TESTING GUIDE

Earth Fault Loop Impedance Testing: Zs Testing Procedure and Accepted Values

A complete guide to measuring and assessing earth fault loop impedance (Zs) for UK electricians. Covers Ze vs Zs, the measurement procedure, BS 7671 Appendix 3 table values, temperature correction, and common causes of high Zs readings.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Earth fault loop impedance (Zs) is the total impedance of the earth fault current path: the supply transformer winding, the line conductor from transformer to fault, and the protective conductor from fault back to the transformer.
  • 2Ze is the external earth fault loop impedance — the part of the loop external to the installation (measured at the origin). Zs is the total loop impedance at any given point in the circuit.
  • 3Zs = Ze + (R1 + R2), where R1 is the line conductor resistance and R2 is the CPC resistance from origin to the point of measurement.
  • 4Accepted maximum Zs values are given in BS 7671:2018+A4:2026 Appendix 3 Tables. These values ensure that the protective device operates within its required disconnection time under fault conditions.
  • 5When measuring Zs with a loop tester, apply a correction factor for conductor temperature — tabulated values assume conductors at 20°C, but a warm installation may read higher than the table maximum even if the installation is compliant.
01 · Testing Guide

What is Earth Fault Loop Impedance?

Earth fault loop impedance (EFLI) is the total impedance of the complete circuit that earth fault current must travel through if a line-to-earth fault occurs at any point in an electrical installation. Understanding and correctly measuring this impedance is fundamental to verifying that protective devices will disconnect within the required time under fault conditions — which is the primary mechanism by which BS 7671 protects against electric shock from indirect contact.

The earth fault current loop consists of: the line conductor from the point of fault back to the supply transformer; the transformer winding itself; and the return path from the transformer neutral (star point) via the earthing system and the protective conductor (CPC) back to the point of fault. The lower the impedance of this loop, the higher the fault current and the faster the protective device operates.

BS 7671:2018+A4:2026 requires that the earth fault loop impedance Zs must not exceed the value corresponding to the required disconnection time for the circuit concerned. The required disconnection times are 0.4 seconds for final circuits up to 32A supplying socket outlets or equipment accessible to the public, and 5 seconds for distribution circuits and final circuits supplying fixed equipment (with some exceptions).

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

Ze vs Zs Explained

The distinction between Ze and Zs is important for both testing and fault finding. Here is a clear breakdown:

Ze — External Impedance

Ze is the external earth fault loop impedance — the portion of the fault loop that is external to the installation. It is measured at the origin of the installation with all internal circuits disconnected, and includes the supply transformer winding, the line conductor from transformer to the installation origin, and the distributor's earthing system (PME, TNS, or TT electrode). Ze is provided by the distributor or measured by the electrician at the intake position.

Zs — Total Impedance

Zs is the total earth fault loop impedance at a specific point in the installation. It equals Ze plus the resistance of the line conductor (R1) and the resistance of the protective conductor (R2) from the origin to the point of measurement. The formula is Zs = Ze + (R1 + R2). Zs must be verified at the furthest point of each circuit to confirm the protective device will operate within the required disconnection time.

For a typical TN-C-S (PME) supply in the UK, Ze is typically 0.35Ω or less. For a TN-S supply it is typically 0.8Ω or less. For a TT supply, Ze can be several ohms because the return path relies on the earth electrode and the distributor's earth, both of which have significant resistance. This is why RCDs are mandatory on TT installations — the Zs is too high to achieve disconnection within the required time using overcurrent devices alone.

03 · Testing Guide

Zs Testing Procedure

Follow this procedure for measuring Zs at the furthest accessible point of a circuit. The circuit must be energised for this test.

  1. 1Safe isolation check — confirm the circuit is energised and that it is safe to proceed with live testing. Warn others in the vicinity that a live test is in progress.
  2. 2Select the correct test mode — if an RCD is in the circuit, use your loop tester's no-trip or low-current mode to avoid tripping the RCD during the test. Check the tester manual for the specific mode.
  3. 3Connect the test leads — at the furthest accessible point (last socket outlet, last lighting point), connect line to line terminal (L), neutral to neutral (N), and earth to earth (E). Ensure good contact.
  4. 4Initiate the test — press the test button and allow the instrument to complete its measurement cycle. The display shows the Zs value in ohms.
  5. 5Record the result — record the measured Zs, the circuit designation, and the test point location on the schedule of test results.
  6. 6Compare with the table maximum — divide the Appendix 3 table maximum Zs by 1.24 to get the ambient-temperature limit. Compare your reading against this corrected value.

Record Zs test results on your phone

Elec-Mate's EIC and EICR apps capture Zs test results for each circuit, automatically compare against the Appendix 3 table values…

Try it free for 7 days
Download on the App StoreGet it on Google Play
04 · Testing Guide

Accepted Zs Values — BS 7671 Appendix 3 Tables

BS 7671:2018+A4:2026 Appendix 3 contains tables of maximum earth fault loop impedance values for different protective devices and disconnection times. The key tables are:

  • Table 41.3 — maximum Zs for BS 88-2 and BS 88-3 fuses (industrial cartridge fuses). Values at 0.4s and 5s disconnection times.
  • Reg 411.4.4 (Zs × Ia ≤ Uo × Cmin, Cmin = 0.95) — maximum Zs for Type B MCBs to BS EN 60898 and BS EN 61009. At 32A, maximum Zs is 1.37Ω (0.4s). At 16A, 2.73Ω. At 6A, 7.28Ω.
  • Table 41.5 — maximum Zs for Type C MCBs. Values are lower than Type B because Type C devices require a higher fault current to operate in the instantaneous region. At 32A, maximum Zs is 0.72Ω (0.4s).
  • Table 41.6 — maximum Zs for Type D MCBs. At 32A, maximum Zs is 0.36Ω (0.4s). Type D devices are used for high-inrush loads and require very low Zs to achieve fast disconnection.
  • Ambient temperature correction — all table values assume conductors at maximum operating temperature. For measurements at ambient temperature (~20°C), divide the tabulated maximum by 1.24 (copper thermoplastic conductors) to obtain the maximum permissible measured value.

These tables are incorporated into the schedule of test results on an Electrical Installation Certificate or EICR. The measured Zs and the design Zs (maximum permitted) must both be recorded for each circuit.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
05 · Testing Guide

Pass/Fail Assessment

Assessing whether a measured Zs is acceptable requires comparing the measured value against the table maximum corrected for conductor temperature:

  • PASS — measured Zs (at ambient temperature) does not exceed 0.8 × the calculated maximum. Example: 32A Type B MCB, calculated maximum = (230 × 0.95) / 160 = 1.37Ω; ambient limit = 0.8 × 1.37 = 1.10Ω. A measured value of 0.95Ω passes.
  • FAIL — measured Zs exceeds the corrected limit. Record as a C2 (potentially dangerous) or C3 (improvement recommended) observation on an EICR depending on severity and risk assessment.
  • Borderline — if the measured value is close to (but below) the corrected limit, consider whether measurement uncertainty in the instrument (typically ±5% to ±10%) could put the true value above the limit. Document any assumptions.

On an initial inspection (EIC), a circuit that fails the Zs test must be rectified before the certificate is issued. On an EICR, a failing Zs is coded as C2 (requires urgent attention) if it represents a genuine risk of the device not operating within the required disconnection time.

06 · Testing Guide

Common Problems and Causes of High Zs

When Zs readings exceed the permissible maximum, a systematic investigation is needed. The most common causes are:

  • Poor main earth connection — corroded or loose connections at the main earthing terminal (MET), the earthing conductor, or the connection to the PME/TNS earth. Measure Ze and compare against the expected distributor value.
  • Corroded or damaged CPC — the protective conductor (earth wire) is corroded, damaged, or has a high-resistance joint. Measure R2 separately to identify the CPC resistance.
  • Undersized CPC — the CPC cross-section is insufficient for the circuit length, resulting in excessive R2. This is particularly common in older installations with single-core earth wires.
  • Excessively long circuit run — very long circuits in large commercial or agricultural premises can result in high R1 + R2 even with correctly sized conductors. Consider upgrading conductor sizes or installing an additional distribution board closer to the load.
  • Poor TT earth electrode — on TT systems, a corroded or poorly installed earth electrode can result in very high Ze. The electrode resistance should be tested separately.
07 · Testing Guide

For Electricians: Efficient Zs Testing on Site

Earth fault loop impedance testing is one of the most time-consuming tests on an inspection. Here are practical tips to work efficiently without compromising accuracy:

Measure Ze First

Always measure Ze at the origin before testing individual circuits. This gives you the baseline for calculating expected Zs values and quickly identifies if a high-Zs reading is due to an external supply issue rather than an internal circuit problem.

Use the EICR App to Record Results

Record Zs readings directly into the Elec-Mate EICR app as you go. The app automatically checks each reading against the Appendix 3 table for the device type and rating you have entered, and flags any exceedances. No manual table-lookups required on site.

Calculate Zs from Continuity Results

For new installations, calculate Zs from the measured R1 + R2 continuity values plus the measured Ze, rather than measuring Zs live on each circuit. This is faster and avoids the risk of nuisance RCD tripping during construction.

Frequently Asked Questions About Earth Fault Loop Impedance Testing

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Record Zs Test Results and Complete EICs on Your Phone

Elec-Mate automatically checks Zs readings against BS 7671 Appendix 3 tables and generates professional test schedules on site. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy