REFERENCE GUIDE

Maximum Zs Values BS 7671: Complete Table Guide

The complete reference to maximum Zs values per BS 7671 for UK electricians. Tables 41.2, 41.3, and 41.4 with values for Type B MCBs, Type C MCBs, and BS 3036 fuses. The 0.8 temperature correction factor, how to use the tables, and what to do when Zs exceeds the maximum permitted value.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

16 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Maximum Zs values are the highest earth fault loop impedance that ensures the protective device will disconnect within the required time (0.4 s for final circuits, 5 s for distribution circuits) in the event of an earth fault.
  • 2BS 7671 Tables 41.2 (BS 3036 fuses), 41.3 (Type B MCBs), and 41.4 (Type C and D MCBs) provide the maximum values at maximum conductor operating temperature. Apply the 0.8 correction factor when testing at ambient.
  • 3Key Type B MCB values for 0.4 s disconnection: B6=7.28 ohms, B10=4.37 ohms, B16=2.73 ohms, B20=2.19 ohms, B32=1.37 ohms, B40=1.09 ohms, B50=0.87 ohms.
  • 4Type C MCBs have lower maximum Zs values than Type B (same rating) because they require higher fault current to trip magnetically — Type C trips at 10x rated current vs 5x for Type B.
  • 5Elec-Mate provides an instant Zs lookup calculator — select the protective device type and rating, and the app shows the maximum permitted Zs with the 0.8 correction already applied.
01 · Reference Guide

What Are Maximum Zs Values?

Maximum Zs values are the highest earth fault loop impedance values at which a protective device (MCB, fuse, or RCBO) will still disconnect the supply within the required time in the event of an earth fault. BS 7671 specifies maximum disconnection times of 0.4 seconds for final circuits and 5 seconds for distribution circuits. The maximum Zs values in the BS 7671 tables are calculated to ensure these disconnection times are achieved.

The calculation is straightforward: the protective device has a time-current characteristic that defines the minimum current at which it will trip within the required time. BS 7671 applies a voltage factor Cmin of 0.95 to the nominal 230 V supply to account for voltage tolerance (per Appendix 3), giving an effective voltage of 218.5 V. Using Ohm's law, the maximum Zs equals this effective voltage divided by the minimum trip current. For example, a Type B 32 A MCB trips magnetically at 5 times its rated current (160 A), giving a maximum Zs of 218.5/160 = 1.37 ohms.

If the actual earth fault loop impedance (Zs) exceeds the maximum permitted value, the fault current will be insufficient to trip the protective device within the required time. This means that in the event of an earth fault, metalwork could remain live at a dangerous voltage for longer than the permitted duration, creating a risk of lethal electric shock.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Reference Guide

Type B MCB Maximum Zs Values — BS 7671 Table 41.3

Type B MCBs are the most commonly used protective devices in domestic and light commercial installations. They trip magnetically at 3 to 5 times their rated current. The BS 7671 maximum Zs values are calculated using the worst case (5 times rated current) to ensure compliance even at the upper end of the device tolerance.

Type B MCBs — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
B67.28 Ω5.82 Ω
B104.37 Ω3.50 Ω
B162.73 Ω2.18 Ω
B202.19 Ω1.75 Ω
B251.75 Ω1.40 Ω
B321.37 Ω1.10 Ω
B401.09 Ω0.87 Ω
B500.87 Ω0.70 Ω

The rightmost column shows the corrected values (tabulated x 0.8) that your measured Zs at ambient temperature should not exceed. These are the values you compare your MFT readings against on site.

Instant Zs lookup by protective device

Select the MCB type (B, C, or D) and rating in Elec-Mate, and the app instantly shows both the tabulated and corrected (x 0.8) maximum Zs values.

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · Reference Guide

Type C MCB Maximum Zs Values — BS 7671 Table 41.4

Type C MCBs have a higher magnetic trip point than Type B — they trip at 5 to 10 times their rated current (compared to 3 to 5 times for Type B). This higher trip threshold makes them suitable for circuits with high inrush currents (motors, discharge lighting, transformers) but results in lower maximum Zs values because more fault current is needed to achieve rapid disconnection.

Type C MCBs — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
C63.64 Ω2.91 Ω
C102.19 Ω1.75 Ω
C161.37 Ω1.10 Ω
C201.09 Ω0.87 Ω
C250.87 Ω0.70 Ω
C320.68 Ω0.54 Ω
C400.55 Ω0.44 Ω
C500.44 Ω0.35 Ω

Notice how much lower the Type C values are compared to Type B at the same rating. A C32 has a corrected maximum of only 0.54 ohms, compared to 1.10 ohms for a B32. This is why Type C MCBs should only be used where the inrush current characteristics of the load genuinely require them — using Type C unnecessarily on a lighting or socket circuit significantly reduces the available Zs margin and may cause the circuit to fail.

04 · Reference Guide

BS 3036 Rewirable Fuse Maximum Zs Values — BS 7671 Table 41.2

BS 3036 rewirable fuses (also known as semi-enclosed fuses) are the older type of fuse that uses replaceable fuse wire. They are still found in many existing installations in the UK, particularly in properties that have not been rewired. The maximum Zs values for BS 3036 fuses are specified in BS 7671 Table 41.2.

BS 3036 Fuses — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
5 A10.35 Ω8.28 Ω
15 A3.26 Ω2.61 Ω
20 A2.51 Ω2.01 Ω
30 A1.69 Ω1.35 Ω
45 A1.14 Ω0.91 Ω

BS 3036 fuses have less predictable operating characteristics than MCBs because the fuse wire can deteriorate over time, oxidise, or even be replaced with the wrong rating by someone who is not qualified. The values in Table 41.2 already include a built-in correction factor of 0.725 to account for this variability. The 0.8 temperature correction should still be applied on top of these values when testing at ambient temperature.

05 · Reference Guide

The 0.8 Temperature Correction Factor

The maximum Zs values in BS 7671 tables are specified at the maximum conductor operating temperature — 70 degrees Celsius for PVC-insulated cables (which covers the vast majority of domestic installations). When you measure Zs on site with your multifunction tester, the conductors are at ambient temperature — typically between 10 and 25 degrees Celsius.

As cables carry current during normal operation, they heat up. Copper conductor resistance increases by approximately 0.4% per degree Celsius. Between ambient temperature (20 degrees Celsius) and maximum operating temperature (70 degrees Celsius), this is an increase of approximately 20%. The impedance of the earth fault loop therefore increases by the same proportion when the cables are at their operating temperature.

Applying the 0.8 Factor

Multiply the tabulated maximum Zs by 0.8 to get the corrected ambient maximum. Your measured Zs should not exceed this corrected value.

Example — B32 MCB:

Tabulated maximum Zs = 1.37 Ω (at 70 degrees Celsius)

Corrected ambient maximum = 1.37 x 0.8 = 1.10 Ω

If you measure Zs = 1.15 Ω at ambient, this exceeds the corrected maximum (1.10 Ω) even though it is below the tabulated maximum (1.37 Ω). When the cables heat up under load, the actual Zs could reach 1.44 Ω — exceeding the tabulated maximum and preventing disconnection within the required time.

The 0.8 factor is a design guideline recommended by the IET rather than a regulation within BS 7671 itself. However, it is widely adopted, expected by verifying bodies, and considered best practice. Elec-Mate applies the 0.8 correction automatically when validating Zs measurements.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Reference Guide

How to Use the Maximum Zs Tables

Using the maximum Zs tables is straightforward once you understand the process. For each circuit in the installation, follow these steps:

  • Step 1 — Identify the device: Determine the type (B, C, D, or fuse) and rating of the protective device for the circuit. Check the front of the MCB or RCBO.
  • Step 2 — Find the table: Use Table 41.2 for BS 3036 fuses, Table 41.3 for Type B MCBs, Table 41.4 for Type C or D MCBs. Use the 0.4 s column for final circuits or the 5 s column for distribution circuits.
  • Step 3 — Apply the 0.8 factor: Multiply the tabulated value by 0.8. This gives the maximum Zs your measured value should not exceed when testing at ambient temperature.
  • Step 4 — Compare: Compare your measured Zs against the corrected maximum. If the measured value is below the corrected maximum, the circuit passes. If it exceeds the corrected maximum, investigate further.

You should also verify that the measured Zs is consistent with the calculated value of Ze + (R1+R2). If the measured Zs is significantly higher than the calculated value, there may be a high-resistance connection in the earth path that requires investigation.

70+ calculators including Zs lookup

Elec-Mate has 70+ electrical calculators built in, including the Zs lookup by protective device.

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Reference Guide

What to Do When Zs Exceeds the Maximum

If the measured Zs exceeds the corrected maximum (tabulated x 0.8), the circuit does not comply and action must be taken. The specific action depends on the circumstances and the extent to which the maximum is exceeded.

Verify the measurement

Retest to confirm the reading. Check that your instrument is calibrated. Compare the measured Zs against Ze + (R1+R2) — if there is a large discrepancy, investigate for high-resistance connections. A loose terminal, corroded earthing clamp, or damaged conductor can add significant impedance.

Reduce R1+R2

Increase the cable size (lower resistance per metre), install a larger CPC, or shorten the cable run. This directly reduces R1+R2 and therefore Zs. For example, upgrading from 2.5/1.5 mm² to 4.0/2.5 mm² cable significantly reduces R1+R2.

Change the protective device type

Type B MCBs have higher maximum Zs values than Type C. If the load does not require the higher inrush current tolerance of a Type C device, changing from Type C to Type B may bring Zs within limits. For example, a C32 has a corrected maximum of 0.54 Ω while a B32 has 1.10 Ω — double the headroom.

Add RCD protection

An RCD provides earth fault disconnection that does not depend on Zs. A 30 mA RCD will trip at 30 mA of earth leakage regardless of the loop impedance. This is the standard approach for TT systems where Zs is inherently high.

On an EICR, a Zs value exceeding the maximum permitted value is recorded as an observation. The classification depends on the severity: C2 (potentially dangerous) if no RCD protection is present, or C3 (improvement recommended) if RCD protection is providing adequate disconnection despite the high Zs.

08 · Reference Guide

5-Second Disconnection Values

BS 7671 also provides maximum Zs values for 5-second disconnection times. These apply to distribution circuits — circuits that supply other distribution boards but do not directly supply current-using equipment or socket outlets. The 5-second values are higher (more lenient) because the risk of electric shock is lower on distribution circuits.

Type B MCBs — 5-Second vs 0.4-Second Maximum Zs (Selected Ratings)

Rating0.4 s Max Zs5 s Max Zs
B162.73 Ω4.55 Ω
B321.37 Ω2.28 Ω
B401.09 Ω1.82 Ω
B500.87 Ω1.46 Ω

In a typical domestic installation, only the circuit feeding a sub-distribution board (if present) would use the 5-second values. All circuits supplying socket outlets, lighting, cookers, showers, and other current-using equipment must use the 0.4-second values. If in doubt, use the 0.4-second values — they are more conservative and always compliant.

09 · Reference Guide

Zs Lookup and Validation with Elec-Mate

Elec-Mate removes the need to carry BS 7671 tables on site. The app provides an instant Zs lookup calculator — select the protective device type (B, C, D MCB, BS 3036 fuse, BS 88 fuse) and rating, and the app shows both the tabulated maximum Zs and the corrected value (tabulated x 0.8) immediately.

Schedule of tests with auto-Zs-validation

Enter your measured Zs values into the schedule of test results and Elec-Mate validates every reading against the BS 7671 maximum for the specific…

Try it free for 7 days
Download on the App StoreGet it on Google Play

The auto-validation works across all test values — not just Zs. Insulation resistance is checked against the 1 MΩ minimum, RCD trip times are checked against the 40 ms and 300 ms limits, and R1+R2 values are cross-referenced with Zs. Voice-to-test-results lets you speak values while testing — no clipboards, no double-handling of data.

Voice to test results — speak Zs values hands-free

On site with your MFT in hand? Just speak: 'Ring 1, Zs 0.89 ohms.' Elec-Mate fills in the schedule and validates automatically.

Try it free for 7 days
Download on the App StoreGet it on Google Play

How to Look Up and Apply Maximum Zs Values

Step-by-step guide to looking up maximum Zs values from BS 7671 tables, applying the 0.8 temperature correction factor, and comparing measured Zs values.

1

Identify the protective device type and rating

Check the type (B, C, or D for MCBs; or the fuse type for BS 3036 or BS 88) and the current rating (6 A, 10 A, 16 A, 20 A, 32 A, 40 A, 50 A, etc.) of the protective device for the circuit under test. This information is printed on the front of the device.

2

Look up the maximum Zs from the correct table

Find the maximum permitted Zs from the appropriate BS 7671 table: Table 41.2 for BS 3036 fuses, Table 41.3 for Type B MCBs (0.4 s disconnection), Table 41.4 for Type C and Type D MCBs. Use the 0.4-second values for final circuits or the 5-second values for distribution circuits.

3

Apply the 0.8 temperature correction factor

Multiply the tabulated maximum Zs by 0.8 to obtain the corrected maximum for ambient temperature testing. For example, B32 tabulated maximum = 1.37 ohms; corrected maximum = 1.37 x 0.8 = 1.10 ohms. Your measured Zs at ambient temperature should not exceed this corrected value.

4

Measure Zs at the furthest point of the circuit

Using the loop impedance function on your multifunction tester, measure Zs at the furthest point of the circuit (the point with the longest cable run). This gives the highest Zs value on the circuit. If this passes, all other points on the circuit will also pass.

5

Compare the measured value against the corrected maximum

Compare your measured Zs against the corrected maximum (tabulated x 0.8). If the measured value is below the corrected maximum, the circuit passes. If it exceeds the corrected maximum, investigate and consider remedial options. Elec-Mate performs this lookup and comparison automatically for every circuit.

6

Record the result on the schedule of test results

Enter the measured Zs value on the schedule of test results. Note the protective device type and rating. If Zs exceeds the maximum, record the appropriate observation code on the EICR (C2 or C3 depending on the circumstances and presence of RCD protection).

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Look up maximum Zs values instantly on site

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. Instant Zs lookup, auto-validation, voice test entry, 70+ calculators. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy