The cross-connected test is the definitive ring final circuit check. It derives the R1+Rn value at every socket outlet on the ring, confirming that every outlet is genuinely on the ring and not a spur, and that connections are correct throughout.
- Cross-connect at the consumer unit: Take one end of the line conductor (leg A) and connect it together with the opposite leg's neutral conductor (leg B neutral). Take the other line conductor end (leg B) and connect it with leg A neutral. This transposition means the instrument now sees the line of one ring leg in series with the neutral of the other.
- Do the same for the CPC if testing R1+R2: Cross-connect the line and CPC ends of opposite legs at the consumer unit. This gives R1+R2 at each outlet when testing between line and earth.
- Test at each outlet: At every socket outlet on the ring, connect the instrument between line and neutral terminals. Record the resistance. This is the R1+Rn value at that outlet.
- Test R1+R2 at each outlet: Connect the instrument between line and earth at each outlet. This gives R1+R2, which combined with Ze gives Zs. GN3 requires the highest R1+R2 found on the circuit — usually at a socket wired as a spur — to be the value recorded on the schedule of test results and used for the Zs calculation.
For a correctly wired ring, the R1+Rn value at every outlet should be approximately equal to one quarter of the sum of r1 and rn (the end-to-end totals from Test 1) — R1+Rn ≈ (r1+rn)/4 — and GN3 states the readings taken at each socket outlet on the ring should be substantially the same. That consistency is the point of the test: a reading that climbs towards the middle of the ring and falls away again indicates the line and neutral have not been cross-connected to opposite legs. Outlets connected as spurs will show a higher reading than the rest of the ring.
The line-to-earth readings behave slightly differently. Where the CPC is a smaller cross-sectional area than the line conductor — as in standard flat twin-and-earth — the R1+R2 readings will not be identical around the ring, and GN3 tabulates the expected spread between the lowest and highest reading for common conductor pairings.
Figure-of-eight fault: GN3 identifies this as a specific diagnostic outcome of the three-step ring test. A figure-of-eight occurs when the ring cable is cut and rejoined incorrectly at an intermediate point, so the circuit appears continuous but the conductors are actually looped back on themselves. It shows up first in Test 1: the end-to-end reading comes out lower than the value you would expect from the cable length and cross-sectional area, because the measurement is no longer following the full route. GN3 then directs you to confirm the suspicion with the cross-connected line-to-neutral measurement and by visually inspecting the wiring for misconnections. This is also why line, neutral and CPC must be measured separately in Test 1 — measuring them together can mask the fault.