Earth fault loop impedance (EFLI) is the total impedance of the complete circuit that earth fault current must travel through if a line-to-earth fault occurs at any point in an electrical installation. Understanding and correctly measuring this impedance is fundamental to verifying that protective devices will disconnect within the required time under fault conditions — which is the primary mechanism by which BS 7671 protects against electric shock from indirect contact.
The earth fault current loop consists of: the line conductor from the point of fault back to the supply transformer; the transformer winding itself; and the return path from the transformer neutral (star point) via the earthing system and the protective conductor (CPC) back to the point of fault. The lower the impedance of this loop, the higher the fault current and the faster the protective device operates.
BS 7671:2018+A4:2026 requires that the earth fault loop impedance Zs must not exceed the value corresponding to the required disconnection time for the circuit concerned. The required disconnection times are 0.4 seconds for final circuits up to 32A supplying socket outlets or equipment accessible to the public, and 5 seconds for distribution circuits and final circuits supplying fixed equipment (with some exceptions).