TESTING GUIDE

Earth Fault Loop Impedance Explained: Ze and Zs Guide

The complete guide to earth fault loop impedance for UK electricians. What Ze and Zs are, why loop impedance determines disconnection time, maximum Zs values per BS 7671, how to measure Ze and Zs, the 0.8 temperature correction factor, TN-C-S vs TN-S vs TT typical values, and what to do when Zs exceeds the maximum.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

20 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Earth fault loop impedance (Zs) is the total impedance of the complete fault current path — from the point of fault, through the CPC, through the external earth return, and back through the transformer to the supply phase.
  • 2Ze is the external earth fault loop impedance measured at the origin of the installation. Zs is the total: Zs = Ze + (R1+R2), where R1+R2 is the resistance of the circuit conductors.
  • 3The maximum permitted Zs values in BS 7671 Tables 41.2, 41.3, and 41.4 ensure the protective device disconnects within the required time (0.4 s for final circuits, 5 s for distribution circuits).
  • 4Temperature correction: measured Zs at ambient temperature should not exceed 80% of the tabulated maximum (multiply by 0.8) to allow for conductor resistance increase at operating temperature.
  • 5Elec-Mate provides a Zs lookup calculator by protective device type and rating, auto-validates every measured Zs in the schedule of tests, and records Ze at the origin on the EICR.
01 · Testing Guide

What Is Earth Fault Loop Impedance?

Earth fault loop impedance is the total impedance of the complete path that fault current takes when a line conductor comes into contact with earth — either directly or through a metallic enclosure. This path forms a loop: from the supply transformer, through the line conductor to the point of fault, through the fault itself, through the circuit protective conductor (CPC) back to the main earthing terminal, through the external earth return path back to the supply transformer, and through the transformer winding back to the line conductor.

The total impedance of this loop determines how much fault current flows when an earth fault occurs. By Ohm's law, fault current equals supply voltage divided by loop impedance: If = Uo / Zs. The higher the loop impedance, the lower the fault current. The lower the fault current, the longer the protective device takes to operate — and if the impedance is too high, the device may not operate at all within the required time, leaving a dangerous situation where metalwork is energised at a voltage that could cause lethal electric shock.

This is why earth fault loop impedance testing is one of the most critical measurements in electrical testing. It is test number five in the GN3 testing sequence — the first live test, carried out after all dead tests have confirmed that the wiring is intact and safe to energise.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

Ze — External Earth Fault Loop Impedance

Ze represents the portion of the earth fault loop that is external to the installation — the part that you, as the electrician, cannot change. It includes the impedance of the supply transformer winding, the supply line conductor from the transformer to the origin of the installation, and the external earth return path from the installation back to the transformer.

The external earth return path differs depending on the earthing system:

Maximum Assumed Ze Values by Earthing System

  • TN-C-S (PME): Maximum assumed Ze = 0.35 ohms. The earth return is via the combined neutral/earth (PEN) conductor of the supply cable. This gives the lowest Ze because the PEN conductor has very low impedance. Typical measured values range from 0.10 to 0.35 ohms.
  • TN-S (cable sheath): Maximum assumed Ze = 0.80 ohms. The earth return is via the metallic sheath or armour of the supply cable. This has higher impedance than a PEN conductor. Typical measured values range from 0.30 to 0.80 ohms, though older cable sheaths with corroded joints can exceed this.
  • TT (earth electrode): Maximum assumed Ze = 21 ohms. The earth return is through the general mass of earth via an earth electrode. The impedance is much higher and varies enormously depending on soil type, moisture content, and electrode characteristics. Typical values range from 10 to 200+ ohms.

Ze is measured at the origin of the installation with the main earthing conductor temporarily disconnected from the main earthing terminal. This isolates the installation earth from the supply earth so you measure only the external loop. The value is recorded on the EICR or EIC.

03 · Testing Guide

Zs — Total Earth Fault Loop Impedance

Zs is the total earth fault loop impedance measured at a specific point in the installation. It includes everything in Ze, plus the impedance of the installation wiring from the distribution board to the point of measurement. The relationship is:

Zs = Ze + (R1 + R2)

Where R1 = line conductor resistance, R2 = CPC resistance

R1 and R2 are the resistances of the line conductor and CPC respectively, measured from the distribution board to the point of test. These are the same R1 and R2 values obtained during continuity testing (test 1 in the GN3 sequence). By adding the measured R1+R2 to the measured Ze, you can calculate the expected Zs and compare it against the measured Zs as a verification check.

Zs is measured at the furthest point of each circuit because this gives the highest (worst-case) value — the point where the conductor lengths are longest and therefore the impedances are highest. If Zs passes at the furthest point, it will pass at every other point on the circuit.

Zs lookup by protective device — instant maximum values

Select the protective device type (B, C, D MCB, BS 3036 fuse, BS 88 fuse) and rating…

Try it free for 7 days
Download on the App StoreGet it on Google Play
04 · Testing Guide

Why Earth Fault Loop Impedance Determines Disconnection Time

The connection between loop impedance and disconnection time is fundamental to electrical safety. BS 7671 requires that in the event of an earth fault, the protective device must disconnect the supply within a maximum time to prevent electric shock. The required disconnection times are:

  • 0.4 seconds: Final circuits supplying socket outlets and circuits supplying portable equipment outdoors. This is the maximum time for most circuits in a domestic installation.
  • 5 seconds: Distribution circuits (those feeding other distribution boards, not final circuits directly).
  • 0.2 seconds: Required for some specific situations, such as circuits in medical locations per Section 710.

The protective device has a time-current characteristic: it operates faster when more current flows through it. An MCB rated at 32 A might take 5 seconds to trip at 100 A but only 0.01 seconds at 500 A. The maximum Zs values in BS 7671 are calculated so that the resulting fault current (Uo/Zs) is sufficient to make the device operate within the required disconnection time.

For example, a Type B 32 A MCB trips magnetically at 5 times its rated current (5 x 32 = 160 A). BS 7671 applies a voltage factor Cmin = 0.95 to account for supply voltage tolerance, giving 0.95 x 230 = 218.5 V. The maximum loop impedance is therefore 218.5/160 = 1.37 ohms. This is exactly the value you find in BS 7671 Table 41.3 for a B32 MCB.

05 · Testing Guide

Maximum Zs Values per BS 7671

The maximum permitted Zs values are found in BS 7671 Tables 41.2 (BS 3036 fuses), 41.3 (Type B MCBs), and 41.4 (Type C and Type D MCBs). These tables give the values at the maximum conductor operating temperature. For a complete reference, see our dedicated maximum Zs values guide.

The regulatory framework behind Zs verification is set out in Reg 643.7.3.1, which requires that where protective measures depend on a knowledge of earth fault loop impedance, the relevant impedances shall be measured or determined by an alternative method, and the measured values shall comply with Chapter 41. Reg 411.4.202 sets out how compliance is demonstrated for circuit-breakers: the maximum Zs shall be determined by the formula in Reg 411.4.4 (Zs = Uo × Cmin / Ia), or — for a nominal voltage of 230 V — the values in Table 41.3 may be used directly as an alternative to calculation. Using Table 41.3 directly is the standard on-site approach; the formula route is used where a device is not listed in the table or where a non-standard voltage applies.

Type B MCBs — Maximum Zs for 0.4 s Disconnection (Key Ratings)

  • B6: 7.28 Ω (corrected: 5.82 Ω)
  • B10: 4.37 Ω (corrected: 3.50 Ω)
  • B16: 2.73 Ω (corrected: 2.18 Ω)
  • B20: 2.19 Ω (corrected: 1.75 Ω)
  • B32: 1.37 Ω (corrected: 1.10 Ω)
  • B40: 1.09 Ω (corrected: 0.87 Ω)
  • B50: 0.87 Ω (corrected: 0.70 Ω)

The "corrected" values in brackets are the tabulated maximum multiplied by 0.8 — the values your measured Zs should not exceed when testing at ambient temperature.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
06 · Testing Guide

How to Measure Ze and Zs

Earth fault loop impedance measurements are live tests — they require the circuit to be energised at mains voltage. They can only be performed safely after all dead tests (continuity, insulation resistance, polarity) have been completed satisfactorily.

Measuring Ze

Ze is measured at the origin of the installation. Temporarily disconnect the main earthing conductor from the main earthing terminal (MET). Using the loop impedance function on your MFT, measure between the incoming line terminal and the disconnected end of the earthing conductor. Record the value. Reconnect the earthing conductor immediately.

Safety warning: While the main earthing conductor is disconnected, the entire installation has no earth connection. This must be done as quickly as possible, and no one should use the installation during this period.

Professional tip (OSG Reg 1.3): On new installations, obtain the typical maximum Ze from the electricity distributor before starting work. The distributor can provide this value for the supply address, allowing you to calculate the maximum achievable Zs and verify disconnection times during the design stage — without needing a site measurement at the origin.

Measuring Zs

With the earthing conductor reconnected and the circuit energised, measure Zs at the furthest point of each circuit using the loop impedance function on your MFT. For socket circuits, plug the test instrument into the last socket. For lighting circuits, measure at the last light fitting. The reading includes Ze plus R1+R2 for that circuit. Compare against the maximum permitted Zs for the protective device.

Voice to test results — speak Zs values on site

With your MFT in one hand, speak: 'Ring 1, Zs 0.89 ohms.' Elec-Mate fills in the schedule of test results and validates the value against the maximum Zs…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Testing Guide

Temperature Correction — The 0.8 Factor

The maximum Zs values in BS 7671 tables are given at the maximum conductor operating temperature — typically 70 degrees Celsius for PVC-insulated cables. However, when you measure Zs on site, the conductors are usually at ambient temperature (approximately 10 to 25 degrees Celsius). As the installation operates and cables carry their design current, the conductor temperature rises and their resistance increases.

Copper conductor resistance increases by approximately 0.4% per degree Celsius. Between 20 degrees Celsius (ambient) and 70 degrees Celsius (maximum operating temperature for PVC), this is a 20% increase. The 0.8 factor compensates for this: if your measured Zs at ambient temperature is no more than 80% of the tabulated maximum, the actual Zs under load (when conductors are hot) should still be within the tabulated maximum.

Example Calculation

For a B32 MCB, the tabulated maximum Zs is 1.37 ohms (at 70 degrees Celsius). Applying the 0.8 factor: 1.37 x 0.8 = 1.10 ohms. Your measured Zs at ambient temperature should not exceed 1.10 ohms. If you measure 1.20 ohms, it passes the tabulated maximum but fails the corrected maximum — when the cables heat up under load, the actual Zs could exceed 1.37 ohms and the circuit would not disconnect within 0.4 seconds.

The 0.8 correction factor appears as the cold-measured site limit within GN3 and is embedded alongside every entry in Table 41.3 of BS 7671 (Reg 411.4.204). For example, the B20 MCB entry states a tabulated maximum of 2.19 ohms and a cold-measured site limit of 1.75 ohms. This makes the 0.8 factor part of the standard's normative guidance package, not merely an optional IET practice — it should be treated as the working limit for on-site testing. Elec-Mate applies the 0.8 correction automatically when validating Zs measurements.

08 · Testing Guide

TN-C-S vs TN-S vs TT — Typical Ze and Zs Values

The earthing system of the supply significantly affects the Ze value and therefore the achievable Zs. Understanding the typical values for each system helps you anticipate whether circuits are likely to pass or fail before you start testing.

TN-C-S (PME) Systems

Maximum assumed Ze: 0.35 ohms. Typical measured values: 0.10 to 0.35 ohms. With such a low Ze, there is plenty of headroom for R1+R2, and most circuits pass Zs comfortably. PME is the most common supply type for modern domestic installations in the UK. The low Ze means even long cable runs with small conductors usually achieve acceptable Zs values.

TN-S (Cable Sheath) Systems

Maximum assumed Ze: 0.80 ohms. Typical measured values: 0.30 to 0.80 ohms. The higher Ze consumes more of the available Zs budget, so circuits with long cable runs or small CPCs may fail. Common in older properties with lead-sheathed or steel-wire-armoured supply cables. Corroded sheath joints can increase Ze above the maximum assumed value.

TT (Earth Electrode) Systems

Maximum assumed Ze: 21 ohms. Typical measured values: 10 to 200+ ohms. The very high Ze means Zs will almost certainly exceed the maximum permitted values for MCBs alone. TT systems require RCD protection on all circuits — RCD testing is therefore critical. The RCD provides disconnection based on leakage current rather than fault current magnitude, and compliance for TT systems is assessed against the maximum Zs values in BS 7671 Table 41.5 (Reg 411.5.3) rather than Table 41.3.

Table 41.5 — Maximum Zs for RCD-protected TT systems (230 V)

  • 30 mA RCD: 1,667 Ω
  • 100 mA RCD: 500 Ω
  • 300 mA RCD: 167 Ω
  • 500 mA RCD: 100 Ω

Source: BS 7671:2018+A4:2026 Table 41.5, Reg 411.5.3. Applies to non-delayed and time-delayed 'S' Type RCDs to BS EN 61008-1 / BS EN 61009-1.

09 · Testing Guide

What to Do if Zs Is Too High

If the measured Zs exceeds the maximum permitted value (after applying the 0.8 correction factor), you must take action. The circuit does not comply with BS 7671 and the protective device will not disconnect within the required time in the event of an earth fault.

Options When Zs Exceeds Maximum

  • Verify the reading: Retest to confirm. Compare measured Zs against Ze + (R1+R2). Check for high-resistance connections. Ensure your instrument is calibrated.
  • Reduce R1+R2: Increase the cable size, shorten the cable run, or use a larger CPC. This directly reduces R1+R2 and therefore Zs.
  • Change the protective device: A Type B MCB has a higher maximum Zs than a Type C or Type D MCB of the same rating. If the load permits, changing from Type C to Type B may bring Zs within limits.
  • Add RCD protection: An RCD provides fault disconnection that does not depend on Zs. A 30 mA RCD will trip at 30 mA of earth leakage current regardless of the loop impedance.

On an EICR, a Zs value exceeding the maximum permitted value is recorded as an observation. The classification code depends on the severity — C2 (potentially dangerous) or C3 (improvement recommended) depending on whether RCD protection is present and functioning.

Auto-validated Zs in the schedule of tests

Elec-Mate validates every measured Zs against BS 7671 maximum permitted values for the specific protective device on each circuit.

Try it free for 7 days
Download on the App StoreGet it on Google Play

How to Measure Ze and Zs — Step by Step

Step-by-step procedure for measuring external earth fault loop impedance (Ze) and total earth fault loop impedance (Zs) per BS 7671 and IET Guidance Note 3.

1

Complete all dead tests first

Before measuring earth fault loop impedance, all dead tests must be completed satisfactorily — continuity of protective conductors, ring circuit continuity (if applicable), insulation resistance, and polarity. Energising a circuit without completing dead tests risks short circuits, electric shock, or instrument damage.

2

Measure Ze at the origin

Temporarily disconnect the main earthing conductor from the main earthing terminal (MET). Using the loop impedance function on your MFT, measure between the incoming line terminal and the disconnected earthing conductor. Record the Ze value. Reconnect the earthing conductor immediately. Ze is recorded on the EICR or EIC.

3

Energise the circuit under test

Restore the circuit to its normal operating condition — reconnect loads, replace fuses, close covers. Remove lock-off devices and warning labels from the dead testing phase. Energise the circuit at the distribution board.

4

Measure Zs at the furthest point

Using the loop impedance function on your MFT, measure Zs at the furthest point of each circuit — this gives the highest (worst-case) Zs value. For socket circuits, measure at the last socket on the circuit. For lighting circuits, measure at the last lighting point.

5

Compare against maximum permitted Zs

Look up the maximum permitted Zs for the protective device type and rating from BS 7671 Tables 41.2, 41.3, or 41.4. Apply the 0.8 temperature correction factor — your measured Zs should not exceed 80% of the tabulated maximum. Elec-Mate does this lookup and comparison automatically.

6

Verify Zs against Ze + (R1+R2)

Check that the measured Zs is approximately equal to Ze + (R1+R2) from your dead test results. If the measured Zs is significantly higher than the calculated value, investigate for high-resistance connections in the earth path. Record all values on the schedule of test results.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Validate Zs against BS 7671 automatically on site

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. Zs lookup by protective device, auto-validation, voice test entry, 70+ calculators. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy