INSPECTION GUIDE

EICR Schedule of Inspections: What to Check

The complete guide to the EICR schedule of inspections per BS 7671 Appendix 6. Every part explained — intake equipment, earthing and bonding arrangements, consumer units and distribution boards, distribution and final circuits, isolation and switching, bath or shower locations and other special locations. Common C2 and C3 observations, plus practical tips for a thorough visual inspection.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-08-06Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is the schedule of inspections on an EICR?

The schedule of inspections is the visual-inspection checklist that accompanies an EICR, based on the model forms in BS 7671 Appendix 6. It works through the installation section by section — intake equipment, arrangements for other sources such as microgenerators, earthing and bonding arrangements, consumer units and distribution boards, distribution and final circuits, locations containing a bath or shower, other Part 7 special locations, and prosumer’s low voltage installations — recording each item as an acceptable condition or noting a defect with a classification code (C1, C2, C3 or FI), or as NV, LIM or N/A. Every relevant item must be addressed before the report can be issued.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01The EICR schedule of inspections follows the BS 7671 Appendix 6 model form. The Condition Report Schedule of Inspection for residential and similar premises with up to a 100 A supply runs 1.0 intake equipment (visual only), 2.0 arrangements for other sources such as microgenerators, 3.0 earthing/bonding arrangements, 4.0 consumer unit(s)/distribution board(s), 5.0 distribution/final circuits, 6.0 location(s) containing a bath or shower, 7.0 other Part 7 special installations or locations, and 8.0 prosumer’s low voltage electrical installation(s).
  2. 02The outcome boxes on the Appendix 6 form are: acceptable condition (tick), unacceptable condition (C1 or C2), improvement recommended (C3), further investigation (FI), not verified (NV), limitation (LIM), and not applicable (N/A) — every item must be addressed and none should be left blank.
  3. 03Common C2 observations include missing CPCs, absent RCD protection where required, damaged consumer unit enclosures, and lack of main protective bonding to services.
  4. 04Common C3 observations include absence of SPD protection, old wiring colours not re-identified, and lack of circuit charts at the distribution board.
  5. 05Elec-Mate has the complete Schedule of Inspections built into the EICR form matching BS 7671 Appendix 6 — tick items as you walk the installation, and any unticked items are flagged before you can complete the certificate.
  6. 06Two requirements that older installations commonly fail: Reg 411.3.4 (in force since BS 7671:2018) requires 30 mA RCD additional protection for AC final circuits supplying luminaires within domestic premises; Reg 421.1.7 requires AFDDs on single-phase AC final circuits supplying socket-outlets not exceeding 32 A in high rise residential buildings, HMOs, purpose-built student accommodation and care homes, and only recommends them for all other premises. Both are codeable observations on a domestic EICR.

01 · Inspection Guide

EICR Schedule of Inspections: Overview

The schedule of inspections is one of the core components of an EICR. It is the structured checklist of visual inspection items that the inspector must work through during a periodic inspection of an electrical installation. The schedule follows the model form published in Appendix 6 of BS 7671:2018+A4:2026.

On the Appendix 6 Condition Report Schedule of Inspection for residential and similar premises with up to a 100 A supply, the sections are 1.0 intake equipment (visual inspection only), 2.0 presence of adequate arrangements for other sources such as microgenerators, 3.0 earthing/bonding arrangements, 4.0 consumer unit(s)/distribution board(s), 5.0 distribution/final circuits, 6.0 location(s) containing a bath or shower, 7.0 other Part 7 special installations or locations, and 8.0 prosumer’s low voltage electrical installation(s). The larger version of the form breaks the same ground into more headings, adding other methods of protection, distribution circuits, final circuits, isolation and switching, and current-using equipment (permanently connected). BS 7671 notes that the schedule is not exhaustive and may be reduced or expanded to suit the installation. The walk-through below groups those items the way most inspectors work through a property rather than following the form line by line.

Every item must be addressed. The outcome boxes printed on the form are acceptable condition (tick), unacceptable condition (C1 or C2), improvement recommended (C3), further investigation (FI), not verified (NV), limitation (LIM) and not applicable (N/A). Items coded C1, C2, C3 or FI must also be recorded as observations with the appropriate classification code. C3 and FI are advisory and do not affect the overall assessment.

The visual inspection is typically the first phase of the periodic inspection process. Before any testing is carried out, the inspector walks the installation, checking every item on the schedule. This walk-through identifies visible defects, damage, deterioration, and departures from the standard. The findings from the visual inspection inform the subsequent testing strategy — for example, if the visual inspection reveals a missing CPC on a circuit, the inspector will prioritise testing on that circuit.

In the app

Complete Schedule of Inspections in the app

Elec-Mate has the full BS 7671 Appendix 6 Schedule of Inspections built into the EICR form. Tick items as you walk the installation.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Inspection Guide

Distribution Equipment: Consumer Units and Boards

On the Appendix 6 form this is item 4.0, consumer unit(s)/distribution board(s). It covers the condition and compliance of the distribution equipment — consumer units, distribution boards, main switches, RCDs, RCBOs, MCBs, fuses, and SPDs. This is typically the starting point of the visual inspection because the distribution board is the heart of the installation.

Items to Check

  • Condition of enclosure: Is the consumer unit or distribution board in good physical condition? No cracks, burn marks, missing covers, or damage. For domestic premises, is it a non-combustible (metal) enclosure as required by Regulation 421.1.201?
  • Security of fixing: Is the board securely fixed to the wall? Are all fixings present and tight?
  • Circuit identification: Are all circuits clearly identified with a circuit chart or schedule? Does the chart correspond to the actual circuit arrangement? (Regulation 514.9.1 — note the exception: the requirement need not be applied for domestic (household) premises or similar installations where an initial verification certificate or an EICR, complete with the guidance for recipients, has been issued to the person ordering the work. Check applicability before coding absent charts in domestic installations.)
  • Adequacy of access: Can the consumer unit or distribution board be accessed safely? Is there adequate working space in front of the board?
  • Presence of SPDs: For installations where SPDs are required (Section 443), are they present and in good condition? Check the status indicator on the SPD if fitted.
  • AFDDs (arc fault detection devices): Regulation 421.1.7 requires AFDDs to BS EN 62606 on single-phase AC final circuits supplying socket-outlets rated not exceeding 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes. For all other premises the same regulation only recommends them, so absence in an ordinary dwelling is typically coded C3 at most. On the Appendix 6 form the item is “Confirmation of indication that AFDD(s) are operational” (421.1.7; 532.6; 651.2(e)).
  • RCD six-monthly test notice: Is the notice advising the user to test the RCD six-monthly by pressing the test button present? The Appendix 6 form item reads “Presence of RCD six-monthly test notice, where required” (Regulation 514.12.2). Note the exception: the requirement need not be applied for domestic (household) premises or similar installations where an initial verification certificate or an EICR, complete with the guidance for recipients, has been issued to the person ordering the work — verify whether it applies before coding absence in a domestic installation.

The classic C2 in this section is missing or damaged covers exposing live busbars in the consumer unit. A combustible (plastic) enclosure in domestic premises, and absence of circuit identification, are ordinarily improvement items (C3) rather than C2 — the notes for the person producing the report in Appendix 6 state that an installation designed to an earlier version of BS 7671, and which does not fully comply with the current version, is not necessarily unsafe for continued use or in need of upgrading. Regulation 421.1.201, which requires domestic consumer units to have a non-combustible enclosure or be enclosed in one, is not retrospective.

03 · Inspection Guide

Wiring Systems: Distribution and Final Circuits

Item 5.0 on the residential form, distribution/final circuits, covers the condition of the wiring systems throughout the installation — cables, containment (trunking, conduit, cable tray), cable supports, and the routing of cables through the building.

Items to Check

  • Cable condition: Is the cable sheath intact and undamaged? Any signs of overheating, discolouration, or deterioration? Cable types such as older rubber-insulated or lead-sheathed cable require particular attention.
  • Cable supports and fixings: Are cables adequately supported at appropriate intervals? Are clips, cleats, and fixings secure? Are cables protected from mechanical damage where they run across surfaces?
  • Cable routing: Are cables routed in safe zones where concealed in walls? Any evidence of cables being routed through thermal insulation without derating?
  • Containment condition: Is trunking, conduit, and cable tray in good condition? Lids in place? No damage or corrosion? Adequate capacity (not overfilled)?
  • Fire barriers and seals: Are fire barriers present where cables pass through fire-rated walls, floors, or ceilings? (Regulation 527.2) This is a commonly missed item.
  • Cable identification: Are cables identified with appropriate markings? For pre-harmonised wiring colours (red/black), have they been re-identified where they terminate alongside harmonised colours (brown/blue)?

04 · Inspection Guide

Current-Using Equipment and Accessories

The current-using equipment (permanently connected) heading covers the condition of the fixed current-using equipment connected to the installation — socket outlets, light fittings, switches, cooker outlets, shaver supply units, immersion heaters, fixed appliances, and other accessories.

Items to Check

  • Condition of accessories: Are socket outlets, light switches, ceiling roses, and other accessories in good physical condition? No cracks, damage, discolouration, or burn marks.
  • Security of mounting: Are all accessories securely mounted to the wall or surface? No loose fixings or accessories pulling away from the mounting surface.
  • Suitability for environment: Are accessories appropriate for the environment? For example, IP-rated accessories in bathrooms (BS 7671 Section 701), weatherproof accessories for outdoor use.
  • Correct connection: Where accessible without removing accessories from the wall, check for signs of incorrect connection — scorch marks indicating loose connections, signs of arcing, or overheating.
  • Enclosure integrity: Are all covers, lids, and bezels in place? No exposed live parts accessible to the user.

05 · Inspection Guide

Earthing, Bonding and Protective Measures

Item 3.0 on the residential form, earthing/bonding arrangements, is critically important — with the additional-protection items in 4.0 and 5.0 it covers the protective measures that prevent electric shock and fire. This section checks that the installation has adequate protection for the people using it and for the building itself.

Items to Check

  • Main protective bonding: Are main protective bonding conductors connected to incoming water, gas, oil, and other metallic services? Regulation 411.3.1.2 requires extraneous-conductive-parts liable to introduce a dangerous potential difference to be connected to the main earthing terminal (411.3.1.1 is protective earthing — the CPC requirement — not bonding); Regulation 544.1.1 governs bonding conductor sizing — under PME (TN-C-S), Table 54.8 sets the minimum at 10 mm² copper where the PEN conductor is 35 mm² or less. Check at the point of entry of each service.
  • Supplementary bonding: Where required (such as bathrooms under certain conditions), are supplementary bonding conductors present and correctly connected?
  • RCD protection — socket outlets and special locations: Are 30 mA RCDs fitted to circuits that require additional protection? This includes socket outlet circuits, bathroom circuits (Section 701), outdoor circuits, and circuits supplying mobile equipment used outdoors.
  • RCD protection — domestic lighting circuits: Regulation 411.3.4 requires that, within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30 mA shall be provided for AC final circuits supplying luminaires. This has been in BS 7671 since the 2018 edition, so a large number of older installations will not comply and it is a routinely codeable observation on a domestic EICR.
  • Earthing arrangement: Is the earthing arrangement correct and appropriate? Verify the type (TN-S, TN-C-S, TT). For TT systems, is the earth electrode present and in good condition?
  • Earthing conductor: Is the main earthing conductor present, of adequate size, correctly connected, and in good condition?
  • SELV/PELV systems: Where separated extra-low voltage or protective extra-low voltage systems are present, is the separation maintained?

Missing main protective bonding is one of the most common and most serious findings during periodic inspection. It is almost always classified as C2 (Potentially Dangerous) because the absence of bonding means that metallic services could become live in the event of a fault, creating a shock risk. For guidance on earthing systems, see the earthing arrangements guide.

In the app

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

06 · Inspection Guide

Isolation and Switching

The isolation and switching heading covers the means of isolation and switching — the switches, isolators, and disconnecting devices that allow the installation or individual circuits to be safely disconnected for maintenance, fault finding, or emergency purposes.

Items to Check

  • Main switch: Is there a readily accessible means of isolation for the entire installation? Is the main switch clearly identified? Can it be operated easily?
  • Circuit isolation: Can each circuit be individually isolated at the distribution board? Are the isolating devices (MCBs, RCBOs) clearly labelled to identify the circuit they protect?
  • Emergency switching: Where required (for example, immersion heaters, fixed space heaters, and some commercial equipment), are emergency switching devices present, accessible, and clearly identified?
  • Functional switching: Do local switches (light switches, cooker switches, fused connection units) operate correctly and provide the switching function intended?
  • Firefighter’s switch: Regulation 537.4.2 requires one in the low-voltage circuit supplying outdoor lighting installations operating at a voltage exceeding low voltage, indoor discharge lighting installations operating at a voltage exceeding low voltage, and specific equipment in certain premises subject to the fire and rescue authority’s requirements or to licensing conditions. It does not apply to a portable discharge lighting luminaire or a sign rated not more than 100 W supplied from an accessible socket-outlet. Where one is fitted, check it is easily visible and accessible (537.4.3) and marked with its ON and OFF positions and the words “FIREFIGHTER’S SWITCH” or “FIRE SWITCH” in letters not less than 10 mm high (537.4.4).

07 · Inspection Guide

Labelling, Notices and Documentation

The labelling, notices and documentation items are spread across the form rather than gathered in one place, but they are important for the overall assessment of the installation.

Items to Check

  • Warning and caution labels: Are all required warning labels present? This includes the RCD six-monthly test notice (Regulation 514.12.2, subject to the domestic exception), the next-inspection recommendation notice (514.12.1, same exception), the alternative or additional supplies warning notice where applicable (514.15.1), voltage warning notices where a voltage exceeding 230 V to earth would not normally be expected (514.10.1), and the “Safety Electrical Connection – Do Not Remove” earthing and bonding labels (514.13.1).
  • Diagrams and documentation: Are circuit diagrams, schedules, and as-installed drawings available and up to date? (Regulation 514.9.1 requires a durable copy of the schedule relating to a distribution board to be provided within or adjacent to each distribution board, and any symbol used to comply with IEC 60617 — subject to the same domestic exception as the notices above.)
  • Presence of non-standard colours: If the installation contains pre-harmonised wiring colours (red and black), are they re-identified where they terminate alongside harmonised colours (brown and blue) at the distribution board?
  • Previous alterations: Is there evidence of previous alterations or additions? Are they of an acceptable standard? Have they been certificated?
  • Additional protection requirements: Where the current edition of BS 7671 requires protection that was not required when the installation was originally installed (30 mA RCD protection for socket-outlets rated not exceeding 32 A per Reg 411.3.3, 30 mA RCD protection for AC final circuits supplying luminaires in domestic premises per Reg 411.3.4, or AFDDs per Reg 421.1.7), has it been assessed and recorded? In an ordinary dwelling Reg 421.1.7 only recommends AFDDs, so absence is typically coded C3 at most; in a high rise residential building, HMO, purpose-built student accommodation or care home it is a requirement for socket-outlet circuits rated not exceeding 32 A.

08 · Inspection Guide

Common Observations by Section

Certain observations come up repeatedly during periodic inspections. Knowing the most common findings for each section helps you inspect more thoroughly and ensures you do not overlook frequently occurring defects.

Common C2 Observations

  • Missing CPC on one or more circuits (older installations)
  • Absent main protective bonding to water, gas, or oil services (Reg 411.3.1.2 / 544.1.1)
  • No RCD protection on socket-outlets rated up to 32 A (Reg 411.3.3)
  • No 30 mA RCD on AC final circuits supplying luminaires in a dwelling (Reg 411.3.4)
  • Damaged consumer unit enclosure with exposed live parts
  • Inadequate earthing conductor (undersized or damaged)
  • Reversed polarity at socket outlets or light fittings
  • Exposed live conductors accessible to the user

Common C3 Observations

  • Absence of AFDDs on socket-outlet circuits in an ordinary dwelling (Reg 421.1.7 — recommended, not required, outside HRRBs, HMOs, purpose-built student accommodation and care homes)
  • Absence of SPD protection (Section 443 requirements)
  • Old wiring colours (red/black) not re-identified at the distribution board
  • No circuit chart or schedule at the distribution board (Reg 514.9.1)
  • Absence of RCD six-monthly test notice (Reg 514.12.2)
  • Consumer unit enclosure is combustible (plastic) in a domestic premises
  • Supplementary bonding absent in bathroom (where no longer required if conditions met)
  • Missing fire seals where cables pass through fire-rated construction

It is worth noting that the classification of some observations depends on the specific circumstances. For example, a missing CPC is typically C2 because it represents a failure of the earth fault protection mechanism. However, if the circuit is protected by a 30mA RCD (which provides additional protection against electric shock independent of the earth), the risk is somewhat mitigated, though the observation would still normally be classified as C2 because the RCD is a secondary protection measure, not a substitute for a CPC.

09 · Inspection Guide

Tips for a Thorough Visual Inspection

A thorough visual inspection is the foundation of a good EICR. Once the visual inspection is complete, the correct testing sequence follows — dead tests first, then live tests. The following practical tips will help you carry out a systematic and comprehensive inspection.

  • Start at the origin: Begin at the supply intake and consumer unit, then work outwards through the installation room by room. This systematic approach ensures nothing is missed.
  • Use a torch: Many consumer units and ceiling voids are poorly lit. A good torch reveals damage, discolouration, and defects that are invisible in ambient lighting.
  • Check every room: Do not skip rooms. Check every socket outlet, switch, light fitting, and visible cable in every room. If you cannot access a room, record the limitation.
  • Look at the loft and under-stairs cupboard: These are common locations for junction boxes, cable runs, and bonding connections. They are also areas where DIY work is frequently found.
  • Check the meter cupboard: Verify the supply type, check the earthing arrangement at the cutout, and look at the condition of the meter tails.
  • Record findings in real time: Do not rely on memory. Record observations as you find them using the Elec-Mate app or a notepad. Details that seem obvious on site become impossible to recall accurately after you have left.

In the app

Board scanner pre-populates the EICR

Point your phone camera at any distribution board and Elec-Mate's AI board scanner reads MCB ratings, circuit designations…

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Schedule of Inspections Built Into the App

Join 1,000+ UK electricians using Elec-Mate for EICRs with the full BS 7671 Appendix 6 schedule of inspections. Tick items as you walk the installation. Board scanner pre-populates board details. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy