INSTALLATION GUIDE

Distribution Board Wiring Guide: Consumer Unit Layout

The distribution board is the heart of every electrical installation. This guide covers split load vs dual RCD vs RCBO board configurations, circuit arrangement and allocation, BS 7671 labelling requirements, type testing under BS EN 61439, SPD installation, wiring best practice, and the common mistakes found during EICR inspections.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

15 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

How is a distribution board (consumer unit) wired in the UK?

The incoming supply enters a double-pole main switch, then feeds the protective devices — MCBs, RCBOs or RCDs — that protect each final circuit. A surge protective device (SPD) sits on the supply side where a risk assessment requires it. Earths land on the earth bar, neutrals on the neutral bar (or the RCBO for RCBO boards), and a circuit chart identifies every way.

Domestic consumer units must be type-tested to BS EN 61439-3 and built from non-combustible material (Regulation 421.1.201). Replacing a board is notifiable under Part P and needs an Electrical Installation Certificate.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1RCBO boards provide individual RCD and overcurrent protection per circuit, eliminating the nuisance tripping and loss-of-supply issues that affect split-load and dual-RCD configurations.
  • 2All consumer units in domestic premises must be constructed from non-combustible material (typically metal) under Amendment 1 of BS 7671:2018 (Regulation 421.1.201).
  • 3Circuit labelling must be clear, permanent, and durable — Regulation 514.9.1 requires a chart or table at or near the distribution board identifying each circuit and the area it serves.
  • 4Consumer units must be type-tested assemblies complying with BS EN 61439-3 — assembling a consumer unit from separate components (a "mix and match" approach) does not meet this requirement unless the assembly is verified by the manufacturer.
  • 5Elec-Mate's AI circuit designer generates a complete circuit schedule with suggested board layout, circuit allocation, and cable sizing for any domestic or commercial installation.
01 · Installation Guide

What Is a Distribution Board?

A distribution board (commonly called a consumer unit in domestic installations) is the central point where the incoming electrical supply is split into individual circuits that serve different areas and appliances throughout the building. It houses the main switch, the protective devices (MCBs, RCBOs, or RCDs), and in modern installations, the surge protective device (SPD).

The distribution board is arguably the most important component in any electrical installation. It provides overcurrent protection for every circuit cable, earth fault protection via RCDs or RCBOs, a means of isolation for the entire installation and for individual circuits, and a central point for circuit identification and labelling.

Under BS 7671:2018+A4:2026, domestic consumer units must be constructed from non-combustible material (metal), must be type-tested assemblies complying with BS EN 61439-3, and must be installed by a competent person. Replacing or upgrading a consumer unit is notifiable work under Part P of the Building Regulations and requires an Electrical Installation Certificate (EIC).

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Split Load, Dual RCD and RCBO Boards Compared

The three main configurations for domestic consumer units are split-load, dual-RCD, and full RCBO boards. Each has advantages and drawbacks.

FeatureSplit-LoadDual-RCDFull RCBO
Earth-fault protectionOne RCD covers a bank of MCBsTwo RCDs, one per bank of MCBsIndividual 30 mA RCD per circuit
Effect of one earth faultAll circuits on that RCD lostAll circuits on that RCD lostOnly the faulty circuit trips
Fault discriminationPoorModerateBest — circuit-level
Relative costLowestModerateHighest
Typical use todayRare in new workLegacy / budget upgradesStandard choice for new boards

Split-Load Board

Main switch + one RCD protecting a group of MCBs + a group of MCBs without RCD protection (typically for the non-RCD-required circuits like the cooker). The simplest and cheapest option, but offers limited protection — if the RCD trips, all circuits on that side lose power. Less common in new installations.

Dual-RCD Board

Main switch + two RCDs, each protecting a separate group of MCBs. Circuits are divided between the two RCDs so that if one trips, essential services remain on the other side. Better protection than split-load, but a fault on one circuit still trips all circuits on the same RCD. The most common domestic configuration before RCBO boards became affordable.

Full RCBO Board

Main switch + individual RCBOs for every circuit. Each RCBO provides both overcurrent and 30mA RCD protection for its circuit independently. A fault on one circuit trips only that RCBO — all other circuits remain live. The best protection and discrimination. Higher cost but increasingly the standard choice for new installations and consumer unit upgrades.

Arc Fault Detection Devices (AFDDs) — Regulation 421.1.7

Regulation 421.1.7 was redrafted in BS 7671:2018+A4:2026. It is now a requirement to protect final circuits supplying socket-outlets rated up to 32 A with AFDDs in Higher Risk Residential Buildings, Houses in Multiple Occupation, purpose-built student accommodation and care homes. For all other premises — including ordinary dwellings — the regulation recommends AFDDs on single-phase AC final circuits supplying socket-outlets up to 32 A. Using an AFDD does not remove the need for the other protective measures in the standard.

AFDDs fit within the consumer unit alongside RCBOs, and several manufacturers now offer combined RCBO+AFDD devices providing overcurrent, RCD and arc-fault protection in a single module. Confirmation that any installed AFDDs are operational is an inspection item under BS 7671 (Regulation 421.1.7).

The trend in the UK is strongly towards full RCBO boards. The cost premium over dual-RCD boards has reduced significantly as RCBO prices have fallen. For new installations and consumer unit replacements, an RCBO board provides the best combination of safety, reliability, and fault discrimination.

Design the board layout with AI

Elec-Mate's AI circuit designer generates a complete circuit schedule with suggested board layout and circuit allocation.

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · Installation Guide

Circuit Arrangement and Allocation

How circuits are arranged within the distribution board affects fault discrimination, maintenance, and safety. The key principles are:

  • Separate lighting and power across RCDs. In dual-RCD boards, put at least one lighting circuit on each RCD so that if one trips, the building is not left in complete darkness. This is a recommendation from the IET Guidance Note 1 and is considered best practice.
  • Smoke alarm on a dedicated circuit or the lighting circuit. The smoke alarm supply should be on a circuit that is unlikely to be switched off accidentally. Some electricians put it on its own dedicated 6A MCB. Others connect it to a lighting circuit — BS 5839-6 permits this, but the circuit must not be shared with a dimmer switch.
  • Dedicated circuits for high-current appliances. Cookers, electric showers, immersion heaters, EV chargers, and other high-current loads must have dedicated radial circuits — they should not share a circuit with general socket outlets.
  • Logical grouping. Group circuits by area (upstairs/downstairs) or by function (lighting/power/dedicated) for easy identification and maintenance. The circuit schedule should make it immediately obvious which circuit serves which area.

For a typical 3-bedroom house, a standard circuit schedule on a full RCBO board might look like the example below. Ratings are indicative — always size every circuit against the actual load, cable and installation method using the cable sizing calculator.

CircuitTypical deviceCable
Downstairs lighting6 A Type B RCBO1.0 / 1.5 mm²
Upstairs lighting6 A Type B RCBO1.0 / 1.5 mm²
Downstairs ring final (sockets)32 A Type B RCBO2.5 mm²
Upstairs ring final (sockets)32 A Type B RCBO2.5 mm²
Cooker32 / 40 A Type B RCBO6 mm²
Electric shower40 / 45 A Type B RCBO10 mm²
Smoke alarms6 A Type B RCBO1.5 mm²
Spare ways1–2 ways left free

A modern RCBO board with 12 to 16 ways accommodates this comfortably and leaves room for future additions such as an EV charger or solar PV.

04 · Installation Guide

Labelling Requirements Under BS 7671

Correct labelling is not optional — it is a regulation requirement and a practical necessity for safe operation and maintenance of the installation.

  • Circuit chart (Regulation 514.9.1) — a durable chart or table must be provided at or near the distribution board. It must identify each circuit by number, describe the area or function served, state the protective device type and rating, and record the cable type and size. Note: A4:2026 amended Regulation 514.9.1 to introduce an exception for domestic (household) premises in certain situations — verify the current amended text before citing this requirement on EICRs for domestic properties.
  • Warning notices — the "SAFETY ELECTRICAL CONNECTION — DO NOT REMOVE" notice must be permanently fixed at or near every earthing conductor connection and every bonding conductor connection to an extraneous-conductive-part (Regulation 514.13.1). Regulation 514.12 requires the periodic inspection and testing notice, including the RCD test notice ("This installation, or part of it, is protected by a device which automatically switches off the supply if an earth fault develops. Test quarterly by pressing the button marked 'T' or 'Test'") and, where applicable, the dual supply warning.
  • SPD notice (Regulation 514.16.1) — where an SPD is installed, a label must indicate its presence so that anyone working on the installation knows surge protection is fitted and can check the status indicator.
Notice / labelRegulationWhere it goes
Circuit chart / schedule514.9.1At or near each distribution board
Next inspection recommendation514.12.1At or near the origin
RCD six-monthly test notice514.12.2At or near the consumer unit
"Safety electrical connection — do not remove"514.13.1At earthing / bonding connections
Alternative / dual supply warning514.15Where a second supply exists
SPD presence label514.16.1At or near the SPD

A4:2026 introduced exceptions to Regulations 514.9.1, 514.12.1 and 514.12.2 for domestic (household) premises — check the current amended text before recording an observation on a domestic EICR.

During an EICR inspection, the inspector will check that all labelling is present, accurate, and legible. Missing or incorrect labelling is a C3 (Improvement Recommended) observation. Illegible or faded labels should be replaced — Elec-Mate can generate professional printed circuit schedules from the circuit data entered during an inspection.

05 · Installation Guide

Type Testing: What BS EN 61439 Means for You

BS EN 61439-3 is the product standard for distribution boards (low-voltage switchgear and controlgear assemblies used by ordinary persons). Consumer units installed in domestic premises must comply with this standard, which requires the assembly to be type-tested by the manufacturer.

  • What type testing covers — temperature rise verification, dielectric properties, short-circuit withstand, effectiveness of protective circuits, clearances and creepage distances, mechanical operation, and degree of protection (IP rating).
  • What this means in practice — you must use a complete consumer unit system from a single manufacturer. The enclosure, busbars, MCBs, RCBOs, and RCDs must all be from the same manufacturer's range and verified as compatible. You cannot mix devices from different manufacturers because the resulting assembly would not be type-tested.
  • Consequences of non-compliance — installing a non-type-tested consumer unit fails to meet BS 7671 requirements. It may be identified during an EICR and could result in a C2 (Potentially Dangerous) or C3 observation depending on the nature of the non-compliance.

The major UK consumer unit manufacturers (Hager, Wylex, MK, Schneider Electric, BG) all offer type-tested ranges. When ordering, confirm that the MCBs or RCBOs you specify are from the same range as the enclosure.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Installation Guide

Main Switch and Isolation

The main switch provides a means of isolating the entire installation from the supply. BS 7671 Regulation 462.1.201 requires a main linked switch or linked circuit-breaker as near as practicable to the origin of every installation, serving both as a means of switching the supply on load and as a means of isolation. Where it is intended for operation by ordinary persons — a household or similar installation — it must interrupt both live conductors of a single-phase supply (i.e. a double-pole switch breaking line and neutral), rated for the maximum demand of the installation.

  • Rating — typically 100A for a domestic installation with a standard single-phase 100A supply. For larger properties or three-phase supplies, the main switch rating must match the supply capacity.
  • Accessibility — the main switch must be readily accessible for emergency switching. For new dwellings, Approved Document M of the Building Regulations sets the accessible zone for switches and consumer unit controls between 450mm and 1350mm above finished floor level (this height range is a Building Regulations requirement, not a BS 7671 one).
  • Locking — the main switch should be lockable in the off position for safe isolation during maintenance. Many modern consumer units include a padlock facility on the main switch.

In a dual-RCD or RCBO board, the main switch is upstream of all other devices. In some configurations, the main switch also serves as the RCD (a main switch RCD or RCCB), but this is less common in modern boards because a fault on any circuit would trip the main switch and disconnect the entire installation.

07 · Installation Guide

Installing an SPD in the Distribution Board

Surge protective devices (SPDs) are addressed under Regulation 443 of BS 7671:2018+A4:2026, which determines whether protection against transient overvoltages is needed. Regulation 443.4.1 requires protection to be provided where the consequence of the overvoltage could result in serious injury to, or loss of, human life (limb a) or significant financial or data loss (limb c) — limb (b) was deleted by the BS 7671:2018+A2:2022 Corrigendum (May 2023). For all other cases, protection must be provided unless the owner of the installation declares it is not required because any loss or damage is tolerable and they accept the risk — though in practice many modern domestic installations will warrant an SPD because of the sensitive electronic equipment present. See the dedicated SPD guide for the full risk-assessment methodology. The SPD is installed at the distribution board to protect against transient overvoltages caused by lightning strikes, switching surges, and other disturbances on the supply network.

  • Type 2 SPD — the standard choice for domestic installations. Installed at the consumer unit on the supply side of the circuit protective devices. Protects against surges on the supply network.
  • SPD overcurrent protection — the SPD must have its own overcurrent protection, typically a dedicated MCB rated between 20A and 40A (check the SPD manufacturer's instructions). The SPD MCB should not be RCD-protected because SPD operation can cause nuisance RCD tripping.
  • Connecting conductor length — under BS 7671 Section 534, the total wiring length of the conductors between the connection points of the SPD assembly should preferably not exceed 0.5 m, and in no case exceed 1.0 m. Keep the SPD leads as short and direct as possible to preserve its protective effectiveness.
  • Status indicator — the SPD must have a visible status indicator showing whether it is operational or has failed. A notice should be provided explaining the indicator and the action required if it shows a fault.

Some consumer unit manufacturers offer boards with integrated SPD mounting positions, which simplify installation and help keep cable lengths short. If using a separate SPD module, position it as close to the supply terminals as possible.

08 · Installation Guide

Distribution Board Wiring Best Practice

The quality of the wiring inside and around the distribution board reflects the quality of the entire installation. Neat, well-organised wiring makes maintenance easier, fault finding faster, and inspections smoother.

  • Cable entry — use cable glands or grommets at the entry points. Cables should enter the board neatly and be dressed (arranged) to follow the inside of the enclosure to their respective devices. Avoid crossing cables unnecessarily.
  • Stripping and termination — strip the correct length of insulation (not too much, not too little). The conductor should be fully inserted into the terminal with no bare copper visible outside the terminal housing. Tighten terminal screws to the manufacturer's torque specification.
  • Earth and neutral connections — earth conductors to the earth bar, neutral conductors to the neutral bar. For RCBO boards, the neutral for each circuit connects to the RCBO, not to the main neutral bar. Double-check this — connecting the neutral to the wrong device is a common error.
  • CPC sleeving — all circuit protective conductors (bare copper earth wires) must be sleeved with green/yellow striped sleeving from the point where they become accessible. This is a basic but frequently overlooked requirement.

Take pride in your board wiring. A well-wired consumer unit is a calling card for your workmanship. A poorly wired board — crossed cables, exposed copper, loose terminals — will be photographed and shared by the next electrician who opens it.

09 · Installation Guide

Common Distribution Board Mistakes

  • Mixing devices from different manufacturers. Using MCBs or RCBOs from a different manufacturer than the consumer unit enclosure. The assembly is not type-tested and fails BS EN 61439-3.
  • All lighting on one RCD in a dual-RCD board. If that RCD trips, the entire property is in darkness. Split lighting circuits across both RCDs or use an RCBO board.
  • Missing circuit schedule or warning notices. The circuit chart, RCD test notice, and earthing label are regulation requirements — not optional extras. Missing labels are a C3 observation on every EICR.
  • Neutral connected to wrong RCBO. In an RCBO board, each circuit's neutral must connect to its own RCBO, not to the main neutral bar. A crossed neutral will cause the RCBO to trip immediately on load.
  • Inadequate prospective fault current rating. The consumer unit and its protective devices must be rated for the prospective fault current (PSCC) at the origin. If the PSCC exceeds the rated short-circuit capacity of the devices, they may not disconnect safely under fault conditions. Always measure PSCC and check against the device ratings.

Certify consumer unit changes on your phone

Elec-Mate generates the Electrical Installation Certificate (EIC) for consumer unit changes on your phone.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Distribution Board Wiring

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design and Certify Board Changes on Your Phone

Elec-Mate's AI circuit designer generates board layouts, the cable sizing calculator verifies every circuit, and the EIC app certifies the finished work. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy