INSTALLATION GUIDE

Second Fix Electrical: Completion, Testing, and Certification

Second fix is where the installation comes together. Fitting accessories, wiring the consumer unit, labelling circuits, completing initial verification, and issuing the EIC. This guide covers the entire second fix process from start to handover.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Second fix electrical covers fitting accessories, wiring the consumer unit, labelling, initial verification testing, and issuing the EIC — it is where the installation becomes a finished, certified product.
  • 2Initial verification under BS 7671 Chapter 64 must be completed before the supply is energised — dead tests first (continuity, insulation resistance, polarity), then live tests (Zs, PFC, RCD operation).
  • 3The Electrical Installation Certificate (EIC) is a legal requirement for all new installations. It must be issued before the installation is handed over to the customer.
  • 4Labelling every circuit at the consumer unit with a circuit chart is required under BS 7671 Regulation 514.9 — unlabelled boards fail inspection.
  • 5Elec-Mate lets you complete EIC certificates and the full schedule of test results on your phone, with voice entry for test readings and AI-assisted observation coding.
01 · Installation Guide

What Is Second Fix Electrical?

Second fix electrical is the final stage of an electrical installation — the work that transforms cables protruding from walls and ceilings into a fully functioning, tested, and certified electrical system. It happens after plastering, decorating, and flooring are complete (or at least substantially complete).

Where first fix is about infrastructure — cables, containment, and back boxes — second fix is about completion. It includes fitting every accessory (socket, switch, light fitting, smoke detector, and fixed appliance), wiring and commissioning the consumer unit, labelling all circuits, performing the full initial verification testing sequence, and issuing the Electrical Installation Certificate (EIC).

Second fix is where the electrician demonstrates their workmanship. Neat terminations, correct torque on connections, level accessories, and a professionally labelled consumer unit all contribute to the customer's impression of the finished job — and to the inspector's assessment if the work is subject to a competent person scheme inspection.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Fitting Accessories: Sockets, Switches, and Light Fittings

Fitting accessories at second fix requires care and attention to detail. Every connection must be correct (polarity, tight termination, correct torque), every accessory must be level and flush with the wall surface, and every earth connection must be made properly.

  • Socket outlets — strip the cable sheath back to just inside the back box. Strip individual cores to the correct length for the terminal. Connect brown to L, blue to N, green/yellow to E. Tighten terminals to the manufacturer's specified torque. Earth the metal back box with a flying earth lead from the accessory earth terminal to the back box earth terminal.
  • Switches — for one-way switching, connect the permanent live (brown) to the COM terminal and the switched live to L1. For two-way switching, connect COM and the two strappers (L1, L2) correctly at both switch positions. Sleeve the blue core brown where it is used as a switched live.
  • Light fittings — ensure the fitting is suitable for the location (IP rating for bathrooms, fire-rated for fire barriers). Connect using the correct terminal block — do not rely on wagos in ceiling voids unless they are accessible for inspection. Downlights through fire barriers must use fire-rated housings.
  • Cooker connection units and fused spurs — size the cable and fuse correctly for the appliance. A 45A cooker switch with a 6.0mm2 cable is standard for most domestic cookers. A fused spur with a 3A or 13A fuse protects fixed appliances such as boilers, extractor fans, and towel rails.
03 · Installation Guide

Consumer Unit Wiring

Wiring the consumer unit is one of the most important tasks at second fix. The consumer unit is the heart of the installation — every circuit originates here, and every protective device must be correctly rated and positioned.

Under BS 7671 and Amendment 4 (A4:2026), consumer units in domestic premises must be constructed of non-combustible material (typically steel). The choice between a split-load board with RCDs and a board populated entirely with RCBOs depends on the installation design and customer requirements.

Consumer Unit Wiring Best Practice

  • Strip cables neatly with consistent sheath lengths. The outer sheath should enter the consumer unit enclosure — do not strip it back outside the enclosure.
  • Route cables neatly around the inside of the enclosure. Use cable combs or ties to keep cables organised and identifiable.
  • Tighten all busbar connections and device terminals to the manufacturer's specified torque. Loose connections cause overheating, arcing, and fires.
  • Install the SPD (Surge Protection Device) if required by the installation design. Connect it to the line side of the main switch.
  • Ensure the main earthing conductor and main protective bonding conductors are correctly terminated at the main earth terminal.
04 · Installation Guide

Labelling and Circuit Charts

BS 7671 Regulation 514.9 requires every circuit to be identified by a label at the distribution board. The circuit chart must show the circuit number, the circuit description (e.g., "Kitchen sockets", "Upstairs lighting"), the protective device type and rating (e.g., "32A Type B MCB"), and the cable size.

  • Circuit chart — must be durable, legible, and fixed inside or adjacent to the consumer unit. Handwritten charts are acceptable under BS 7671 but printed charts look more professional and are easier to update.
  • Warning labels — include labels for dual supply (if applicable), mixed earthing (if applicable), RCD test reminder ("This installation, or part of it, is protected by a device which automatically switches off the supply if an earth fault develops. Test quarterly by pressing the button marked 'T' or 'Test'.").
  • Periodic inspection label — "IMPORTANT — This installation should be periodically inspected and tested" with the recommended date of next inspection.

Elec-Mate generates a professional circuit chart as part of the EIC certificate workflow. Enter the circuit details once and the chart is included in the certificate PDF — no separate chart to print.

05 · Installation Guide

Initial Verification Testing

Initial verification is the testing that proves the installation is safe before it is energised for the first time. Under BS 7671 Chapter 64 and GN3, the tests must be carried out in a specific order — dead tests before live tests.

Dead Tests (Supply Isolated)

  1. Continuity of protective conductors (R1+R2) — verify the CPC is continuous from the distribution board to the furthest point of every circuit.
  2. Continuity of ring final circuits — the figure-of-eight test on every ring circuit. Cross-connect L-L, N-N, and E-E at the distribution board end and measure at every socket. The readings should be consistent.
  3. Insulation resistance — test at 500V DC between all live conductors and earth. Minimum acceptable reading is 1 megohm. Disconnect surge protection devices (SPDs) and any electronic equipment before testing.
  4. Polarity — confirm all single-pole switching devices are in the line conductor. Confirm the connections at every accessory are correct.

Live Tests (Supply Energised)

  1. Earth fault loop impedance (Zs) — measure at the furthest point of every circuit. Compare against the maximum Zs for the protective device (from BS 7671 Table 41.2, 41.3, or 41.4).
  2. Prospective fault current (PSCC) — measure at the origin. This value determines the required breaking capacity of the protective devices.
  3. RCD operation — test every RCD at 1x rated residual current (trip within 300ms) and 5x rated residual current (trip within 40ms for Type AC/A).

Enter test results by voice while you test

Elec-Mate's voice test entry lets you speak your readings directly into the schedule of test results.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Installation Guide

Issuing the Electrical Installation Certificate

The Electrical Installation Certificate (EIC) is the formal document that certifies a new electrical installation complies with BS 7671. It is a legal requirement for all new installations and must be issued before the installation is handed over to the customer.

The EIC consists of several sections:

  • Part 1: Details of the client and installation — client name, installation address, description of the work, and the extent of the installation covered by the certificate.
  • Part 2-4: Designer, installer, and inspector declarations — each signatory confirms their role and that the work complies with BS 7671.
  • Part 5: Supply characteristics and earthing — supply type (TN-S, TN-C-S, TT), voltage, frequency, prospective fault current, and external earth fault loop impedance (Ze).
  • Schedule of items inspected — a checklist covering every aspect of the installation from connections to accessories, cable selection, and protective devices.
  • Schedule of test results — the full test results for every circuit in the installation. This is the most time-consuming section to complete manually.

Elec-Mate's EIC certificate app guides you through every section, auto-populates fields from previous jobs, and lets you enter test results by voice. The finished certificate exports as a professional PDF that you can send to the customer by email or WhatsApp before leaving the site.

Complete EIC certificates on your phone

Join 1,000+ UK electricians creating professional EIC certificates with Elec-Mate. AI board scanner, voice test entry, schedule of test results…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Installation Guide

Common Second Fix Snags to Watch For

Second fix is where installation quality becomes visible. These are the most common snags that inspectors and customers notice:

  • Loose connections — the single most common cause of electrical fires. Tighten every terminal to the manufacturer's specified torque. Re-check after 24 hours if possible (connections can settle after first tightening).
  • Missing earth connections — every metal back box must be earthed. Every accessory with an earth terminal must have the CPC connected. A missing earth on a metal socket faceplate is a C2 (Potentially Dangerous) defect.
  • Blue cores not sleeved brown — where a blue (neutral) core is used as a switched live (e.g., in switch drops), it must be sleeved with brown sleeving to indicate it is a line conductor. Missing sleeving is an inspection failure.
  • No circuit chart — an unlabelled consumer unit fails BS 7671 Regulation 514.9. Every circuit must be identified on a durable chart fixed at the board.
  • Accessories not level — use a spirit level on every socket and switch. Accessories visibly out of level look unprofessional and customers notice.
08 · Installation Guide

Customer Handover

The customer handover is the final step. It is your opportunity to explain the installation, hand over the certificates, and demonstrate the safety features. A professional handover leaves a lasting impression and generates referrals.

  • Walk the customer through the consumer unit — explain the main switch, show them how to reset a tripped MCB or RCD, and demonstrate the RCD test button.
  • Hand over the EIC, the schedule of test results, and the schedule of items inspected. Explain that these documents should be kept safely — they will be needed for future inspections, property sales, and insurance claims.
  • Explain the recommended date of next periodic inspection (typically 5 years for domestic, 3 years for commercial). Write this on the periodic inspection label at the consumer unit.
  • If the installation includes AFDDs or an SPD, explain what they do and what the customer should do if they trip.

Use Elec-Mate's quoting app to send the final invoice alongside the certificate. The customer receives the EIC and the invoice in one professional package — no chasing for payment later.

Frequently Asked Questions About Second Fix Electrical

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Complete Certificates On Site, Not At Your Desk

Elec-Mate lets you test, certify, and invoice in a single visit. Voice test entry, AI board scanning, professional EIC certificates, and instant delivery. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy