7671 Regulation 525.1 sets the maximum permitted voltage drop from the origin of the installation to the load. The limits differ depending on the circuit type:

Maximum Voltage Drop Limits

Circuit TypePercentage230V Single-Phase400V Three-Phase
Lighting3%6.9V12V
All other circuits5%11.5V20V

These limits apply from the origin of the installation (the main switch or distribution board) to the most distant point on the circuit. For installations supplied from a private LV supply (such as a generator or transformer), the limits may be relaxed — BS 7671 permits up to 6% for lighting and 8% for other circuits in these cases (Regulation 525.1.1).

Important: The voltage drop values of 6.9V and 11.5V assume a nominal supply voltage of 230V. The actual UK supply voltage can vary between 216.2V and 253V (230V -6% / +10%). The voltage drop limit applies at the nominal voltage, not the worst-case low voltage.

03 · BS 7671 Guide

How to Calculate Voltage Drop

The voltage drop formula for single-phase circuits is straightforward:

VD = (mV/A/m x Ib x L) / 1000

VD = Voltage drop in volts

mV/A/m = Millivolts per amp per metre (from Appendix 4 tables)

Ib = Design current in amps (the actual load current)

L = One-way cable length in metres (route length, not straight-line distance)

The mV/A/m value is specific to each cable type, cable size, and installation method. It is found in the voltage drop columns of the Appendix 4 current-carrying capacity tables. Each table provides both single-phase (two-column) and three-phase (three-column) mV/A/m values.

The result is in volts. Compare it against the appropriate limit — 6.9V for lighting or 11.5V for other circuits (single-phase 230V). If the voltage drop exceeds the limit, you need to increase the cable size or reduce the cable length.

Voltage Drop Calculator — Instant Results

Enter the cable type, cable size, length, and load current. Elec-Mate calculates the voltage drop instantly and shows a clear pass/fail against BS 7671…

Try it free for 7 days
Download on the App StoreGet it on Google Play
04 · BS 7671 Guide

Worked Examples

Example 1: Domestic Ring Circuit

Circuit: Ring final circuit, 2.5mm2 twin and earth, Reference Method C (clipped direct)

Design current (Ib): 25A (typical domestic ring circuit load)

Cable length: 50m total ring length (longest route to the most distant socket = 25m)

mV/A/m: 18 mV/A/m (from Table 4D5A, 2.5mm2, column for Reference Method C)

VD = (18 x 25 x 25) / 1000 = 11.25V

11.25V is within the 5% limit (11.5V) — but only just. Marginal pass.

Note: For a ring circuit, the voltage drop is calculated using the design current and half the total ring length (the longest route to the most distant point). If the ring becomes unbalanced (which happens in practice), the actual voltage drop may be higher. Consider 4mm2 cable for long ring circuits.

Example 2: Lighting Circuit

Circuit: Lighting radial, 1.5mm2 twin and earth, Reference Method A (enclosed in insulated wall)

Design current (Ib): 6A (typical domestic lighting circuit)

Cable length: 20m to the furthest luminaire

mV/A/m: 29 mV/A/m (from Table 4D5A, 1.5mm2)

VD = (29 x 6 x 20) / 1000 = 3.48V

3.48V is within the 3% lighting limit (6.9V). Compliant.

Example 3: EV Charger (Long Run)

Circuit: 32A radial for 7.4kW EV charger, 6mm2 twin and earth, Reference Method C

Design current (Ib): 32A

Cable length: 30m (consumer unit to detached garage)

mV/A/m: 7.3 mV/A/m (from Table 4D5A, 6mm2)

VD = (7.3 x 32 x 30) / 1000 = 7.01V

7.01V is within the 5% power limit (11.5V). Compliant.

If the cable run were 50m instead: VD = (7.3 x 32 x 50) / 1000 = 11.68V — this would exceed the 5% limit and require upsizing to 10mm2 cable.

05 · BS 7671 Guide

Appendix 4 Tables Explained

The mV/A/m values used in voltage drop calculations come from the voltage drop columns in the Appendix 4 current-carrying capacity tables of BS 7671. Each table covers a specific cable type, and within each table, the mV/A/m values vary by cable size and number of cores.

Key Appendix 4 Tables

  • Table 4D5A — Single-core and multicore 70C thermoplastic (PVC) insulated cables. The most commonly used table for domestic T&E cable.
  • Table 4E4A — Single-core 90C thermosetting (XLPE/LSF) insulated cables in conduit or trunking.
  • Table 4D4A — Multicore armoured cables (SWA) with thermoplastic insulation.
  • Table 4J4A — Mineral-insulated cables (MICC).

Each table provides two sets of mV/A/m values: one for single-phase (two conductors carrying current) and one for three-phase (three conductors carrying current). Ensure you use the correct column for your circuit type. The mV/A/m values account for both the resistance and the reactance of the cable — for smaller cables, resistance dominates; for larger cables, reactance becomes significant.

Every Appendix 4 Table Built In

Elec-Mate's voltage drop calculator and cable sizing calculator have every Appendix 4 table built in.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · BS 7671 Guide

Temperature Correction for Voltage Drop

The mV/A/m values in Appendix 4 are given at the conductor's maximum operating temperature (70C for PVC, 90C for XLPE). In practice, the conductor operating temperature depends on the load current and the ambient temperature. If the cable is not fully loaded, the conductor temperature will be lower than the maximum, and the actual voltage drop will be less than the calculated value.

BS 7671 Appendix 4 provides a correction formula for when a more precise voltage drop is needed. The corrected mV/A/m value accounts for the actual conductor temperature:

mV/A/m (corrected) = mV/A/m (tabulated) x [230 + tp - (Ca2 - Ib2/It2) x (tp - 30)] / (230 + tp)

tp = Maximum conductor operating temperature (70C for PVC)

Ca = Ambient temperature correction factor applied

Ib = Design current

It = Tabulated current-carrying capacity of the cable

In most domestic situations, the simpler calculation using the tabulated mV/A/m value directly is sufficient and gives a conservative (worst-case) result. The temperature correction is most useful in borderline cases where the calculated voltage drop is just above the limit — the correction may bring it within limits and avoid unnecessarily upsizing the cable.

07 · BS 7671 Guide

When Voltage Drop Matters Most

Voltage drop is not always the determining factor in cable sizing — for short cable runs with moderate loads, the current-carrying capacity usually dictates the cable size, and voltage drop is well within limits. However, there are common situations where voltage drop becomes the critical factor:

Long Cable Runs

Any cable run over 20 metres should be checked for voltage drop. Circuits to detached garages, garden offices, outbuildings, and EV chargers in driveways often involve cable runs of 30-50 metres or more. At these distances, voltage drop can easily exceed the 5% limit and may require a cable size one or two steps larger than the current-carrying capacity alone would suggest.

Lighting Circuits

Lighting circuits have the tighter 3% limit (6.9V), making voltage drop more likely to be the critical factor. This is particularly relevant for long lighting circuits in commercial buildings, warehouses, and large domestic properties where cable runs to distant luminaires can be substantial.

High-Current Loads

Electric showers (32-45A), cookers (30-45A), and EV chargers (32A) draw high currents that produce significant voltage drop even on moderate cable lengths. A 10.8kW shower on a 15-metre run of 10mm2 cable produces a voltage drop of about 3V — well within limits. But the same shower on a 40-metre run produces about 8V, pushing close to the limit.

Motor Loads

Motors draw significantly higher current during starting than during running. If the voltage drop is already near the limit at running current, the starting current may cause sufficient voltage drop to prevent the motor starting at all. For motor circuits, it is good practice to keep the running voltage drop well below the 5% limit to allow for starting current.

08 · BS 7671 Guide

Three-Phase Voltage Drop

For three-phase circuits, the same formula applies, but you use the three-phase mV/A/m values from Appendix 4 (these are different from the single-phase values) and compare against the three-phase limits:

VD = (mV/A/m [3-phase] x Ib x L) / 1000

3% lighting limit: 400V x 0.03 = 12V

5% other limit: 400V x 0.05 = 20V

Three-phase mV/A/m values are lower than single-phase values for the same cable because the voltage drop calculation accounts for three conductors sharing the load. The three-phase values are typically about 87% (1/root 3) of the single-phase values for the resistive component.

Three-Phase Worked Example

Circuit: Three-phase distribution to a sub-board, 16mm2 4-core SWA, Reference Method D (direct buried)

Design current (Ib): 60A per phase

Cable length: 35m

mV/A/m (3-phase): 2.4 mV/A/m (from Table 4D4A, 16mm2 SWA, three-phase column)

VD = (2.4 x 60 x 35) / 1000 = 5.04V

5.04V is within the 5% limit (20V for 400V three-phase). Compliant.

Single-Phase and Three-Phase Calculations

Elec-Mate's voltage drop calculator handles both single-phase and three-phase circuits. Select the supply type, enter the cable details and load…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Calculate Voltage Drop in Seconds

Every Appendix 4 table built in. Enter cable type, length, and load — get an instant pass/fail result. Plus 70 more calculators, 16 certificate types, and 8 AI agents. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy