Commercial installations must comply with BS 7671:2018+A4:2026 and the Electricity at Work Regulations 1989. Part P of the Building Regulations does not apply to commercial premises, but the installation must still satisfy the relevant parts of the Building Regulations, particularly Part B (fire safety). These are the regulations that change what a commercial rewire costs.
Quick reference — BS 7671:2018+A4:2026
| Regulation | What it means on a commercial rewire |
|---|
| 443.4.1 | SPDs are the default. Omission depends on the owner declaring they are not required. |
| 534.4.4.2 | Protective distance over 10 m — consider additional coordinated SPDs closer to the equipment. |
| 411.3.3 | 30 mA RCD on socket-outlets rated up to 32 A. A documented risk assessment can disapply indent (b) only. |
| 411.3.4 | RCD protection of lighting circuits is a domestic requirement — it does not apply to commercial premises. |
| 421.1.7 | AFDDs are recommended, not required, in offices, retail and industrial units. |
| 560.9 / 560.10 | Emergency lighting to BS 5266-1; fire detection and alarm to the BS 5839 series. |
| 644.1 / 644.4 | An EIC shall be issued on completion by those responsible for design, construction and verification. |
Surge protection: Regulation 443.4.1
Regulation 443.4.1 requires protection against transient overvoltages where the consequence caused by the overvoltage could result in:
- (a) serious injury to, or loss of, human life;
- (b) deleted by BS 7671:2018+A2:2022, Corrigendum (May 2023);
- (c) significant financial or data loss.
For all other cases, protection against transient overvoltages shall be provided unless the owner of the installation declares it is not required due to any loss or damage being tolerable and they accept the risk of damage to equipment and any consequential loss.
On commercial premises the “significant financial or data loss” limb is usually met outright, and even where it is not, the default position is that an SPD goes in. Price one unless the client puts the declaration in writing. Where SPDs are used they shall be selected and erected in accordance with Section 534. Regulation 534.4.4.2 adds a detail worth carrying into the design: if the protective distance between the SPD and the equipment it protects exceeds 10 metres, oscillations could lead to a voltage at the equipment terminals of up to twice the SPD's voltage protection level, so consider additional coordinated SPDs closer to the equipment or a device with a lower protection level. In a multi-storey office that means budgeting Type 2 units at each sub-distribution board, not just one at the origin.
RCD protection: Regulations 411.3.3 and 411.3.4
Regulation 411.3.3 requires additional protection by a 30 mA RCD for socket-outlets rated up to 32 A. It has three indents: (a) socket-outlets in locations where they are liable to be used by persons of capability BA1 or children (BA2), (b) socket-outlets in other locations, and (c) mobile equipment up to 32 A for use outdoors. An exception is permitted to indent (b) — but not to (a) or (c) — where a suitably documented risk assessment undertaken with the involvement of a skilled person (electrically) determines that RCD protection is not necessary. That risk assessment shall be provided with the electrical installation certificate, so allow for producing it rather than assuming a verbal agreement will do.
Note that Regulation 411.3.4, which requires 30 mA RCD protection of final circuits supplying luminaires, applies within domestic (household) premises only. Commercial lighting circuits do not attract it, which is a genuine saving on a large lighting package.
Commercial installations are usually protected by RCBOs on individual circuits rather than bank RCDs, so that a fault on one circuit does not take out several others. Regulation 314.1 backs the approach directly: an installation shall be divided into circuits to (a) avoid danger and minimise inconvenience in the event of a fault and (d) reduce the possibility of unwanted tripping of RCDs due to excessive protective conductor currents not due to a fault. Budget for it at tender — retrofitting RCBOs after a client complains about nuisance tripping is not a variation you will get paid for.
AFDDs: Regulation 421.1.7
Arc fault detection devices conforming to BS EN 62606 shall be provided for single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation, and care homes. For all other premises — which covers most commercial work — the use of AFDDs is recommended, not required. Where they are used, they shall be placed at the origin of the circuit to be protected. Price them as a priced option and let the client decide, rather than either omitting them silently or loading the tender with them.
Certification
Under Regulation 644.1, an Electrical Installation Certificate based on the model in Appendix 6 shall be issued to the person ordering the work on completion of verification. Regulation 644.3 requires it to include the extent of the work covered, Schedule(s) of Inspection, and Schedule(s) of Circuit Details and Test Results — on a large commercial job those schedules run to many pages, which is why testing is not a last-afternoon activity. Regulation 644.4 requires the persons responsible for the design, construction and verification to issue the certificate taking account of their respective responsibilities, and to record the recommended interval between initial verification and the first periodic inspection.
Fire alarm and emergency lighting are certified separately. Regulation 560.9 requires emergency lighting systems to comply with BS 5266-1, BS EN 1838 and BS EN 50172; Regulation 560.10 requires fire detection and fire alarm systems to comply with the relevant parts of the BS 5839 series. Both systems need commissioning certificates and ongoing periodic testing.