The complete guide to the EICR schedule of inspections per BS 7671 Appendix 6. Every section explained — distribution equipment, wiring systems, current-using equipment, protective measures, isolation and switching, and miscellaneous items. Common C2 and C3 observations for each section, plus practical tips for a thorough visual inspection.
The schedule of inspections is the visual-inspection checklist that accompanies an EICR, based on the model forms in BS 7671 Appendix 6. It works through the installation section by section — intake and distribution equipment, wiring systems, current-using equipment, special locations, and isolation and switching — recording each item as acceptable or noting a defect with a classification code (C1, C2, C3 or FI). Every relevant item must be checked before the report can be issued.
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1The EICR schedule of inspections follows the BS 7671 Appendix 6 model form and covers six main sections: distribution equipment, wiring systems, current-using equipment, protective measures, isolation and switching, and miscellaneous items.
2Each item in the schedule is marked as satisfactory (tick), unsatisfactory (cross), not applicable (N/A), or limitation (LIM) — every item must be addressed and none should be left blank.
3Common C2 observations include missing CPCs, absent RCD protection where required, damaged consumer unit enclosures, and lack of main protective bonding to services.
4Common C3 observations include absence of SPD protection, old wiring colours not re-identified, and lack of circuit charts at the distribution board.
5Elec-Mate has the complete Schedule of Inspections built into the EICR form matching BS 7671 Appendix 6 — tick items as you walk the installation, and any unticked items are flagged before you can complete the certificate.
6A4:2026 introduced new requirements relevant to domestic EICRs: Reg 411.3.4 mandates 30 mA RCD protection for AC lighting circuits in domestic premises; Reg 421.1.7 recommends AFDDs on AC final circuits to mitigate arc-fault fire risk. Both are codeable observations on a domestic EICR.
01 · Inspection Guide
EICR Schedule of Inspections: Overview
The schedule of inspections is one of the core components of an EICR. It is the structured checklist of visual inspection items that the inspector must work through during a periodic inspection of an electrical installation. The schedule follows the model form published in Appendix 6 of BS 7671:2018+A4:2026.
The schedule is divided into six main sections, each covering a different aspect of the installation. Every item must be addressed — satisfactory, unsatisfactory, not applicable, or limitation. Unsatisfactory items must be recorded as observations with the appropriate classification code (C1, C2, C3, or FI).
The visual inspection is typically the first phase of the periodic inspection process. Before any testing is carried out, the inspector walks the installation, checking every item on the schedule. This walk-through identifies visible defects, damage, deterioration, and departures from the standard. The findings from the visual inspection inform the subsequent testing strategy — for example, if the visual inspection reveals a missing CPC on a circuit, the inspector will prioritise testing on that circuit.
Complete Schedule of Inspections in the app
Elec-Mate has the full BS 7671 Appendix 6 Schedule of Inspections built into the EICR form. Tick items as you walk the installation.
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Inspection Guide
Section 1: Distribution Equipment
Section 1 of the schedule covers the condition and compliance of the distribution equipment — consumer units, distribution boards, main switches, RCDs, RCBOs, MCBs, fuses, and SPDs. This is typically the starting point of the visual inspection because the distribution board is the heart of the installation.
Items to Check
Condition of enclosure: Is the consumer unit or distribution board in good physical condition? No cracks, burn marks, missing covers, or damage. For domestic premises, is it a non-combustible (metal) enclosure as required by Regulation 421.1.201?
Security of fixing: Is the board securely fixed to the wall? Are all fixings present and tight?
Circuit identification: Are all circuits clearly identified with a circuit chart or schedule? Does the chart correspond to the actual circuit arrangement? (Regulation 514.9.1 — note: A4:2026 introduced an exception for certain domestic premises; check applicability before coding absent charts as C3 in domestic installations)
Adequacy of access: Can the consumer unit or distribution board be accessed safely? Is there adequate working space in front of the board?
Presence of SPDs: For installations where SPDs are required (Regulation 443), are they present and in good condition? Check the status indicator on the SPD if fitted.
AFDDs (arc fault detection devices): Regulation 421.1.7 (A4:2026) recommends AFDDs on AC final circuits of a fixed installation to mitigate fire risk from arc fault currents. Absence is typically coded C3 on new or rewired domestic installations. Note the regulation is recommendatory (not mandatory).
RCD quarterly test notice: Is the notice advising the user to test the RCD quarterly present? (Regulation 514.12 — note: A4:2026 introduced an exception for domestic premises in certain situations; verify whether the exception applies before coding absence as C3 in a domestic installation)
Common C2 observations in this section include: consumer unit with a combustible (plastic) enclosure in a domestic premises where Regulation 421.1.201 requires a non-combustible (or non-combustible-enclosed) enclosure, missing or damaged covers exposing live busbars, and absence of circuit identification.
03 · Inspection Guide
Section 2: Wiring Systems
Section 2 covers the condition of the wiring systems throughout the installation — cables, containment (trunking, conduit, cable tray), cable supports, and the routing of cables through the building.
Items to Check
Cable condition: Is the cable sheath intact and undamaged? Any signs of overheating, discolouration, or deterioration? Cable types such as older rubber-insulated or lead-sheathed cable require particular attention.
Cable supports and fixings: Are cables adequately supported at appropriate intervals? Are clips, cleats, and fixings secure? Are cables protected from mechanical damage where they run across surfaces?
Cable routing: Are cables routed in safe zones where concealed in walls? Any evidence of cables being routed through thermal insulation without derating?
Containment condition: Is trunking, conduit, and cable tray in good condition? Lids in place? No damage or corrosion? Adequate capacity (not overfilled)?
Fire barriers and seals: Are fire barriers present where cables pass through fire-rated walls, floors, or ceilings? (Regulation 527.2) This is a commonly missed item.
Cable identification: Are cables identified with appropriate markings? For pre-harmonised wiring colours (red/black), have they been re-identified where they terminate alongside harmonised colours (brown/blue)?
04 · Inspection Guide
Section 3: Current-Using Equipment
Section 3 covers the condition of the fixed current-using equipment connected to the installation — socket outlets, light fittings, switches, cooker outlets, shaver supply units, immersion heaters, fixed appliances, and other accessories.
Items to Check
Condition of accessories: Are socket outlets, light switches, ceiling roses, and other accessories in good physical condition? No cracks, damage, discolouration, or burn marks.
Security of mounting: Are all accessories securely mounted to the wall or surface? No loose fixings or accessories pulling away from the mounting surface.
Suitability for environment: Are accessories appropriate for the environment? For example, IP-rated accessories in bathrooms (BS 7671 Section 701), weatherproof accessories for outdoor use.
Correct connection: Where accessible without removing accessories from the wall, check for signs of incorrect connection — scorch marks indicating loose connections, signs of arcing, or overheating.
Enclosure integrity: Are all covers, lids, and bezels in place? No exposed live parts accessible to the user.
05 · Inspection Guide
Section 4: Protective Measures
Section 4 is critically important — it covers the protective measures that prevent electric shock and fire. This section checks that the installation has adequate protection for the people using it and for the building itself.
Items to Check
Main protective bonding: Are main protective bonding conductors connected to incoming water, gas, oil, and other metallic services? Regulation 411.3.1.1 requires exposed-conductive-parts to be connected to a protective conductor; Regulation 544.1.1 governs bonding conductor sizing — under PME (TN-C-S), Table 54.8 sets the minimum at 10 mm² copper where the PEN conductor is 35 mm² or less. Check at the point of entry of each service.
Supplementary bonding: Where required (such as bathrooms under certain conditions), are supplementary bonding conductors present and correctly connected?
RCD protection — socket outlets and special locations: Are 30 mA RCDs fitted to circuits that require additional protection? This includes socket outlet circuits, bathroom circuits (Section 701), outdoor circuits, and circuits supplying mobile equipment used outdoors.
RCD protection — domestic lighting circuits (A4:2026): Regulation 411.3.4 requires that, within domestic (household) premises, AC final circuits supplying luminaires shall have additional protection by an RCD with a rated residual operating current not exceeding 30 mA. Absence of RCD protection on domestic lighting circuits is a codeable C2 observation introduced by A4:2026.
Earthing arrangement: Is the earthing arrangement correct and appropriate? Verify the type (TN-S, TN-C-S, TT). For TT systems, is the earth electrode present and in good condition?
Earthing conductor: Is the main earthing conductor present, of adequate size, correctly connected, and in good condition?
SELV/PELV systems: Where separated extra-low voltage or protective extra-low voltage systems are present, is the separation maintained?
Missing main protective bonding is one of the most common and most serious findings during periodic inspection. It is almost always classified as C2 (Potentially Dangerous) because the absence of bonding means that metallic services could become live in the event of a fault, creating a shock risk. For guidance on earthing systems, see the earthing arrangements guide.
Record test results hands-free on site
AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.
Section 5 covers the means of isolation and switching — the switches, isolators, and disconnecting devices that allow the installation or individual circuits to be safely disconnected for maintenance, fault finding, or emergency purposes.
Items to Check
Main switch: Is there a readily accessible means of isolation for the entire installation? Is the main switch clearly identified? Can it be operated easily?
Circuit isolation: Can each circuit be individually isolated at the distribution board? Are the isolating devices (MCBs, RCBOs) clearly labelled to identify the circuit they protect?
Emergency switching: Where required (for example, immersion heaters, fixed space heaters, and some commercial equipment), are emergency switching devices present, accessible, and clearly identified?
Functional switching: Do local switches (light switches, cooker switches, fused connection units) operate correctly and provide the switching function intended?
Fireman's switch: Where required (for example, for exterior luminous signs above 230V or high-voltage discharge lighting installations), is the fireman's switch present, correctly positioned, and clearly labelled in red?
07 · Inspection Guide
Section 6: Miscellaneous
Section 6 covers items that do not fit neatly into the other five sections but are important for the overall assessment of the installation.
Items to Check
Warning and caution labels: Are all required warning labels present? This includes RCD quarterly test notices (Regulation 514.12 — A4:2026 introduced an exception for domestic premises in certain situations), dual supply warnings (where applicable), voltage warnings, and labels indicating the type of earthing system.
Diagrams and documentation: Are circuit diagrams, schedules, and as-installed drawings available and up to date? (Regulation 514.9.1 requires that a durable circuit chart or schedule is provided at or near each distribution board — A4:2026 introduced an exception for certain domestic premises.)
Presence of non-standard colours: If the installation contains pre-harmonised wiring colours (red and black), are they re-identified where they terminate alongside harmonised colours (brown and blue) at the distribution board?
Previous alterations: Is there evidence of previous alterations or additions? Are they of an acceptable standard? Have they been certificated?
Additional protection requirements: Where the current edition of BS 7671 requires protection that was not required when the installation was originally installed (such as RCD protection for socket outlet circuits, 30 mA RCD protection for domestic lighting circuits per Reg 411.3.4 A4:2026, or AFDDs per Reg 421.1.7 A4:2026), has it been assessed and recorded? Absence of AFDDs on new or rewired domestic installations is typically coded C3 (Reg 421.1.7 is recommendatory).
08 · Inspection Guide
Common Observations by Section
Certain observations come up repeatedly during periodic inspections. Knowing the most common findings for each section helps you inspect more thoroughly and ensures you do not overlook frequently occurring defects.
Common C2 Observations
Missing CPC on one or more circuits (older installations)
Absent main protective bonding to water, gas, or oil services (Reg 411.3.1.1 / 544.1.1)
No RCD protection on socket outlet circuits up to 32A
No 30 mA RCD on domestic lighting circuits (Reg 411.3.4, A4:2026)
Damaged consumer unit enclosure with exposed live parts
Inadequate earthing conductor (undersized or damaged)
Reversed polarity at socket outlets or light fittings
Exposed live conductors accessible to the user
Common C3 Observations
Absence of AFDD on new/rewired domestic installation (Reg 421.1.7, A4:2026 — recommendatory)
Absence of SPD protection (Regulation 443 requirements)
Old wiring colours (red/black) not re-identified at the distribution board
No circuit chart or schedule at the distribution board
Absence of RCD quarterly test notice
Consumer unit enclosure is combustible (plastic) in a domestic premises
Supplementary bonding absent in bathroom (where no longer required if conditions met)
Missing fire seals where cables pass through fire-rated construction
It is worth noting that the classification of some observations depends on the specific circumstances. For example, a missing CPC is typically C2 because it represents a failure of the earth fault protection mechanism. However, if the circuit is protected by a 30mA RCD (which provides additional protection against electric shock independent of the earth), the risk is somewhat mitigated, though the observation would still normally be classified as C2 because the RCD is a secondary protection measure, not a substitute for a CPC.
09 · Inspection Guide
Tips for a Thorough Visual Inspection
A thorough visual inspection is the foundation of a good EICR. Once the visual inspection is complete, the correct testing sequence follows — dead tests first, then live tests. The following practical tips will help you carry out a systematic and comprehensive inspection.
Start at the origin: Begin at the supply intake and consumer unit, then work outwards through the installation room by room. This systematic approach ensures nothing is missed.
Use a torch: Many consumer units and ceiling voids are poorly lit. A good torch reveals damage, discolouration, and defects that are invisible in ambient lighting.
Check every room: Do not skip rooms. Check every socket outlet, switch, light fitting, and visible cable in every room. If you cannot access a room, record the limitation.
Look at the loft and under-stairs cupboard: These are common locations for junction boxes, cable runs, and bonding connections. They are also areas where DIY work is frequently found.
Check the meter cupboard: Verify the supply type, check the earthing arrangement at the cutout, and look at the condition of the meter tails.
Record findings in real time: Do not rely on memory. Record observations as you find them using the Elec-Mate app or a notepad. Details that seem obvious on site become impossible to recall accurately after you have left.
Board scanner pre-populates the EICR
Point your phone camera at any distribution board and Elec-Mate's AI board scanner reads MCB ratings, circuit designations…
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Schedule of Inspections Built Into the App
Join 1,000+ UK electricians using Elec-Mate for EICRs with the full BS 7671 Appendix 6 schedule of inspections. Tick items as you walk the installation. Board scanner pre-populates board details. 7-day free trial.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy