TESTING GUIDE

Insulation Resistance Minimum Values: BS 7671 Guide

Complete guide to insulation resistance minimum values per BS 7671 Table 64 (Reg 643.3.2). The 1 megohm minimum, two-stage test procedure (Reg 643.3.3), test voltage selection by circuit voltage, factors that affect IR readings, and how to troubleshoot low values.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1The minimum acceptable insulation resistance for standard circuits (up to 500V) per BS 7671 Table 64 (Reg 643.3.2) is 1.0 megohm. For SELV and PELV circuits the general minimum is 0.5 megohm, rising to 1.0 megohm where SPDs or similar equipment are included (GN3 Reg 4.8). Any reading below the applicable minimum is a failure.
  • 2The test voltage depends on the circuit voltage: 250V DC for SELV and PELV circuits (up to 50V), 500V DC for circuits up to and including 500V (standard 230V circuits), and 1000V DC for circuits above 500V.
  • 3Insulation resistance readings are affected by temperature, humidity, cable age, contamination, and cable length. Hot, humid conditions give lower readings — always note the environmental conditions.
  • 4Low IR readings can be caused by moisture ingress, damaged cable insulation, contaminated accessories, over-long cable runs, or connected equipment with low insulation resistance.
  • 5Elec-Mate auto-validates every insulation resistance reading against the BS 7671 minimum of 1 megohm and flags any reading below this threshold instantly.
01 · Testing Guide

What Is Insulation Resistance?

Insulation resistance (IR) is a measurement of how effectively the insulation material around electrical conductors prevents current leakage between them. In a perfect cable, the insulation would have infinite resistance — no current would leak between conductors. In practice, all insulation materials allow a tiny amount of leakage current, and this leakage increases as the insulation ages, gets damaged, or is exposed to moisture and contaminants.

The insulation resistance test applies a DC voltage between the conductors and measures the resulting leakage current. From Ohm's law (R = V/I), the instrument calculates the insulation resistance in megohms (MΩ). A high reading indicates good insulation; a low reading indicates that the insulation is compromised and current is leaking.

Insulation resistance testing is test number three in the GN3 testing sequence, carried out after continuity testing and before live tests. It is performed with the circuit de-energised and all loads disconnected.

A4:2026 changes to Chapter 64

BS 7671:2018+A4:2026 renumbered Chapter 61 (Inspection and Testing) to Chapter 64. The insulation resistance requirements previously in Reg 643.3 and Table 61 are now in Reg 643.3 and Table 64. Reg 643.3 was also redrafted to clarify testing procedures for circuits where connected equipment is likely to influence the test or be damaged — introducing the explicit two-stage test sequence in Reg 643.3.3. Readers cross-referencing pre-A4 guidance should note that Table 61 and Table 64 carry the same numeric values.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

Minimum Values — BS 7671 Table 64

BS 7671 Table 64 (Regulation 643.3.2, Chapter 64) sets out the minimum insulation resistance values. In earlier editions this table appeared as Table 61 or Table 61.1 in Chapter 61 — A4:2026 renumbered Chapter 61 to Chapter 64. The values themselves are unchanged:

BS 7671 Table 64 — Minimum Insulation Resistance Values

SELV and PELV circuits (nominal voltage up to and including 50V)

Test voltage: 250V DC | Minimum IR: 0.5 MΩ

Up to and including 500V (e.g. standard 230V and 400V circuits)

Test voltage: 500V DC | Minimum IR: 1.0 MΩ

Above 500V

Test voltage: 1000V DC | Minimum IR: 1.0 MΩ

Note that the general minimum for SELV/PELV circuits is 0.5 MΩ, but for all standard circuits (230V and 400V), the minimum is 1.0 MΩ. In everyday domestic and commercial testing, you will almost always be testing at 500V DC with a minimum of 1.0 MΩ.

GN3 exception — SELV/PELV circuits containing SPDs

Where a SELV or PELV circuit includes equipment such as surge protective devices (SPDs) that may influence the test result or be damaged by higher test voltages, the circuit is tested at 250V DC (rather than 500V DC). In this case GN3 Reg 4.8 raises the minimum acceptable insulation resistance to 1.0 MΩ — not the standard 0.5 MΩ shown in Table 64 for SELV/PELV. Always check whether SPDs or similar components are present before recording a SELV/PELV reading against the 0.5 MΩ threshold.

03 · Testing Guide

Test Voltage by Circuit Voltage

Selecting the correct test voltage is critical. Using too high a test voltage on a circuit rated for lower voltages can damage the insulation. Using too low a test voltage will not adequately stress-test the insulation and may miss defects.

For standard domestic and commercial work in the UK, the vast majority of circuits operate at 230V single-phase or 400V three-phase. These all fall in the "up to and including 500V" category and are tested at 500V DC.

SELV (Separated Extra-Low Voltage) and PELV (Protective Extra-Low Voltage) circuits are tested at 250V DC. These include doorbell transformers, LED strip driver outputs, garden lighting transformers, and bathroom shaver socket SELV supplies. Always check the circuit voltage before selecting the test voltage on your MFT.

BS 7671 Reg 643.3.3 — mandatory two-stage procedure

Where equipment is likely to influence the test or be damaged, Reg 643.3.3 requires a specific two-stage sequence — simple disconnection is not the only option:

  1. 1.Test all cables at 500V DC per Table 64 before connecting any equipment that could be damaged or skew the result. This confirms the wiring insulation is sound.
  2. 2.After connecting the equipment, apply a 250V DC post-connection test between live conductors (linked together) and the protective conductor. The minimum acceptable reading is 1 MΩ. Record the 250V DC test voltage on the schedule of test results (GN3 Reg 2.24).

Note: manufacturer instructions may still require some equipment to be disconnected during the 250V DC stage — follow manufacturer guidance where it applies (Reg 643.3.3 Note).

Auto-validates every IR reading on site

Enter your insulation resistance reading into Elec-Mate and the app instantly validates it against the BS 7671 minimum of 1 MΩ.

Try it free for 7 days
Download on the App StoreGet it on Google Play
04 · Testing Guide

The 1 Megohm Minimum

The 1 megohm minimum is the absolute floor for insulation resistance on standard circuits. Any reading of 0.99 MΩ or below is a fail. However, treating 1 megohm as a "target" would be a mistake — it is the minimum acceptable value, not a good value.

For context, new PVC-insulated cable typically produces insulation resistance readings of 200 MΩ or higher per circuit. A brand-new installation that produces readings of only 2 or 3 megohms would technically pass but should raise serious questions about the quality of the installation. Similarly, an existing installation that has dropped from 50 MΩ at the last EICR to 2 MΩ at this one shows a significant trend of deterioration that warrants investigation even though the absolute value still passes.

IET guidance recommends investigating any reading below 2 MΩ, even though the minimum is 1 MΩ. A reading between 1 and 2 MΩ passes but indicates that the insulation is close to failure and may fail at the next periodic inspection. Recording this as a C3 (improvement recommended) on an EICR is common practice.

05 · Testing Guide

What Affects Insulation Resistance Readings

Several factors affect insulation resistance readings beyond the actual condition of the cable insulation. Understanding these factors helps you interpret your results correctly and avoid false failures.

Temperature

Insulation resistance decreases as temperature increases. For every 10 degrees Celsius rise in temperature, IR approximately halves. Testing on a hot summer day will give lower readings than testing in winter. Always record the ambient temperature alongside your IR results.

Humidity and Moisture

High humidity and moisture reduce IR readings. Water is a conductor — even small amounts of moisture on cable surfaces, in accessories, or in junction boxes can create leakage paths that dramatically reduce the measured IR. Damp environments (basements, bathrooms, outdoor installations) consistently produce lower readings.

Cable Length

Longer cables produce lower IR readings because the total leakage surface area is greater. Each metre of cable adds a parallel leakage path. Very long circuits (100+ metres) may produce readings that appear low but are within expected values for the cable length.

Connected Equipment

Equipment left connected during testing can dramatically reduce IR readings. Electronic devices often have surge protection components (MOVs, TVS diodes) that have low insulation resistance by design. Always disconnect all loads before testing.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
06 · Testing Guide

Troubleshooting Low Insulation Resistance Values

When you get a low IR reading (below 2 MΩ), systematic troubleshooting is needed to identify the cause. The process involves progressively isolating sections of the circuit to narrow down where the fault is.

Troubleshooting Process

  • Step 1: Confirm all loads and equipment are disconnected. Re-test. If the reading improves, a connected device was the cause.
  • Step 2: Disconnect the circuit at the midpoint (or at junction boxes). Test each half separately. This halves the problem — the low-reading half contains the fault.
  • Step 3: Continue subdividing the faulty section until you isolate the specific cable run, junction box, or accessory causing the low reading.
  • Step 4: Inspect the faulty section visually — look for moisture, physical damage, scorching, contamination, or deteriorated insulation.
  • Step 5: Rectify the fault (replace damaged cable, dry out moisture, replace contaminated accessories) and re-test the complete circuit.

Common causes of low IR include: water ingress into buried or concealed cables (especially after heavy rain or plumbing leaks), nails or screws through cables behind plasterboard, rodent damage to cable insulation, thermal degradation in overheated cable runs (behind radiators, in insulated ceiling voids), and deteriorated rubber insulation on pre-1970 wiring systems.

07 · Testing Guide

Three-Phase Insulation Resistance Testing

Three-phase circuits require additional conductor combinations to be tested. As well as the standard all-live-to-earth and live-to-live tests, you must test between each phase combination.

The full set of tests for a three-phase, four-wire circuit is: L1+L2+L3+N to E (all live conductors to earth), L1 to L2, L1 to L3, L2 to L3, L1 to N, L2 to N, L3 to N. All readings must be at least 1.0 MΩ. In practice, many electricians use the "all connected together" method — connect all live conductors together and test to earth in one go, then separate them and test between each pair. The first test confirms the cable-to-earth insulation; the individual tests confirm the inter-conductor insulation.

For three-phase motors, the motor windings themselves have their own insulation resistance that is tested separately from the cable. Motor winding IR testing is beyond the scope of standard BS 7671 testing and is covered by BS EN 60034-1. However, if a three-phase circuit feeding a motor produces a low IR reading, disconnecting the motor and re-testing will clarify whether the problem is in the cable or the motor.

For more on testing three-phase installations, see our dedicated three-phase testing guide.

08 · Testing Guide

Recording Insulation Resistance Results

Insulation resistance results are recorded on the schedule of test results on the EICR or EIC. For each circuit, record the IR value in megohms, the test voltage used (250V, 500V, or 1000V), and the conductor combination tested.

Where the instrument displays a reading greater than its maximum range (e.g., "> 200 MΩ" or "> 999 MΩ"), record the value as shown — for example, "> 200" in the IR column. This indicates excellent insulation. Do not record it as "pass" or "OK" — the actual value (or the maximum displayed value) must be recorded.

If any circuit produces a reading below 1.0 MΩ, the circuit fails and the fault must be investigated and rectified. On an EICR, a failing IR reading is recorded as an observation with the appropriate observation code. On an EIC, the certificate should not be issued until the insulation fault is rectified.

09 · Testing Guide

Insulation Resistance Testing with Elec-Mate

Elec-Mate auto-validates every insulation resistance reading as you enter it. Any reading below 1.0 MΩ is flagged immediately in the schedule of tests, and the app prompts you to record an observation with the appropriate code. Readings between 1 and 2 MΩ trigger a warning suggesting further investigation.

Instant IR validation on site

Enter your insulation resistance readings and Elec-Mate validates each one against the BS 7671 minimum of 1 MΩ. Failures are flagged in red.

Try it free for 7 days
Download on the App StoreGet it on Google Play

The app records the test voltage alongside each IR value and includes the complete schedule of tests with auto-validated IR, R1+R2, Zs, and RCD results — all cross-referenced against BS 7671 limits for the protective device on each circuit.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Auto-validate every IR reading on site

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. Instant BS 7671 validation for insulation resistance, Zs, R1+R2, and RCD results. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy