SAFETY PROCEDURE GUIDE

Safe Isolation Procedure: GS38, EAW Regulations, and Proving Dead

Safe isolation is a legal requirement under the Electricity at Work Regulations 1989. This guide covers the prove-isolate-secure-prove sequence, HSE GS38 requirements for test instruments, locking off, multi-lock hasps, and the correct method for proving dead.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is the safe isolation procedure for electricians?

Safe isolation follows a prove-isolate-secure-prove sequence: identify the circuit, prove your GS38 voltage indicator works on a known live source, switch off and isolate, secure the isolation point with a lock or by removing the fuse, prove dead at the point of work testing all conductor combinations, then re-prove the indicator still works. It is a legal duty under Regulations 12 and 13 of the Electricity at Work Regulations 1989.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01The legal requirement comes from the Electricity at Work Regulations 1989 — Regulation 12 (means for cutting off the supply and for isolation) and Regulation 13 (precautions for work on equipment made dead). Neither is qualified by "so far as is reasonably practicable".
  2. 02Regulation 12(2) defines isolation as disconnection and separation from every source of electrical energy in such a way that the disconnection and separation is secure. Securing the isolation point is part of the legal definition, not an optional extra.
  3. 03GS38 is HSE guidance, not statute. It carries no legal force of its own, but it is the HSE’s account of what "suitable" test equipment means under Regulation 4(4) of the EAW Regulations — so departing from it means proving suitability another way.
  4. 04The sequence is prove — isolate — secure — prove dead — prove again: demonstrate the voltage indicator works on a known live source, isolate, lock off, prove dead at the point of work, then re-prove the indicator.
  5. 05The HSE prefers a dedicated two-pole voltage indicator over a multimeter for proving dead. A multimeter’s high input impedance can display a phantom voltage from capacitive coupling on a circuit that really is dead.
  6. 06BS 7671 does not set the safe isolation procedure — it provides the means. Section 462 requires an isolator for every circuit, Regulation 462.3 recognises padlocking and lockable enclosures, and Regulation 514.11.1 requires a warning notice wherever live parts cannot be isolated by a single device.
  7. 07For inspection and testing, IET Guidance Note 3 (Regulation 1.1) is explicit: where testing does not require the installation to be live, it shall be made dead and safely isolated before the test. BS 7671 Regulation 642.1 adds that inspection shall normally be done with that part disconnected from the supply.

01 · Safety Procedure Guide

Legal Basis for Safe Isolation

The sequence, in one line

Identify → prove the indicator → isolate → secure → prove dead at the point of work → prove the indicator again.

Six steps, in that order, every time. The legal duty is Regulations 12 and 13 of the Electricity at Work Regulations 1989. BS 7671 makes sure a suitable means of isolation is there to use, and HSE Guidance Note GS38 covers the instrument you prove dead with.

Safe isolation is not a recommendation. The Electricity at Work Regulations 1989 (the EAW Regulations) place duties on employers, the self-employed and employees to ensure electrical work is carried out safely, and safe isolation is the foundation of working dead. Two regulations do most of the work:

Regulation 12 — cutting off the supply and isolation

Where necessary to prevent danger, suitable means — including, where appropriate, methods of identifying circuits — shall be available for cutting off the supply of electrical energy to any equipment and for the isolation of any equipment. Regulation 12(2) then defines isolation as disconnection and separation from every source of electrical energy in such a way that the disconnection and separation is secure. Locking off is not an add-on to isolation; it is part of what the word means.

Regulation 13 — precautions for work on equipment made dead

Adequate precautions shall be taken to prevent equipment that has been made dead, in order to prevent danger while work is carried out on or near it, from becoming electrically charged during that work where danger may thereby arise. In practice that means locking off, warning notices and proving dead at the point of work.

These are absolute duties, and what that means

Neither regulation is qualified by ‘so far as is reasonably practicable’. Regulation 29 of the EAW Regulations does provide a defence of having taken all reasonable steps and exercised all due diligence — but that is a defence argued at trial, not a relaxation of the duty on site. A breach is prosecuted under the Health and Safety at Work etc. Act 1974: on indictment, an unlimited fine and up to two years’ imprisonment for an individual. Beyond that, an electrical accident — particularly a fatality — has consequences that no penalty describes.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Safety Procedure Guide

HSE Guidance Note GS38

Is GS38 statutory?

No — GS38 is HSE guidance, not law. The duty it interprets is.

GS38 has no legal force of its own and is not an Approved Code of Practice. What is statutory is Regulation 4(4) of the EAW Regulations: equipment provided to protect people working on or near electrical equipment shall be suitable for the use for which it is provided, be maintained in a condition suitable for that use, and be properly used. GS38 is the HSE’s published account of what ‘suitable’ means for test leads, probes and voltage indicators — so working outside it is not automatically an offence, but it leaves you proving suitability some other way, usually after an incident.

GS38, ‘Electrical test equipment for use by electricians’, sets out what the HSE regards as suitable test equipment for use during safe isolation and electrical testing. IET Guidance Note 3 reinforces it directly, stating that the testing safety procedures detailed in GS38 shall be observed when using electrical test equipment.

What GS38 asks of your test kit

  • Measurement category rating — instruments, leads and probes must be rated for the category and voltage of the circuit under test. For fixed domestic and commercial installations that means CAT III or CAT IV. The rating describes the transient overvoltage the equipment can withstand without breaking down.
  • Fused leads where the manufacturer advises them — fuses limit the energy released if a probe bridges to a live part. Guidance Note 3 notes that some manufacturers permit non-fused leads where the instrument itself has built-in protection; follow the instrument instructions, and remember that internal protection does not extend to the leads.
  • Shrouded connectors — where the leads plug into the instrument, the connectors must be shrouded so they cannot be touched or bridge adjacent terminals.
  • Insulated probes with a short exposed tip — probe shafts insulated, with only a short length of metal exposed at the tip, plus finger barriers. Long bare shafts bridge adjacent terminals in a crowded board.
  • A way of proving the indicator — a voltage indicator used for proving dead should have an integral prove facility, or be used with a separate proving unit.

Matching the CAT rating to where you are working

The measurement category tells you how close to the supply origin an instrument and its leads can safely be used. The closer to the origin, the larger the transient overvoltage the equipment has to survive.

Measurement category ratings and where each applies
CAT ratingWhere it appliesTypical use
CAT IIAppliances and equipment downstream of a socket-outletPlug-in loads
CAT IIIFixed installation wiring — distribution boards, final circuits, socket-outletsMost fixed-wiring work
CAT IVThe origin of the installation — supply intake, meter tails and main switchOrigin / intake work

For most fixed installation work a CAT III 1000 V or CAT IV 600 V instrument with matching leads is appropriate. The whole set-up carries the rating — instrument, leads and probes — and the lowest-rated component sets the safe limit. BS 7671 applies the same logic to the installation itself: Regulation 537.2.3 requires devices for isolation to be designed for overvoltage category III or IV.

03 · Safety Procedure Guide

Safe Isolation Procedure: 6 Steps

The sequence must not be shortened or reordered. It rests on one principle: the voltage indicator has to be shown to be working, both before and after it is used to declare a circuit dead.

  1. 1
    Identify the circuit

    Identify the circuit to be isolated and confirm which protective device controls it. In a well-labelled board this is straightforward; in an unlabelled one, use a plug-in circuit tracer or careful load switching. Never take a label at face value — verify it. Regulation 12 of the EAW Regulations specifically includes methods of identifying circuits within the "suitable means" it requires.

  2. 2
    Select and prove the voltage indicator

    Select a GS38-compliant two-pole voltage indicator. Prove it works on a known live source — a proving unit, or the circuit itself before you switch off. It must give a positive indication on a known live source before you can rely on it to confirm anything is dead.

  3. 3
    Isolate the circuit

    Switch off the breaker, withdraw the fuse, or open the isolator. A single-pole MCB breaks only the line conductor, leaving the neutral connected. BS 7671 Regulation 461.2 allows this in TN-S and TN-C-S systems where protective equipotential bonding is installed and the neutral is reliably connected to Earth; on a TT or IT system, isolation requires all live conductors to be disconnected.

  4. 4
    Secure the isolation point

    Lock off the device, fit an MCB lock-off clip, or withdraw the fuse and keep it on you, and add a warning notice. Regulation 12(2) of the EAW Regulations makes the security of the disconnection part of the definition of isolation. Where several operatives are working, use a multi-lock hasp so each holds their own lock.

  5. 5
    Prove dead at the point of work

    Test at the actual point of work, not just at the board. Test every conductor combination — line to neutral, line to earth, neutral to earth. Any indication on any combination means the circuit is not dead: stop and investigate before going any further.

  6. 6
    Prove the indicator is still working

    Re-test the voltage indicator on the proving unit or a known live source. If it no longer responds, the dead reading in step 5 proves nothing — stop, replace the instrument and start the proving sequence again.

Work can now proceed. The locking device and warning notice stay in place until the work is finished and the circuit is ready to be re-energised — and it is re-energised by the person who isolated it, after checking nobody is still working on it.

04 · Safety Procedure Guide

Key References for Safe Isolation

Safe isolation sits across statutory law, HSE guidance and the BS 7671 ecosystem. No single document holds all of it — BS 7671 itself does not set out a safe isolation procedure at all. These are the documents that do.

  • Electricity at Work Regulations 1989 — Regulations 12, 13 and 4(4)

    The statutory foundation. Regulation 12 requires suitable means for cutting off the supply and for isolation, and defines isolation as a secure disconnection and separation. Regulation 13 requires precautions to stop dead equipment becoming live during work. Regulation 4(4) requires the protective equipment you use — including test instruments — to be suitable, maintained and properly used.

  • HSE Guidance Note GS38 — Electrical test equipment for use by electricians

    The HSE’s practical account of suitable test equipment: measurement category, fusing, insulated probes, shrouded connectors and the means of proving the indicator. Guidance, not law, but the reference point against which your kit will be judged.

  • HSE HSG85 — Electricity at work: Safe working practices

    The HSE’s detailed guidance on safe electrical working, including the key principles of the working dead procedure. It also places responsibility on managers to establish a system of rules and procedures wherever electrical work is carried out — a duty that stays with the premises management even when contractors are engaged. Free to download from the HSE.

  • IET On-Site Guide — Appendix M, ‘Safe working practices’

    Appendix M is where the On-Site Guide puts its safe isolation guidance, reproducing the key principles of the working dead procedure from HSG85 and stressing that modern installations may have more than one source of supply. The Guide’s requirements for the isolation devices themselves sit separately at Section 5.1.

  • IET Guidance Note 3 — Regulation 1.1

    For inspection and testing: where testing does not require the equipment or part of an installation to be live, the installation or part shall be made dead and safely isolated before the test is performed. Guidance Note 3 also requires the absence of voltage to be verified after isolation, and the GS38 procedures to be observed.

  • Electrical Safety First — Best Practice Guide 2

    Guidance on the management of electrical safety and safe isolation procedures for low voltage installations. Referenced by both the On-Site Guide and Guidance Note 3 as recognised best practice, and free to download.

05 · Safety Procedure Guide

Test Instruments in Practice

Choosing the right instruments is not just about compliance. Substandard test leads are one of the most common causes of electrical accidents in the trade — and Guidance Note 3 requires the condition of probes and leads to be checked before any live test.

  • Check the CAT rating on the leads, not just the instrument — a CAT IV meter on unrated leads is a CAT-nothing set-up. The lowest-rated component in the chain sets the limit. Replace any lead that does not display a rating.
  • Inspect leads before every use — cracked insulation, exposed conductor near the probe or connector, a blown fuse in the probe body, a bent or loose tip. Damaged leads are replaced, not taped up.
  • Carry a proving unit — it removes any dependence on finding a convenient adjacent live source, and it is the only way to complete the final prove once everything nearby has been isolated.
  • Ask whether the live test is needed at all — Guidance Note 3 asks the inspector to consider, in each case, whether a particular live test is necessary before undertaking it. The safest live test is the one you did not need to do.

06 · Safety Procedure Guide

Proving Dead: The HSE Guidance

Proving dead — confirming a circuit is not live at the point of work — is the step that everything else exists to support. An approved two-pole voltage indicator is the correct instrument for it. A multimeter can be a secondary check, but not the primary one.

Two-pole voltage indicator compared with a multimeter for proving dead
FactorTwo-pole voltage indicatorMultimeter
Proving deadDesigned for it — the HSE’s preferred instrumentSecondary check only, never on its own
Input impedanceLower — rejects capacitive couplingHigh, typically around 10 MΩ — can show a phantom voltage
Range selectionNone — a clear go / no-go indicationMay auto-range, with a settling delay
Prove before and afterIntegral prove facility or a separate proving unitRelies on a separate known live source

The two failure modes to understand are the reason for the preference. A multimeter on the voltage range has an input impedance of around 10 megohms, high enough that capacitive coupling from adjacent cables can produce a readable voltage on a conductor that is genuinely dead — which trains people to distrust a real warning. And an auto-ranging meter takes a moment to settle, so a reading taken immediately after the probes land can be wrong. A two-pole indicator has a lower impedance, no range to select and a clear go / no-go indication.

Test every conductor combination

At the point of work, one test is not enough. For a single-phase circuit with line, neutral and earth, test all three combinations:

Line to neutral
Line to earth
Neutral to earth

Any indication on any combination means the circuit is not dead — stop and investigate. Borrowed neutrals, shared CPCs and second supplies all leave conductors live with the controlling device off. BS 7671 Regulation 537.1.2 requires a durable warning notice wherever an item of equipment or enclosure contains live parts connected to more than one supply; on an unfamiliar installation, do not assume that notice was ever fitted.

In the app

Generate RAMS in minutes

Site-specific risk assessments and method statements, written to CDM 2015 expectations and ready to send. From £6.99/mo.

07 · Safety Procedure Guide

Locking Off and Warning Notices

Once the circuit is isolated, the isolation point has to be secured. Switching the MCB off is not enough — someone else can switch it back on without knowing anyone is working. Regulation 12(2) of the EAW Regulations builds security into the definition of isolation, and BS 7671 Regulation 462.3 requires devices for isolation to be designed or installed so as to prevent unintentional or inadvertent closure.

Securing methods and what each suits
MethodBest suited to
Withdraw the fuse or carrier and keep itRewireable and cartridge fuse boards; single-operative domestic work
MCB lock-off clip with padlockStandard MCB consumer units where there is no fuse to remove
Padlock on the isolator or switch-disconnectorBoards and equipment with built-in provision for a padlock
Multi-lock haspMore than one operative on the same circuit or item of plant
Lockable enclosure or cupboardPlant rooms and intake rooms — recognised by Regulation 462.3

The warning notice is not optional decoration

A notice — ‘Do not switch on, work in progress’, with your name on it — goes on the board alongside whatever physical device you have fitted, every time. It tells the next person what is happening and who owns the isolation.

BS 7671 requires notices in its own right, too. Regulation 514.11.1 requires a durable warning notice in each position where there are live parts that cannot be isolated by a single device, indicating the location of each disconnector. Regulation 537.1.2 requires a warning notice wherever an installation, item of equipment or enclosure contains live parts connected to more than one supply, positioned so that anyone about to gain access is warned of the need to isolate every supply. Those notices are your first clue that a board is not as simple as it looks.

08 · Safety Procedure Guide

How BS 7671 Supports Safe Isolation

The duty to isolate comes from the EAW Regulations; BS 7671 makes sure the means of isolation you rely on exists, is fit for the job and can be secured. BS 7671 defines isolation as the function intended to make dead, for reasons of safety, all or a discrete section of the installation by separating it from every source of electrical energy — wording that lines up closely with Regulation 12(2). Chapter 46 and Section 537 set out where isolation devices go and how they must behave.

BS 7671 regulations relevant to isolation and lock-off
RegulationRequirement
462.1.201A main linked switch or linked circuit-breaker shall be provided as near as practicable to the origin of every installation as a means of switching the supply on load and as a means of isolation. A main switch intended for operation by ordinary persons, for example in a household installation, shall interrupt both live conductors of a single-phase supply.
462.2Every circuit shall be provided with isolation means for all live conductors, except as detailed in Regulation 461.2. Provision may be made for isolating a group of circuits by a common means if the service conditions allow this.
462.3Devices for isolation shall be designed and/or installed so as to prevent unintentional or inadvertent closure. The examples given are: located within a lockable space or lockable enclosure; padlocking; located adjacent to the associated equipment.
462.4Where residual electrical energy is potentially present, suitable means shall be provided for its discharge, with a warning label giving the discharge time before the enclosure can be safely opened where relevant.
537.2.3Devices for isolation shall be designed for overvoltage category III or IV — the exception being the plug of a plug and socket-outlet combination identified in Table 537.4 as suitable for isolation.
537.2.6Means of isolation shall preferably be a multipole switching device disconnecting all applicable poles, although single-pole devices situated adjacent to each other are not excluded, subject to Regulation 461.2.
537.2.7Each device used for isolation shall be clearly identified by position or durable marking to indicate the installation or circuit it isolates.
514.11.1A durable warning notice shall be fixed in each position where there are live parts which are not capable of being isolated by a single device. The location of each disconnector shall be indicated unless there is no possibility of confusion.

Not every switch is a device for isolation

Section 537 sets the device-level requirements, and Table 537.4 — ‘Guidance on the selection of protective, isolation and switching devices’ — is the lookup that tells you which device does which job, against which product standard. Two points from it are worth carrying around. A device only counts as suitable for isolation where it is marked with the symbol for isolation, IEC 60617 identity number S00288. And on a TT or IT system, isolation requires disconnection of all the live conductors, neutral included — the single-pole allowance in Regulation 461.2 is a TN-S and TN-C-S concession, not a general one.

The requirements do not stop at selection. Regulation 537.2.7 requires every isolating device to be clearly identified, by position or durable marking, to show what it isolates — which is exactly the circuit identification Regulation 12 of the EAW Regulations calls for, and the reason an unlabelled board is a safe isolation problem as well as a paperwork one.

Isolation during inspection and testing

Part 6 assumes dead working as the default. Regulation 642.1 states that inspection shall precede testing and shall normally be done with that part of the installation under inspection disconnected from the supply, and Regulation 641.4 requires precautions to be taken to avoid danger to persons and livestock, and damage to property and installed equipment, during inspection and testing. Guidance Note 3 puts the same duty in procedural terms at Regulation 1.1.

Recording the isolation and the instruments used is part of completing an EIC or EICR. For the wider inspection workflow, see the inspection and testing course.

09 · Safety Procedure Guide

Complex Isolations and Multi-Lock Hasps

On larger commercial and industrial installations, where several operatives work on the same plant, isolation needs a structure around it: multi-lock hasps and a permit to work. The On-Site Guide makes the same point for modern domestic and small commercial work — an installation with solar PV, battery storage or a generator may have more than one source of supply, and isolating the incoming supply does not necessarily make the installation dead.

  • Multi-lock hasp

    A steel bar with multiple padlock holes, fitted to the isolation point. Every operative working on the circuit fits their own padlock and keeps their own key. The isolation cannot be released until the last lock comes off, so no one person can re-energise the circuit while anybody else is still working.

  • Permit to work

    A formal document identifying the equipment, the isolation points that have been locked off, the people authorised to do the work and the precautions in place, signed by the issuer and by the person receiving it. Required for high voltage work and standard practice for complex low voltage work on large installations.

  • Multiple supplies

    Where an installation, item of equipment or enclosure contains live parts connected to more than one supply, BS 7671 Regulation 537.1.2 requires a durable warning notice so that anyone gaining access is warned of the need to isolate every supply, unless an interlocking arrangement isolates all the circuits together. Prove dead after isolating each source, not after the first.

In the app

Issue method statements and risk assessments on site

Elec-Mate's AI health and safety tools can generate method statements and risk assessments for complex electrical work…

10 · Safety Procedure Guide

For Electricians: Safe Isolation on Every Job

Safe isolation happens on every job, every time. There is no exemption for a quick job, and a circuit is not dead because a switch is off — the switch may be the wrong one, the circuit may be fed from two places, or there may be a borrowed neutral. Prove it dead before you touch it.

Essential kit for safe isolation

  • GS38-compliant two-pole voltage indicator
  • Proving unit, so the indicator can be proved anywhere
  • GS38-compliant test leads rated CAT III or CAT IV
  • MCB lock-off devices — carry several, in more than one pattern
  • Padlocks with your own keys
  • Warning notices (‘Do not switch on’) and a marker pen
  • Multi-lock hasp for multi-operative jobs

Record the instruments in your certificate

The EIC and EICR both include sections for the test instruments used. Complete them — they are the record that suitable, GS38-compliant equipment was used on that job, on that date, and Regulation 4(4) of the EAW Regulations puts the burden of showing suitability on you.

Frequently Asked Questions About Safe Isolation

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Record Test Instruments and Certify Work On Site

Elec-Mate's EIC and EICR certificate apps include full test instrument recording. Complete compliant certificates on your phone, issue PDFs on site, and keep GS38 instrument records in every certificate. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy