Commercial electrical installations must comply with BS 7671:2018+A4:2026 and the Electricity at Work Regulations 1989. Unlike domestic work, Part P of the Building Regulations does not apply to commercial premises — but the installation must still comply with the relevant parts of the Building Regulations, particularly Part B (fire safety).
An Electrical Installation Certificate (EIC) must be issued on completion, signed by the designer, installer, and inspector/tester. For larger installations, the testing and inspection may be split across multiple schedules of test results.
Surge protection is a key consideration on commercial rewires. BS 7671:2018+A4:2026 redrafted Regulation 443.4, and Regulation 443.4.1 now requires protection against transient overvoltages where the consequence of an overvoltage could result in:
- (a)serious injury to, or loss of, human life;
- (b)deleted by BS 7671:2018+A2:2022, Corrigendum (May 2023);
- (c)significant financial or data loss.
For all other cases, protection against transient overvoltages shall be provided unless the owner of the installation declares it is not required due to any loss or damage being tolerable and they accept the risk of damage to equipment and any consequential loss. Limb (b) of Regulation 443.4.1 was deleted by the BS 7671:2018+A2:2022 Corrigendum (May 2023).
On most commercial premises the "significant financial or data loss" condition is readily met, so in practice a Type 1+2 SPD at the main distribution board is specified on the large majority of commercial rewires. Where SPDs are used they must be selected and erected to Section 534. If the protective distance between an SPD and the equipment it protects exceeds 10 metres, Regulation 534.4.4.2 warns that oscillations can lift the voltage at the equipment terminals to up to twice the SPD's voltage protection level — so additional coordinated Type 2 SPDs are typically fitted closer to downstream sub-distribution boards and sensitive equipment.
Additional protection by a 30mA RCD is required for socket-outlets with a rated current not exceeding 32A under Regulation 411.3.3 of BS 7671. In commercial installations this is typically delivered by RCBOs on individual circuits rather than bank RCDs, so that a fault on one circuit does not take out several others — the same approach the regulations encourage to avoid unwanted tripping.
Fire alarm systems must be designed and installed to BS 5839-1, with a separate commissioning certificate. Emergency lighting must comply with BS 5266-1. Both systems require ongoing periodic testing and maintenance.