Continuity testing (R1+R2) on three-phase circuits follows the same principles as single-phase — the long lead method is used to measure the combined resistance of the phase conductor and CPC. However, you must measure R1+R2 on each phase separately because the cable routing may differ and the connection resistances at terminals may vary.
For a three-phase circuit with a four-core (or five-core) cable, connect the long lead between each phase conductor and the CPC in turn. Record R1+R2 for L1, L2, and L3 separately. The readings should be approximately equal for all three phases if the cable is symmetrical (which it should be for a multi-core cable). Significant differences between phases indicate a problem — possibly a high-resistance connection on one phase terminal.
For three-phase systems using single-core cables (for example, SWA singles in trefoil), the cable lengths for each phase may genuinely differ slightly depending on the routing, so small differences in R1+R2 between phases are expected.
Polarity is a separate required dead test — distinct from phase rotation. Polarity confirms each conductor is correctly connected to its intended terminal at every accessory and outlet. Per Reg 442.1.2, both polarity results (single-phase circuits) and phase rotation (three-phase installations) must be recorded on the Generic Schedule of Test Results (Appendix 6) before the installation is energised.