Insulation resistance testing on three-phase circuits requires testing between all conductor combinations. The minimum acceptable value is 1.0 MΩ per BS 7671 Table 64 (Reg 643.3.2) at 500 V DC test voltage for standard 400 V circuits.
The full test set is: all live conductors connected together to earth (L1+L2+L3+N to E), then between each pair of live conductors (L1-L2, L1-L3, L2-L3, L1-N, L2-N, L3-N). All three-phase equipment must be disconnected before testing — motors, variable speed drives, contactors with electronic coils, and control panel electronics.
A4:2026 note (Reg 643.3.3): Where connected equipment is likely to influence the measurement or result of the test, or be damaged — VSD panels, control electronics and the like — the test shall be applied prior to the connection of that equipment, in accordance with Table 64 (500 V DC, 1.0 MΩ minimum for a 400 V installation). Following connection of the equipment, a further test at 250 V DC shall then be applied between live conductors and the protective conductor connected to the earthing arrangement, and the insulation resistance shall be at least 1 MΩ. The 250 V DC test is an additional post-connection check, not a substitute for the 500 V DC test. Note that manufacturers' instructions may still recommend disconnecting some equipment even for the 250 V DC test, as it can influence the result.
For more detail on insulation resistance values, test voltages, and troubleshooting, see the insulation resistance minimum values guide.