SAFETY HUB

Safe Isolation Procedure: Prove, Test, Prove — Step by Step

The complete guide to safe electrical isolation: the prove-test-prove method, lock-off and LOTO, GS 38 voltage indicator requirements, which systems need the neutral isolated, legal duties under the Electricity at Work Regulations 1989, and the mistakes that kill electricians.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,600+ UK electricians

17 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is the safe isolation procedure?

Safe isolation is the prove–test–prove method for confirming a circuit is dead before work: (1) identify the correct circuit; (2) prove your voltage indicator works on a proving unit or known live source; (3) switch off, then lock off with your personal padlock and apply a caution notice so the circuit cannot be re-energised; (4) test the circuit dead at the point of work between every conductor pair — L-N, L-E and N-E on single phase, all ten pairs on three phase; (5) prove the indicator again on the known source to confirm it did not fail mid-test. The voltage indicator must comply with HSE Guidance Note GS 38, and working dead rather than live is a legal duty under the Electricity at Work Regulations 1989.

1,600+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Safe isolation is a legal requirement under the Electricity at Work Regulations 1989: Reg 12 requires a means of cutting off and isolating supply, Reg 13 requires precautions (lock-off, prove dead) before working on equipment made dead, and Reg 14 makes dead working the default over live work.
  2. 02The prove-test-prove method is the standard: prove your voltage indicator works, test the circuit is dead, prove the indicator still works.
  3. 03HSE Guidance Note GS 38 specifies the requirements for test equipment — HBC fused leads, finger guards, maximum 4 mm exposed probe tips, and a proving unit.
  4. 04Lock-off with a personal padlock is not optional — it prevents inadvertent re-energisation and is the physical guarantee of your safety.
  5. 05BS 7671 Reg 462.2 requires isolation means for all live conductors "except as detailed in Regulation 461.2" — and 461.2 permits the neutral to be left unswitched in TN-S and TN-C-S. Table 537.4 note (d) is explicit that it is TT and IT systems where isolation requires disconnection of every live conductor.
  6. 06Reg 537.2.2 prohibits semiconductor devices (smart dimmers, relay modules, EVSE controller relays) from serving as the means of isolation. Reg 537.3.1.3 explains why: a semiconductor device can interrupt the current without opening the poles.
  7. 07On solar PV installations, Reg 712.514.102 requires a permanent warning notice at every DC access point and Reg 712.514.103 a notice on every inverter reading "WARNING Isolate both AC and DC sides before servicing".
  8. 08Elec-Mate includes guided safe isolation checklists, AI Health and Safety agents that generate RAMS with safe isolation procedures, and testing tools that validate results against BS 7671.

01 · Safety Hub

What Is Safe Isolation?

Safe isolation is the process of disconnecting an electrical circuit from its supply and confirming that it is dead before any work begins. It is the single most important safety procedure for any electrician, and it is the procedure that prevents electrical fatalities. Every year in the UK, electricians and other workers are killed or seriously injured by contact with electricity that they believed was dead but was not.

The procedure involves three core elements: isolation (physically disconnecting the circuit from all sources of supply), proving dead (using a tested voltage indicator to confirm that no voltage is present on any conductor), and securing (locking off the means of isolation to prevent anyone from re-energising the circuit while work is in progress). These three elements together form the safe isolation procedure.

Safe isolation is required before any work on or near electrical conductors — not just major rewiring jobs but any task that involves touching or working near conductors, including changing a socket outlet, replacing a light fitting, adding a circuit, or carrying out dead testing as part of an EICR. The only exception is live working, which is permitted under the Electricity at Work Regulations 1989 only when it is unreasonable for the work to be done dead and suitable precautions are taken — a rare situation that most domestic and commercial electricians should never encounter.

Prove–Test–Prove at a Glance

1
Prove

Confirm your voltage indicator reads live on a proving unit or known source.

2
Isolate

Switch off, then lock off the means of isolation with your personal padlock.

3
Test

Test the dead circuit at the point of work — every conductor combination.

4
Prove

Re-test the indicator on the known source to confirm it did not fail mid-test.

5
Work

Keep the lock and caution notice on throughout — remove only when clear.

Every pair must read 0 V — three pairs on single phase (L–N, L–E, N–E), ten on three phase. Full detail in the GS 38 proving-dead guide and the 10-step procedure below.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

03 · Safety Hub

GS 38 Test Equipment Requirements

HSE Guidance Note GS 38 ("Electrical test equipment for use by electricians") is the key reference document for the test equipment used during safe isolation. Although it is guidance rather than regulation, compliance with GS 38 is the accepted industry standard and is expected by all competent person scheme providers, training bodies, and the HSE itself.

GS 38 covers the equipment, not the procedure. The duty to isolate and work dead comes from the Electricity at Work Regulations 1989 (HSE guidance HSR25); GS 38 tells you what the instrument in your hand has to be. Its requirements exist because poorly designed or damaged test equipment has been a contributing factor in serious and fatal accidents.

GS 38 at a Glance

ItemWhat GS 38 asks forWhy
Probe tipsNo more than 4 mm of exposed metal; 2 mm or less, or spring-loaded screened probes, strongly recommendedStops the probe bridging between live conductors or slipping onto adjacent live parts
Finger barriersSubstantial barriers on the probe body, not a decorative mouldingStops the user's fingers sliding forward onto live parts
Fused leadsHBC fuse of low current rating (usually not exceeding 500 mA), as close to the probe as practicableLimits the energy let through if the probes short a circuit. Carry spares — a blown fuse reads as dead
Lead insulationFully insulated over the whole length, no exposed metal except the tip, no cracks or cutsA damaged lead is both a shock risk and a source of false readings
Marking and categoryClearly marked voltage rating and measurement category — CAT IV at the origin, CAT III at distribution levelMatches the instrument to the transient energy present at the point of use
Indicator standardTwo-pole voltage indicator to a recognised standard such as BS EN 61243-3Purpose-built for proving dead, with far fewer silent failure modes than a multimeter

Before every use, visually inspect your test equipment for damage. Check that probe tips are intact, leads are not cracked or frayed, fuses are present, and the instrument is within its calibration date. Never use test equipment that shows any sign of damage. The cost of replacing a set of test leads is trivial compared to the cost of a serious electrical accident.

04 · Safety Hub

Voltage Indicators vs Multimeters

GS 38 strongly recommends the use of a dedicated two-pole voltage indicator for safe isolation rather than a general-purpose multimeter. Understanding why is critical for every electrician.

Two-Pole Voltage Indicators

  • No batteries required — powered by the circuit being tested
  • No range selector to set incorrectly
  • Simple live/dead indication — no interpretation needed
  • Low impedance — not affected by ghost voltages or induced EMFs
  • Purpose-built for safety-critical proving

Multimeter Risks

  • Flat battery gives a false dead reading
  • Wrong range setting (amps instead of volts) gives false dead
  • Blown internal fuse gives false dead reading
  • High impedance picks up ghost voltages (false live)
  • Multiple failure modes that a user may not detect

The key advantage of a two-pole voltage indicator is reliability through simplicity. It has fewer things that can go wrong, and when it does fail, the failure is typically obvious (no indication at all rather than a misleading reading). For the purpose of proving a circuit dead — which is a life-safety decision — simplicity and reliability outweigh the versatility of a multimeter.

05 · Safety Hub

Lock-Off and LOTO Procedures

Lock-Off / Tag-Out (LOTO) is the physical control measure that prevents a circuit from being re-energised while work is in progress. It is not a supplement to safe isolation — it is an integral part of it. Isolation without lock-off is incomplete isolation.

BS 7671 backs this directly. Regulation 462.3 requires devices for isolation to be designed and/or installed so as to prevent unintentional or inadvertent closure, and gives three examples of how: located within a lockable space or lockable enclosure, padlocking, or located adjacent to the associated equipment. Regulation 537.2.4 repeats the requirement for the device itself. Padlocking is the one you can apply on any board, on any job.

Personal padlock

Every electrician must have their own personal padlock with a unique key. This padlock is used exclusively for locking off isolation points. It must not be a combination lock (someone could guess the code), a master-keyed lock (management could override it), or a shared lock. The principle is that only you hold the key, so only you can remove the lock and re-energise the circuit. Your padlock should be distinctively coloured or labelled with your name.

Lock-off devices

Lock-off devices are mechanical devices that fit over circuit breakers, isolator handles, or fuse carriers to prevent them from being operated. Different devices are available for different types of switchgear: MCB lock-off devices clamp over the MCB toggle, isolator lock-off devices fit over the handle or keyhole, and fuse carrier lock-off devices prevent the carrier from being reinserted. Universal lock-off kits are available that include devices for the most common switchgear types. Always carry your lock-off kit on site.

Multi-lock hasps

When multiple people are working on the same isolated circuit, a multi-lock hasp allows each person to apply their own padlock to the same isolation point. The isolation cannot be removed until every person has removed their padlock — which means every person must confirm they are clear of the circuit before it can be re-energised. This is essential on multi-person jobs and is a standard requirement on commercial and industrial sites.

Caution notices

A caution notice must be attached to the isolated switchgear, clearly visible to anyone approaching the distribution board. Typical wording is “DANGER — DO NOT SWITCH ON — WORK IN PROGRESS”. The notice should carry the name of the person who applied the lock-off, the date, and a contact number. Notices alone are not sufficient — they must be used in conjunction with physical lock-off. A label without a lock can be ignored; a lock without a label does not communicate the reason for the lock-off.

Stored energy — Reg 462.4 and the discharge-time label

Locking off does not empty a capacitor. Where residual electrical energy is potentially present, Regulation 462.4 requires suitable means to be provided for its discharge and, where relevant, a warning label indicating the discharge time required before the enclosure can be safely opened. Inverters, variable-speed drives, power factor correction gear and UPS units all fall into this bracket. Find the label, wait the stated time, then prove dead — in that order.

06 · Safety Hub

Does the Neutral Have to Be Isolated?

This is the most commonly misquoted point in safe isolation, and it is worth getting right, because the answer depends on the earthing system. Regulation 462.2 says that every circuit shall be provided with isolation means for all live conductors — “except as detailed in Regulation 461.2”. It is that exception that does the work.

Regulation 461.2 permits the neutral to be left unswitched in TN-S and TN-C-S systems where protective equipotential bonding is installed and either the neutral is reliably connected to Earth by a low resistance sufficient to meet the Chapter 41 disconnection times, or the distributor declares that the PEN or neutral conductor of the supply is. In a TN-C or TN-C-S system the PEN conductor shall not be isolated or switched at all. The requirement to break every live conductor bites in TT and IT systems — Table 537.4 note (d) states it in terms, cross-referring back to Regulation 462.2.

Isolation of the Neutral by System

Earthing systemNeutral isolationReference
TN-S, TN-C-SNot required, provided protective equipotential bonding is installed and the neutral is reliably earthed to meet Chapter 41 disconnection times (or the distributor declares that it is)461.2
TT, ITRequired — isolation must disconnect all live conductors, neutral included462.2, Table 537.4 note (d)
PEN conductor (TN-C, TN-C-S)Shall not be isolated or switched461.2
Household main switchA main switch intended for operation by ordinary persons shall interrupt both live conductors of a single-phase supply462.1.201

Any device inserted in an earthed neutral must be linked and arranged to break all the related line conductors (Reg 132.14.2); a single-pole fuse, switch or circuit-breaker goes in the line conductor only (Reg 132.14.1).

None of this changes what you do on site. Whatever the system, you still test between every conductor pair at the point of work and expect 0 V on all of them — including neutral to earth. A neutral that is not switched can still be at a dangerous potential if it is borrowed, cross-connected, or open-circuit upstream, which is exactly why the N–E test is part of the procedure and not an optional extra.

In the app

Generate RAMS in minutes

Site-specific risk assessments and method statements, written to CDM 2015 expectations and ready to send. From £6.99/mo.

07 · Safety Hub

Common Safe Isolation Mistakes

Safe isolation accidents are almost always caused by shortcuts, complacency, or failure to follow the full procedure. These are the mistakes that kill electricians.

Skipping the second prove

The most dangerous shortcut. If you skip the final prove step and your voltage indicator had failed during the test, you have no way of knowing whether the dead reading was genuine or the result of a faulty instrument. HSE accident investigations have identified this as a contributing factor in multiple fatalities.

Relying on circuit labels

Circuit labels can be wrong. Previous electricians may have modified circuits without updating the chart. Labels fade and become illegible. In older installations, there may be no labels at all. Always verify the circuit identity independently by switching the load and observing the result at the point of work.

Not locking off

“I’ll only be a minute” and “No one else is here” are the two most dangerous phrases in electrical work. It takes seconds for someone to walk past and flip a switch back on. Building managers, caretakers, tenants, and other trades all have access to distribution boards. Lock off every time, no exceptions.

Testing only L–N

Testing only between line and neutral is insufficient. A borrowed neutral, a cross-connection to another circuit, or a fault in the earthing system could leave a conductor at a dangerous potential that an L–N test alone would not detect. Test all three pairs: L–N, L–E and N–E. This matters most where the neutral has not been switched — which Reg 461.2 permits in TN-S and TN-C-S.

Proving dead at the board, not at the point of work

A dead reading at the consumer unit tells you about the consumer unit. Borrowed neutrals, shared circuits, back-feed and mis-identified circuits all show up downstream. Test at the point where your hands will be.

Not considering alternative supplies

Solar PV inverters, battery storage systems, UPS units, standby generators and other sources can energise circuits from the load side even when the main supply is isolated. Reg 537.1.2 requires a durable warning notice where an enclosure contains live parts fed from more than one supply — but never assume it is present. Identify and isolate every source before confirming dead.

08 · Safety Hub

Three-Phase Safe Isolation

Three-phase safe isolation follows the same prove-test-prove principle as single-phase but requires additional tests due to the greater number of conductors. On a three-phase system, there are three line conductors (L1, L2, L3), a neutral, and an earth — five conductors that must all be confirmed dead.

Every Pair to Prove — Single Phase vs Three Phase

Three pairs on a single-phase circuit, ten on a three-phase circuit. Every one must read 0 V at the point of work.

GroupPairs to testCountExpected
Single phaseL–N, L–E, N–E30 V
Three phase — line to lineL1–L2, L1–L3, L2–L330 V
Three phase — line to neutralL1–N, L2–N, L3–N30 V
Three phase — to earthL1–E, L2–E, L3–E, N–E40 V
Three-phase total100 V

Any reading other than zero on any pair means the circuit is not isolated — stop, investigate, and do not proceed until every conductor is confirmed dead.

The type of isolator matters as much as the tests. Regulation 462.1.201 requires a main linked switch or linked circuit-breaker as near as practicable to the origin of every installation, as the means of switching the supply on load and as the means of isolation — “linked” being the operative word. Some older installations use separate single-pole devices on each phase; those must all be opened and locked off individually. Regulation 462.4 also applies at this scale: where residual energy may be present, look for the discharge-time label before opening an enclosure. On commercial and industrial sites, permit-to-work systems are often used alongside safe isolation as an additional layer of administrative control.

In the app

Elec-Mate's testing tools validate every result

Enter your test results on site and the app validates them against BS 7671 maximum permitted values automatically.

09 · Safety Hub

Solar PV, Battery Storage, and EV Isolation

Installations with solar PV panels, battery storage, or EV charge points introduce additional isolation hazards that are not present in conventional circuits. The prove-test-prove procedure still applies, but these systems require extra steps before work can be considered safe — see the dedicated solar PV guide for full DC-side isolation detail.

Solar PV panels cannot be switched off

Isolating the AC supply at the inverter disconnects the inverter output, but the DC cabling between the array and the inverter input remains live at panel voltage whenever there is daylight. The DC conductors between the array, combiner boxes and inverter DC terminals stay energised even after the AC isolator is open and locked off. Working on these conductors without understanding and managing the DC risk has caused serious electrical burns and fatalities.

Reg 712.514.102 — permanent DC warning notice

BS 7671:2018+A4:2026 Regulation 712.514.102 requires that each point of access to live parts on the DC side — such as distribution boards and combiner boxes — has a permanent warning notice indicating that live parts may still be energised after isolation. The regulation gives example wording: “SOLAR DC — Live parts can remain energised after isolation”. Because the requirement is for a permanent notice, a paper or handwritten label does not meet it. Record a missing or non-permanent notice as an observation on the EICR and apply your own judgement to the classification code — BS 7671 does not assign codes.

Reg 712.514.103 — the notice on the inverter itself

A separate warning notice is required on all inverters, with words similar to “WARNING Isolate both AC and DC sides before servicing”. That is the procedure in one line: two isolations, two lock-offs, then prove dead. Reg 537.1.2 applies here too — where an enclosure contains live parts fed from more than one supply, a durable warning notice must be positioned so that anyone gaining access is warned to isolate from every supply, unless interlocking does it for them.

Battery storage and EV charge points

Battery storage systems can supply energy to circuits from the load side even when the DNO supply is isolated. Isolate the battery system at its dedicated isolator before working on any circuit the battery could energise, and prove dead at the point of work after isolating both the DNO supply and the battery output. EV charge points with on-board energy management may have control circuitry that remains energised after the supply MCB is switched off — identify the dedicated EVSE isolator and lock that off in addition to the circuit breaker. On both, check for a Reg 462.4 discharge-time label before opening any enclosure.

10 · Safety Hub

Semiconductor Devices Cannot Be Used as Isolators

As smart-home retrofits, energy management systems, and automated lighting become more common, electricians are increasingly encountering circuits where the only apparent switching device is a semiconductor-based module rather than a mechanical switch. These devices cannot legally serve as the means of isolation.

Reg 537.2.2 — semiconductor devices shall not be used as isolating devices

The wording of Regulation 537.2.2 is one line long and admits no exception: “Semiconductor devices shall not be used as isolating devices.” Regulation 537.3.1.3 explains why. Its note records that functional switching devices may control the current without necessarily opening the corresponding poles, and names semiconductor switching devices as an example of exactly that — a device capable of interrupting the current in the circuit but not opening the poles. Off, in other words, is not the same as disconnected.

Regulation 537.2.1 sets the positive test: a device for isolation shall be of a type for which the isolation function is explicitly recognised by the relevant product standard, or is identified as suitable for isolation in Table 537.4. Reg 537.2.3 adds that devices for isolation shall be designed for overvoltage category III or IV, except the plug of a plug and socket-outlet combination identified in Table 537.4 as suitable for isolation.

Practical examples of Reg 537.2.2 breaches that are becoming common EICR observations:

  • Smart dimmer modules: Trailing-edge and leading-edge dimmers fitted behind standard faceplates — the mechanical rocker operates the dimmer's control input, not a mechanical isolation contact. Switching the dimmer off does not isolate the circuit.
  • Relay-switch modules: Wireless relay modules installed in back-boxes or ceiling roses to control lighting. The relay coil may de-energise on command, but the semiconductor switching element remains connected across the load terminals.
  • EVSE controller relays: Some EV charge point designs use solid state switching inside the charge point enclosure. The dedicated EVSE isolator upstream of the charge point is the correct means of isolation — not the charge point's own internal switching.

When carrying out an EICR or working on any circuit where the only switching device is semiconductor-based, identify and use a compliant isolating device upstream — one recognised for isolation by its product standard or listed as suitable in Table 537.4. Where no such isolation point exists, the installation does not satisfy Reg 462.2 read with Reg 537.2.2, and that belongs on the schedule of observations.

Safe Isolation Procedure: 10-Step Guide

The complete 10-step safe isolation procedure following HSE Guidance Note GS 38, covering client notification, prove-test-prove, lock-off and LOTO, alternative supplies, and reinstatement.

1

Obtain permission and notify the client or occupant

Before touching the distribution board, inform the client or building occupant of the circuit you are about to isolate, the duration of the outage, and any services that will be affected (for example, alarms, refrigeration, or other trades on site). Obtain permission to turn off the power. This step is required practice — it prevents disputes, protects people who may be relying on the supply (medical equipment, heating systems), and is explicitly identified in practical work intelligence as a preparation requirement before isolation is carried out.

2

Identify the circuit to be worked on

Identify the correct circuit at the distribution board or consumer unit. Check the circuit chart and labelling, but never rely solely on labels — they may be incorrect or out of date. Verify the circuit identity by switching the load on and off at the consumer unit and observing the result at the point of work. For example, switch off the MCB and confirm that the light or socket at the work location goes off. This prevents you from isolating the wrong circuit — a surprisingly common error.

3

Select a GS 38 compliant voltage indicator

Choose a two-pole voltage indicator that complies with HSE Guidance Note GS 38. The instrument must be rated to at least CAT III (for distribution-level testing) or CAT IV (for origin-level testing). Check that test leads are protected by an HBC fuse of low current rating (usually not exceeding 500 mA), that probes have finger barriers to prevent contact with live parts, and that no more than 4 mm of metal is exposed at the tip — GS 38 strongly recommends reducing this to 2 mm or less, or using spring-loaded screened probes. Verify the instrument is within its calibration date. Have a proving unit (battery-powered device that outputs a known voltage) available for the prove steps.

4

Prove the voltage indicator works (first prove)

Test your voltage indicator on a known live source — either a dedicated proving unit or another circuit you know is energised. The indicator must give a clear, positive indication that voltage is present. If the indicator does not respond to the known live source, it is faulty. Do not use it. Replace the instrument, battery, or fuses and re-test. This step confirms that the instrument you are about to rely on for your safety is actually working.

5

Isolate and lock off

Switch off the circuit breaker or remove the fuse carrier for the identified circuit. Apply a lock-off device and your personal padlock to the circuit breaker or fuse carrier to prevent re-energisation — BS 7671 Reg 462.3 requires devices for isolation to be installed so as to prevent unintentional or inadvertent closure, and gives padlocking as one of its examples. Attach a clearly visible caution notice on the distribution board, typically worded "DANGER — DO NOT SWITCH ON — WORK IN PROGRESS", with your name, the date and a contact number. If multiple people are working on the same circuit, each person must apply their own padlock using a multi-lock hasp. Keep the key in your personal possession at all times.

6

Prove the circuit is dead at the point of work

At the point where you will be working (not at the consumer unit), use your proved voltage indicator to test between all conductor combinations. For single-phase: Line to Neutral (L-N), Line to Earth (L-E), and Neutral to Earth (N-E). All three tests must show zero volts. If any test shows voltage, the circuit is not properly isolated — stop immediately, investigate, and do not proceed until all conductors are confirmed dead. For three-phase circuits, test between all phase combinations (L1-L2, L1-L3, L2-L3) plus each phase to neutral and each phase to earth.

7

Prove the voltage indicator still works (second prove)

Immediately after confirming the circuit is dead, return to the known live source and test your voltage indicator again. It must give the same clear, positive indication of voltage as it did in Step 4. This final step confirms that your instrument did not fail between the first prove and the test — if it had failed silently, the dead reading you got in Step 6 would be meaningless. If the indicator fails the second prove, treat the circuit as live and repeat the entire procedure with a different instrument.

8

Consider alternative supplies and assess remaining risks

Before beginning work, consider whether any alternative supply sources could re-energise the circuit: solar PV inverters, battery storage, UPS systems, standby generators, or back-feed from interconnected circuits. Isolate any such sources independently. Where equipment or an enclosure contains live parts fed from more than one supply, BS 7671 Reg 537.1.2 requires a durable warning notice positioned so that anyone gaining access is warned to isolate from every supply (unless interlocking does it for them) — but never assume the notice is there. On installations with solar PV, DC conductors between the panels and the inverter remain live even after AC isolation; Reg 712.514.102 requires a permanent warning notice at every DC access point. Check too for a discharge-time label under Reg 462.4 where stored energy may be present. Satisfy yourself that all energisation risks have been addressed before touching any conductors.

9

Carry out the work and maintain isolation throughout

Carry out the intended work with your lock-off and tag in place throughout. Do not remove the lock until all work is complete, tools are clear, and all personnel are away from the circuit. On multi-person jobs, no one removes their padlock until they personally confirm they are clear. Never hand your padlock key to another person or allow the lock to be removed on your behalf.

10

Reinstate supply and record the isolation

Once work is complete, restore all covers and enclosures. Remove warning labels and lock-off devices. Restore supply in a controlled manner, confirming with the client or occupant before energising. Record the isolation in your method statement or site log: circuit reference, time isolated, time reinstated, and the name of the person who performed the isolation. A written record protects you and provides evidence that the correct procedure was followed.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Safe isolation tools built for site

Join 1,600+ UK electricians using Elec-Mate for safe isolation checklists, AI RAMS generation, testing tools, and 19 certificate types. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,600+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy