How to Fill In anEICR Form

A complete step-by-step guide to filling in an Electrical Installation Condition Report. Every section explained — supply characteristics, observations, C1/C2/C3/FI codes, test results, and the declaration.

What Is an EICR and Why Does It Matter?

An Electrical Installation Condition Report (EICR) is the formal document produced following a periodic inspection and testing of a fixed electrical installation. It is defined by BS 7671:2018+A4:2026 (the IET Wiring Regulations, 18th Edition with Amendment 4) and follows the model forms published in Appendix 6 of the standard. The EICR replaced the older Periodic Inspection Report (PIR) and is the standard report format used across the UK electrical industry.

The EICR records the condition of the installation at the time of inspection, identifies any damage, deterioration, defects, or dangerous conditions, and provides recommendations for remedial work. The overall assessment is either Satisfactory (the installation is safe for continued use) or Unsatisfactory (remedial work is needed before the installation can be considered safe). For landlords in England, a valid EICR is a legal requirement under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, with penalties of up to 30,000 pounds per breach for non-compliance.

Filling in an EICR correctly is essential. An incomplete or incorrectly completed report can result in rejection by the scheme provider, disputes with clients, or — in the worst case — failure to identify a dangerous condition that leads to an incident. This guide walks through every section of the EICR form in the order you should complete it on site, with practical tips for avoiding the most common mistakes. Before you start the inspection, ensure you have carried out safe isolation and understand how to carry out insulation resistance testing and interpret the results against BS 7671 observation codes.

Step-by-Step: How to Fill In an EICR

Follow these steps to complete every section of the EICR form correctly. Each step corresponds to a section of the model form in BS 7671 Appendix 6.

1

Complete the details of the contractor and client

Start by filling in Section A of the EICR — the details of the person ordering the report, the installation address, and the contractor details. Include the contractor name, address, registration or scheme membership number (e.g., NICEIC registration number), and the name of the inspector carrying out the inspection. Record the date of the inspection, the date of the previous inspection report (if known), and the recommended date for the next inspection.

2

Record the purpose of the report and extent of the installation covered

In Section B, state the purpose of the report (e.g., periodic inspection, change of occupancy, insurance requirement). In the Extent and Limitations section, describe in detail which parts of the installation were inspected and tested, and which parts were not. List every distribution board inspected, the number of circuits tested, and any limitations such as areas not accessed, circuits not isolated, or concealed wiring not inspected. Be specific — vague descriptions are not acceptable.

3

Enter the supply characteristics and earthing arrangements

In Section C, record the supply details. Identify the earthing arrangement (TN-S, TN-C-S, TT), the supply type (single-phase AC, three-phase AC), the nominal voltage (230V or 400V), and the supply conductor size and type. Measure and record the external earth fault loop impedance (Ze) at the origin with the main earthing conductor temporarily disconnected. Record the prospective fault current (Ipf) at the origin. Document the means of earthing — the type and size of the earthing conductor, the main bonding conductors, and the earth electrode (if applicable for TT systems).

4

Document the particulars of the installation

In Section D, record the details of the consumer unit or distribution boards — the type, number of ways, the rating of the main switch or RCCB, the presence of SPDs (surge protective devices), and the condition of the enclosure. List each circuit with its protective device type and rating, cable type and size, and the circuit designation. Note the presence and type of any RCDs protecting circuits. Record whether the installation has main protective bonding to water, gas, oil, and other services as required by Regulation 411.3.1.2.

5

Complete the schedule of inspections

Work through the schedule of items inspected — this is the checklist of visual inspection items covering the condition of wiring, accessories, distribution boards, protective devices, earthing, bonding, and labelling. For each item, record whether it is satisfactory (tick), unsatisfactory (cross), not applicable (N/A), or limited (LIM). This section covers items such as: correct identification and labelling of circuits, condition of consumer unit, presence of appropriate circuit protection, condition of accessories, suitability of wiring systems for the environment, and presence of fire barriers and seals where required.

6

Record all test results in the schedule of test results

Enter the test results for every circuit inspected. For each circuit, record: continuity of protective conductors (R1+R2 or R2 in ohms), insulation resistance (in megohms, tested at 500V DC between L-E and L-N), polarity (confirmed or not), earth fault loop impedance Zs (in ohms), RCD operating time (in milliseconds at 1x and 5x rated current), and the prospective fault current at the furthest point if different from the origin. Use a calibrated multifunction tester and record the instrument make, model, serial number, and calibration date on the form.

7

Add observations with correct classification codes

For every deficiency, departure from BS 7671, or defect found during the inspection, add an observation to the observations table. Assign the correct classification code: C1 (Danger Present — risk of injury, immediate remedial action required), C2 (Potentially Dangerous — urgent remedial action required), C3 (Improvement Recommended — does not comply with current standard but not dangerous), or FI (Further Investigation — could not be fully assessed). Write a clear description of the observation, the location, and the relevant regulation reference where applicable. Be specific enough that a different electrician could find and rectify the issue from your description.

8

Determine the overall condition and complete the declaration

Based on the observations, determine the overall condition of the installation. If any C1, C2, or FI observations are present, the overall condition must be Unsatisfactory. If only C3 observations or no observations are present, the overall condition is Satisfactory. Complete the declaration section with the inspector name, signature, qualifications, and the date. If there is a separate supervisor reviewing the report, they must also sign the declaration. The person responsible for the electrical installation (the client or landlord) should be informed of the results and provided with a copy of the completed report.

EICR Observation Codes Explained

The observation codes are the most important part of the EICR. Each deficiency or departure from the standard must be assigned a classification code that indicates the severity of the issue. The codes determine the overall condition of the installation.

C1

Danger Present

Risk of injury exists. Immediate remedial action is required. The person responsible for the installation must be advised to take immediate action. Examples: exposed live conductors, absence of earthing on metalwork, dangerously overloaded circuits, or a consumer unit with a missing cover exposing live busbars.

C2

Potentially Dangerous

Risk of injury may arise. Urgent remedial action is required. Examples: missing CPC connections, inadequate fault protection, absence of RCD protection where required by current regulations, or earth fault loop impedance exceeding the maximum permitted value for the protective device.

C3

Improvement Recommended

The installation does not comply with the current edition of BS 7671 but is not immediately dangerous. Improvement is recommended. Examples: lack of supplementary bonding where no longer required, older wiring colours not re-identified, or absence of SPD protection that would be required for a new installation.

FI

Further Investigation

Further investigation is required without delay. The inspector could not fully assess a part of the installation. Common where access was restricted, where unexpected test results need deeper analysis, or where concealed wiring shows signs of deterioration that cannot be fully assessed without more intrusive investigation.

Common Mistakes to Avoid

Vague extent and limitations

Writing "limited inspection" or "standard periodic inspection" is not sufficient. You must describe precisely which boards were inspected, which circuits were tested, which areas were accessed, and what was excluded. Scheme providers regularly reject reports with vague limitations.

Missing or incorrect Ze measurement

The external earth fault loop impedance (Ze) must be measured at the origin with the main earthing conductor temporarily disconnected from the main earthing terminal. Measuring Ze with the earthing conductor still connected gives an incorrect reading because parallel earth paths through the installation affect the result.

Not applying the temperature correction to Zs

The Zs values tabulated in BS 7671 are maximum values at the design stage. When comparing measured Zs values on site, you must account for conductor temperature rise during normal operation. The rule of thumb is that the measured Zs at ambient temperature should not exceed 80% of the tabulated maximum (i.e., multiply by 0.8 to get the on-site limit). Alternatively, multiply the measured value by 1.2 and compare against the table.

Marking the report Satisfactory with a C2 present

Any C1, C2, or FI observation makes the overall condition Unsatisfactory — no exceptions. This is a mandatory requirement. Some electricians mark a report Satisfactory despite a C2 or FI observation being present, perhaps because the client pressures them or because the issue seems minor. This is incorrect and could result in disciplinary action from the scheme provider.

Forgetting to record the test instrument details

The EICR requires the make, model, serial number, and calibration due date of every test instrument used. Missing this information can invalidate the report. Ensure your instruments are within their calibration date before starting the inspection.

Tools and Equipment Needed

Multifunction Tester (MFT)

Your primary test instrument for continuity, insulation resistance, loop impedance, prospective fault current, and RCD testing. Must be calibrated annually. Major brands: Megger, Metrel, Fluke, Kewtech, Seaward.

GS38 Voltage Indicator

A dedicated voltage indicator complying with HSE GS38 for safe isolation. Must have fused test leads, finger guards, and clear voltage markings. Always prove-test-prove before working dead.

Safe Isolation Kit

Padlocks, lock-off devices, and warning labels for securing isolation points. Essential for dead testing — you must lock off before removing consumer unit covers and testing circuits.

Elec-Mate App

The digital EICR form on your phone or tablet. Enter test results on site, capture signatures digitally, auto-validate readings against BS 7671 limits, and export a professional PDF before you leave.

How Elec-Mate Makes EICR Completion Faster

Stop double-handling with paper forms. Enter results directly on your phone, get auto-validation, and export a professional PDF on site.

Complete EICR Form

Every section of the EICR pre-loaded and structured exactly as per the BS 7671 Appendix 6 model forms. Nothing to miss.

Digital Signatures

Capture inspector and client signatures on-screen. No paper, no scanning, no double-handling.

BS 7671:2018+A4:2026

Built to the current 18th Edition including Amendment 4. Observation coding, Zs limits, and form structure all follow the standard.

Auto-Validation

Test results are checked against BS 7671 maximum permitted values as you enter them. Zs, insulation resistance…

Auto-Save Everywhere

Your work saves locally every 10 seconds and syncs to the cloud every 30 seconds. A flat battery or lost signal will not lose your data.

Professional PDF Export

Generate a clean, professional PDF that meets scheme provider requirements. Email it directly to clients from the app before you leave site.

8 Elec-AI Agents

Ask the AI about observation codes, regulation references, or testing procedures. Get instant answers on site without reaching for the brown book.

Works on Any Device

Complete the full EICR on your phone, tablet, or laptop. Works offline on site and syncs when you are back in signal.

Smart Observation Coding

The app guides you through C1, C2, C3, and FI classification with descriptions, and automatically determines the overall assessment.

Digital EICR Forms — Complete on Your Phone, Export PDF on

Elec-Mate's digital EICR and test certificates make inspection reporting faster and more professional.

Try Elec-Mate free
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What is the difference between an EICR and a PIR?

The EICR (Electrical Installation Condition Report) replaced the PIR (Periodic Inspection Report) when BS 7671:2018 was published. The EICR uses the same model forms from Appendix 6 of BS 7671 and serves the same purpose — recording the condition of a fixed electrical installation following periodic inspection and testing. The key differences are in the form layout and the observation coding system. The EICR uses classification codes C1, C2, C3, and FI, whereas the older PIR used a simpler coding system. In practice, the terms are sometimes used interchangeably, but the correct current terminology is EICR. All reports produced under the 18th Edition must use the EICR format.

How do I determine the overall condition of the installation on an EICR?

The overall condition is determined by the observation codes recorded during the inspection. If any C1 (Danger Present), C2 (Potentially Dangerous), or FI (Further Investigation) observations are recorded, the overall condition must be marked as Unsatisfactory. FI makes the report Unsatisfactory because the inspector could not fully determine the condition of part of the installation — the installation cannot be confirmed as safe until that investigation is completed. If only C3 (Improvement Recommended) observations are present, or no observations are recorded at all, the overall condition is Satisfactory.

What should I write in the "Extent and Limitations" section of an EICR?

The Extent and Limitations section must clearly describe what was inspected, what was tested, and what was not. You should list every distribution board inspected, every circuit tested, and any areas or circuits that were excluded from the inspection. Common limitations include: concealed wiring not inspected (as this is normal for a periodic inspection — you cannot strip back plasterwork), circuits not tested because equipment could not be disconnected, areas not accessed due to furniture or stored goods, and any circuits or boards excluded at the client request. It is essential to be specific — vague statements like "limited inspection" are not acceptable. The extent and limitations must be detailed enough that another competent person could understand exactly what was and was not covered.

What qualifications do I need to carry out an EICR?

To carry out an EICR, you must be a competent person as defined by BS 7671. In practice, this means holding a current edition qualification (the 18th Edition IET Wiring Regulations, C&G 2382), plus an inspection and testing qualification such as C&G 2391 (Inspection and Testing) or C&G 2394/2395 (the older equivalents). You should also hold a relevant NVQ Level 3 or equivalent in Electrical Installation. Most competent person scheme providers (such as NICEIC, NAPIT, or ELECSA) require these qualifications for their registered members who carry out periodic inspection and testing. Experience is also critical — the regulations state that the inspector must have sufficient knowledge, skill, and experience to avoid danger.

How do I record supply characteristics on an EICR?

The supply characteristics section of the EICR records the details of the incoming supply. You must record: the earthing arrangement (TN-S, TN-C-S, TT, or IT), the supply type (single-phase or three-phase), the nominal voltage (typically 230V single-phase or 400V three-phase in the UK), the supply conductor type and size, the number and type of live conductors, the origin of the supply (e.g., supplier cutout), the external earth fault loop impedance (Ze) measured at the origin with the main earthing conductor disconnected, and the prospective fault current (Ipf) measured at the origin. These values are critical because they form the basis for verifying that the installation protective devices can operate within the required disconnection times.

Can I issue an EICR digitally using an app?

Yes. There is no requirement in BS 7671 for EICR certificates to be on paper. Digital certificates are fully accepted by competent person scheme providers (NICEIC, NAPIT, ELECSA, and others), local authorities, letting agents, and insurance companies. Elec-Mate provides the complete EICR form structure digitally, including all required sections — supply characteristics, particulars of the installation, schedule of items inspected, schedule of test results, observations and recommendations, and the declaration. Digital signatures can be captured on-screen, and the completed certificate exports as a professional PDF ready to send to clients, upload to scheme provider portals, or store in your records. The advantage of digital is that auto-save prevents data loss, auto-validation catches errors as you enter results, and the PDF is ready to send before you leave site.

What happens if a landlord does not have a valid EICR?

Under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020, landlords must have a valid EICR for all privately rented properties. Failure to comply can result in civil penalties of up to 30,000 pounds per breach, enforced by the local authority. The local authority can also arrange for the inspection and any remedial work to be carried out at the landlord expense. If an EICR returns an unsatisfactory result (any C1, C2, or FI observations), the landlord must complete the remedial work or further investigation within 28 days (or a shorter period if specified by the inspector) and obtain confirmation from a qualified person that the work has been completed satisfactorily. The EICR must be provided to new tenants before they move in and to existing tenants within 28 days of the inspection date.

7-Day Free Trial — Cancel Anytime, No Hassle

Fill In EICR Forms Digitally

Join 1,000+ UK electricians creating professional EICR certificates on their phones. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy