REFERENCE GUIDE

Maximum Zs Values BS 7671: Complete Table Guide

The complete reference to maximum Zs values per BS 7671 for UK electricians. Tables 41.2, 41.3, and 41.4 with values for Type B MCBs, Type C MCBs, and BS 3036 fuses. The 0.8 temperature correction factor, how to use the tables, and what to do when Zs exceeds the maximum permitted value.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

16 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Maximum Zs values are the highest earth fault loop impedance that ensures the protective device will disconnect within the required time in the event of an earth fault. In a TN system that is 0.4 s for the final circuits covered by Regulation 411.3.2.2, and 5 s for distribution circuits and any circuit outside that scope (Regulation 411.3.2.3).
  2. 02BS 7671 Table 41.2 covers fuses at 0.4 s, Table 41.3 covers circuit-breakers (Types B, C and D are all in that one table), and Table 41.4 covers fuses at 5 s. NOTE 2 to each table sets the temperature basis: line conductors at the maximum permitted operating temperature of Table 52.2, protective conductors at the assumed initial temperature of Tables 54.2 to 54.5. Apply the 0.8 factor of Appendix 3 when testing at ambient.
  3. 03Key Type B MCB values for 0.4 s disconnection: B6=7.28 ohms, B10=4.37 ohms, B16=2.73 ohms, B20=2.19 ohms, B32=1.37 ohms, B40=1.09 ohms, B50=0.87 ohms.
  4. 04Type C MCBs have lower maximum Zs values than Type B (same rating) because they require higher fault current to trip magnetically — Type C trips at 10x rated current vs 5x for Type B.
  5. 05Elec-Mate provides an instant Zs lookup calculator — select the protective device type and rating, and the app shows the maximum permitted Zs with the 0.8 correction already applied.

01 · Reference Guide

What Are Maximum Zs Values?

Jump to the free Zs lookup calculator

Maximum Zs values are the highest earth fault loop impedance values at which a protective device (MCB, fuse, or RCBO) will still disconnect the supply within the required time in the event of an earth fault. In a TN system, Regulation 411.3.2.2 and Table 41.1 require 0.4 seconds for final circuits rated up to 63 A with socket-outlets or up to 32 A supplying only fixed connected equipment, and Regulation 411.3.2.3 permits 5 seconds for distribution circuits and for any final circuit outside that scope. Tables 41.2 to 41.4 are the TN tables and are calculated to ensure those times are achieved. TT systems are different — Table 41.1 requires 0.2 seconds and Regulation 411.3.2.4 permits 1 second for a distribution circuit — and on TT the disconnecting device is normally an RCD.

The calculation is straightforward: the protective device has a time-current characteristic that defines the minimum current at which it will trip within the required time. BS 7671 applies a voltage factor Cmin of 0.95 to the nominal 230 V supply to account for voltage tolerance (per Appendix 3), giving an effective voltage of 218.5 V. Using Ohm's law, the maximum Zs equals this effective voltage divided by the minimum trip current. For example, a Type B 32 A MCB trips magnetically at 5 times its rated current (160 A), giving a maximum Zs of 218.5/160 = 1.37 ohms.

If the actual earth fault loop impedance (Zs) exceeds the maximum permitted value, the fault current will be insufficient to trip the protective device within the required time. This means that in the event of an earth fault, metalwork could remain live at a dangerous voltage for longer than the permitted duration, creating a risk of lethal electric shock.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Reference Guide

Type B MCB Maximum Zs Values — BS 7671 Table 41.3

Type B MCBs are the most commonly used protective devices in domestic and light commercial installations. They trip magnetically at 3 to 5 times their rated current. The BS 7671 maximum Zs values are calculated using the worst case (5 times rated current) to ensure compliance even at the upper end of the device tolerance.

Type B MCBs — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
B67.28 Ω5.82 Ω
B104.37 Ω3.50 Ω
B162.73 Ω2.18 Ω
B202.19 Ω1.75 Ω
B251.75 Ω1.40 Ω
B321.37 Ω1.10 Ω
B401.09 Ω0.87 Ω
B500.87 Ω0.70 Ω

The rightmost column shows the corrected values (tabulated x 0.8) that your measured Zs at ambient temperature should not exceed. These are the values you compare your MFT readings against on site.

In the app

Instant Zs lookup by protective device

Select the MCB type (B, C, or D) and rating in Elec-Mate, and the app instantly shows both the tabulated and corrected (x 0.8) maximum Zs values.

03 · Reference Guide

Type C MCB Maximum Zs Values — BS 7671 Table 41.3

Type C MCBs have a higher magnetic trip point than Type B — they trip at 5 to 10 times their rated current (compared to 3 to 5 times for Type B). This higher trip threshold makes them suitable for circuits with high inrush currents (motors, discharge lighting, transformers) but results in lower maximum Zs values because more fault current is needed to achieve rapid disconnection.

Type C MCBs — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
C63.64 Ω2.91 Ω
C102.19 Ω1.75 Ω
C161.37 Ω1.10 Ω
C201.09 Ω0.87 Ω
C250.87 Ω0.70 Ω
C320.68 Ω0.54 Ω
C400.55 Ω0.44 Ω
C500.44 Ω0.35 Ω

Notice how much lower the Type C values are compared to Type B at the same rating. A C32 has a corrected maximum of only 0.54 ohms, compared to 1.10 ohms for a B32. This is why Type C MCBs should only be used where the inrush current characteristics of the load genuinely require them — using Type C unnecessarily on a lighting or socket circuit significantly reduces the available Zs margin and may cause the circuit to fail.

04 · Reference Guide

BS 3036 Rewirable Fuse Maximum Zs Values — BS 7671 Table 41.2

BS 3036 rewirable fuses (also known as semi-enclosed fuses) are the older type of fuse that uses replaceable fuse wire. They are still found in many existing installations in the UK, particularly in properties that have not been rewired. The maximum Zs values for BS 3036 fuses are specified in BS 7671 Table 41.2.

BS 3036 Fuses — Maximum Zs for 0.4-Second Disconnection

RatingMax Zs (Table)Max Zs (x 0.8)
5 A9.10 Ω7.28 Ω
15 A2.43 Ω1.94 Ω
20 A1.68 Ω1.34 Ω
30 A1.04 Ω0.83 Ω
45 A0.56 Ω0.45 Ω
60 A0.40 Ω0.32 Ω

These are the current Table 41.2 figures. If you are working from older notes you may recognise a different set — 10.35 Ω for a 5 A, 3.26 Ω for a 15 A and so on. Those are the pre-Cmin values and they are no longer correct: NOTE 1 to Table 41.2 records that the tabulated impedances were determined using a Cmin of 0.95, which tightens every figure in the table. Working to the old numbers will pass a circuit that the current edition fails.

BS 3036 fuses have less predictable operating characteristics than MCBs because the fuse wire can deteriorate over time, oxidise, or be replaced with the wrong gauge by someone who is not qualified. That is a good reason to treat a measured value close to the limit with suspicion, and the 0.8 temperature correction still applies when testing at ambient.

05 · Reference Guide

Look Up the Maximum Zs for Your Device

Free to use, no sign-up and no email needed. Choose the device — MCB or RCBO on a B, C or D curve, BS 3036 or BS 88 fuse, or an RCD — and the lookup returns the tabulated maximum Zs from Tables 41.2 to 41.5 alongside the 0.8-corrected figure you compare your ambient reading against. Switch the disconnection time between 0.4 s and 5 s, or type a designation such as B32 or C20 straight into the quick device box.

Working the other way round, the compliance mode takes a measured Zs and lists every protective device that reading would satisfy — useful when you are deciding whether a circuit needs a smaller rating or a different curve.

Type MCB designation

Empty: Quick Device, Device Type.

06 · Reference Guide

The 0.8 Temperature Correction Factor

NOTE 2 to Tables 41.2 to 41.4 sets out the temperature basis, and it is worth reading carefully because it is not simply “everything at 70 degrees”. The tabulated values should not be exceeded when the line conductors are at the maximum permitted operating temperature given in Table 52.2 — 70 degrees Celsius for 70 °C thermoplastic (PVC), which covers the vast majority of domestic installations — and the circuit protective conductors are at the assumed initial temperature given in Tables 54.2 to 54.5. When you measure Zs on site with your multifunction tester, the conductors are at ambient temperature — typically between 10 and 25 degrees Celsius — and NOTE 2 directs you to Appendix 3 to adjust the reading.

As cables carry current during normal operation, they heat up. Copper conductor resistance increases by approximately 0.4% per degree Celsius. Between ambient temperature (20 degrees Celsius) and maximum operating temperature (70 degrees Celsius), this is an increase of approximately 20%. The impedance of the earth fault loop therefore increases by the same proportion when the cables are at their operating temperature.

Applying the 0.8 Factor

Multiply the tabulated maximum Zs by 0.8 to get the corrected ambient maximum. Your measured Zs should not exceed this corrected value.

Example — B32 MCB:

Tabulated maximum Zs = 1.37 Ω (at 70 degrees Celsius)

Corrected ambient maximum = 1.37 x 0.8 = 1.10 Ω

If you measure Zs = 1.15 Ω at ambient, this exceeds the corrected maximum (1.10 Ω) even though it is below the tabulated maximum (1.37 Ω). Apply the roughly 20 per cent rise between ambient and 70 °C and the actual Zs under load reaches about 1.38 Ω — over the tabulated maximum, and no longer guaranteed to disconnect within the required time.

The 0.8 factor is not something the trade invented — it is published in BS 7671 itself. Appendix 3 states that where impedance measurements are made at ambient temperature, the requirements of Regulation 411.4.4 or 411.5.4 are considered to be met when Zs(measured) ≤ 0.8 × U0 × Cmin / Ia, and defines 0.8 as “a factor to take into account the increase of resistance of the conductors with the increase of temperature due to load current”. Appendix 3 also notes that this is one method of correcting for temperature difference and that other methods are not precluded. Elec-Mate applies the 0.8 correction automatically when validating Zs measurements.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

07 · Reference Guide

How to Use the Maximum Zs Tables

Using the maximum Zs tables is straightforward once you understand the process. For each circuit in the installation, follow these steps:

  • Step 1 — Identify the device: Determine the type (B, C, D, or fuse) and rating of the protective device for the circuit. Check the front of the MCB or RCBO.
  • Step 2 — Find the table: Use Table 41.2 for fuses at 0.4 s, Table 41.3 for circuit-breakers — every curve, B, C and D, is in that one table — and Table 41.4 for fuses at 5 s. Use the 0.4 s column for final circuits or the 5 s column for distribution circuits.
  • Step 3 — Apply the 0.8 factor: Multiply the tabulated value by 0.8. This gives the maximum Zs your measured value should not exceed when testing at ambient temperature.
  • Step 4 — Compare: Compare your measured Zs against the corrected maximum. If the measured value is below the corrected maximum, the circuit passes. If it exceeds the corrected maximum, investigate further.

You should also verify that the measured Zs is consistent with the calculated value of Ze + (R1+R2). If the measured Zs is significantly higher than the calculated value, there may be a high-resistance connection in the earth path that requires investigation.

In the app

70+ calculators including Zs lookup

Elec-Mate has 70+ electrical calculators built in, including the Zs lookup by protective device.

08 · Reference Guide

What to Do When Zs Exceeds the Maximum

If the measured Zs exceeds the corrected maximum (tabulated x 0.8), the circuit does not comply and action must be taken. The specific action depends on the circumstances and the extent to which the maximum is exceeded.

Verify the measurement

Retest to confirm the reading. Check that your instrument is calibrated. Compare the measured Zs against Ze + (R1+R2) — if there is a large discrepancy, investigate for high-resistance connections. A loose terminal, corroded earthing clamp, or damaged conductor can add significant impedance.

Reduce R1+R2

Increase the cable size (lower resistance per metre), install a larger CPC, or shorten the cable run. This directly reduces R1+R2 and therefore Zs. For example, upgrading from 2.5/1.5 mm² to 4.0/2.5 mm² cable significantly reduces R1+R2.

Change the protective device type

Type B MCBs have higher maximum Zs values than Type C. If the load does not require the higher inrush current tolerance of a Type C device, changing from Type C to Type B may bring Zs within limits. For example, a C32 has a corrected maximum of 0.54 Ω while a B32 has 1.10 Ω — double the headroom.

Add RCD protection

An RCD disconnects on residual current rather than on fault current, so it needs far less of an earth path than an MCB does. There is still a Zs limit — Regulation 411.5.3 and Table 41.5 give 1667 Ω for a 30 mA device and 500 Ω for a 100 mA device — but those are orders of magnitude above anything an MCB will tolerate. This is the standard approach for TT systems where Zs is inherently high.

On an EICR, a Zs value exceeding the maximum permitted value is recorded as an observation. The classification depends on the severity: C2 (potentially dangerous) if no RCD protection is present, or C3 (improvement recommended) if RCD protection is providing adequate disconnection despite the high Zs.

09 · Reference Guide

5-Second Disconnection Values

BS 7671 provides maximum Zs values for 5-second disconnection. Under Regulation 411.3.2.3 that applies in a TN system to distribution circuits and to any circuit not covered by Regulation 411.3.2.2 — so it also picks up large final circuits above 63 A with socket-outlets or above 32 A supplying only fixed equipment. But there is a catch that trips up a lot of people, and it is worth being precise about.

Which devices actually have different 5-second values?

Type B and Type C MCBs — no difference. Table 41.3(a) and 41.3(b) each print a single row of Zs values that is valid for both 0.4 s and 5 s. This is not an omission. An MCB clears an earth fault on its magnetic trip, which is effectively instantaneous — so the fault current needed does not change with the permitted disconnection time. A B32 is 1.37 Ω whether the circuit is a final circuit or a distribution circuit.

Type D MCBs — the exception. Table 41.3(c) is the only circuit-breaker table that prints two rows: a 0.4 s row computed at 20 × In, and a 5 s row at 10 × In. The 5 s values are exactly double the 0.4 s ones.

Fuses — genuinely different. Fuses clear on a thermal characteristic, so time really does matter. Table 41.2 gives the 0.4 s values and Table 41.4 gives the 5 s values — a separate table, not a separate column.

The practical upshot: if you are looking for a more lenient 5-second figure for a Type B or Type C MCB, there isn't one, and any table offering you a higher number is wrong. In a typical domestic installation it is mainly the circuit feeding a sub-distribution board that uses 5-second values, along with any final circuit large enough to fall outside Regulation 411.3.2.2. Everything supplying socket outlets and lighting uses 0.4 seconds. If in doubt, use the 0.4-second values — they are never wrong, only conservative.

10 · Reference Guide

Zs Lookup and Validation with Elec-Mate

Elec-Mate removes the need to carry BS 7671 tables on site. The app provides an instant Zs lookup calculator — select the protective device type (B, C, D MCB, BS 3036 fuse, BS 88 fuse) and rating, and the app shows both the tabulated maximum Zs and the corrected value (tabulated x 0.8) immediately.

In the app

Schedule of tests with auto-Zs-validation

Enter your measured Zs values into the schedule of test results and Elec-Mate validates every reading against the BS 7671 maximum for the specific…

The auto-validation works across all test values — not just Zs. Insulation resistance is checked against the 1 MΩ minimum of Table 64, RCD trip times are checked against the single AC test at IΔn — 300 ms maximum for a general non-delay RCD, 130 to 500 ms for a Type S — and R1+R2 values are cross-referenced with Zs. Voice-to-test-results lets you speak values while testing — no clipboards, no double-handling of data.

In the app

Voice to test results — speak Zs values hands-free

On site with your MFT in hand? Just speak: 'Ring 1, Zs 0.89 ohms.' Elec-Mate fills in the schedule and validates automatically.

How to Look Up and Apply Maximum Zs Values

Step-by-step guide to looking up maximum Zs values from BS 7671 tables, applying the 0.8 temperature correction factor, and comparing measured Zs values.

1

Identify the protective device type and rating

Check the type (B, C, or D for MCBs; or the fuse type for BS 3036 or BS 88) and the current rating (6 A, 10 A, 16 A, 20 A, 32 A, 40 A, 50 A, etc.) of the protective device for the circuit under test. This information is printed on the front of the device.

2

Look up the maximum Zs from the correct table

Find the maximum permitted Zs from the appropriate BS 7671 table: Table 41.2 for fuses at 0.4 s, Table 41.3 for circuit-breakers (Types B, C and D are all in that one table), Table 41.4 for fuses at 5 s. Use the 0.4-second values for final circuits or the 5-second values for distribution circuits.

3

Apply the 0.8 temperature correction factor

Multiply the tabulated maximum Zs by 0.8 to obtain the corrected maximum for ambient temperature testing. For example, B32 tabulated maximum = 1.37 ohms; corrected maximum = 1.37 x 0.8 = 1.10 ohms. Your measured Zs at ambient temperature should not exceed this corrected value.

4

Measure Zs at the furthest point of the circuit

Using the loop impedance function on your multifunction tester, measure Zs at the furthest point of the circuit (the point with the longest cable run). This gives the highest Zs value on the circuit. If this passes, all other points on the circuit will also pass.

5

Compare the measured value against the corrected maximum

Compare your measured Zs against the corrected maximum (tabulated x 0.8). If the measured value is below the corrected maximum, the circuit passes. If it exceeds the corrected maximum, investigate and consider remedial options. Elec-Mate performs this lookup and comparison automatically for every circuit.

6

Record the result on the schedule of test results

Enter the measured Zs value on the schedule of test results. Note the protective device type and rating. If Zs exceeds the maximum, record the appropriate observation code on the EICR (C2 or C3 depending on the circumstances and presence of RCD protection).

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Look up maximum Zs values instantly on site

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. Instant Zs lookup, auto-validation, voice test entry, 70+ calculators. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy