SYMBOL REFERENCE

SPD (Surge Protection Device) Symbol BS EN 60617 reference

SPD surge protection device electrical symbol BS EN 60617 — what it represents, where it appears in UK electrical drawings, and how it relates to the rest of the symbol library.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

5 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is the SPD symbol in electrical drawings?

The SPD symbol represents a Surge Protective Device to BS EN 61643-11 — a component that diverts transient overvoltages from lightning or supply switching safely to earth. On UK drawings it appears at the origin of the installation. BS 7671 defines three types by Lightning Protection Zone: Type 1 (incoming service), Type 2 (consumer unit/distribution board) and Type 3 (sensitive final equipment).

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Surge Protective Device to BS EN 61643-11. Types placed by LPZ zone: Type 1 at incoming service (LPZ 0/1, direct lightning), Type 2 at consumer unit/distribution board origin (LPZ 1/2), Type 3 at final equipment.
  • 2BS 7671 Reg 443.4.1: SPD protection is mandatory where a transient overvoltage could result in serious injury to, or loss of, human life (a), or significant financial or data loss (c). Limb (b) was deleted by the A2:2022 Corrigendum (May 2023). For all other cases protection shall be provided unless the owner of the installation declares it is not required because any loss or damage is tolerable and accepts the risk.
  • 3Where Section 443 requires SPDs and no external lightning protection system is fitted, Reg 534.4.1.4 requires Type 2 SPDs as close as possible to the installation origin. PE connecting-conductor minimums (Reg 534.4.10): 6 mm² Cu for Type 2, 16 mm² Cu for Type 1.
  • 4Voltage protection level (Up): for a 230/400 V installation the installed SPD assembly Up shall not exceed 2.5 kV (Reg 534.4.4.2 / Table 443.2 Category II). An SPD on the load side of an RCD needs an RCD with 3 kA 8/20 surge immunity (Reg 534.4.7).
  • 5Section 534 (selection and erection of SPDs) was substantially revised in BS 7671:2018+A4:2026 — apply the current requirements.
  • 6Every Elec-Mate certificate + circuit diagram uses this symbol where applicable, drawn to BS EN 60617.
01 · Symbol Reference

SPD (Surge Protection Device) — BS EN 60617 Symbol

SPD surge protection device electrical symbol BS EN 60617

SPD (Surge Protection Device)

A Surge Protective Device to BS EN 61643-11. Type 1 (lightning current), Type 2 (transient overvoltage), Type 3 (point of use). BS 7671 443.4 risk assessment usually requires Type 2 at origin.

Used in: New installations + rewires — Type 2 at consumer unit origin; Type 1 where lightning protection is fitted.

See all distribution board symbols →

Right-click the symbol above to save the SVG, or use the AI Diagram Builder to drop it into a working drawing.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Symbol Reference

What the SPD (Surge Protection Device) Symbol Represents

The symbol denotes a Surge Protective Device to BS EN 61643-11 — a component that diverts transient overvoltages (from a lightning strike or supply switching) to earth before they reach equipment. Where it appears on a UK drawing it almost always sits at the origin of the installation, alongside the main switch and distribution.

BS 7671 Reg 443.4.1 — when is SPD protection mandatory? Protection against transient overvoltages shall be provided where the consequence caused by the overvoltage could result in:

Reg 443.4.1(a)

Serious injury to, or loss of, human life

Reg 443.4.1(c)

Significant financial or data loss

Limb (b) was deleted by the BS 7671:2018+A2:2022 Corrigendum (May 2023).

For all other cases, protection against transient overvoltages shall be provided unless the owner of the installation declares it is not required due to any loss or damage being tolerable and they accept the risk of damage to equipment and any consequential loss. Record the decision on the certificate.

Section 534 (selection and erection of SPDs) was substantially revised in the BS 7671:2018+A4:2026 amendment, including the voltage protection level (Up) selection criteria covered further down this page.

03 · Symbol Reference

SPD Types 1, 2 and 3 — at a Glance

Three SPD types are positioned by the Lightning Protection Zone (LPZ) concept (Figure 534.1). Each protects a different boundary, so a fully protected installation often uses more than one, coordinated together.

Type 1

LPZ 0/1 boundary

Handles partial direct lightning current (10/350 µs waveform). Required at the origin where the structure has an external lightning protection system or otherwise needs protection against direct lightning. Bigger connecting conductors than a Type 2.

Type 2

LPZ 1/2 boundary

Handles transient overvoltage (8/20 µs waveform) at the consumer unit or main distribution board origin. The most common device on a UK domestic or light-commercial drawing.

Type 3

point of use

Fine protection at, or close to, sensitive final equipment. Always installed downstream of, and coordinated with, a Type 1 and/or Type 2 device — never on its own.

Type 2 or Type 3 SPDs may also be placed in sub-distribution boards or close to the equipment to be protected to achieve the required voltage protection level, coordinated with the device(s) at the origin (Reg 534.4.1.5; Figure 534.2).

04 · Symbol Reference

When + Where the SPD (Surge Protection Device) Symbol Is Used

Once Section 443 has established that SPDs are required, Section 534 decides which type goes where. The trigger is whether the structure has external lightning protection:

Reg 534.4.1.4

No external lightning protection (or no need for direct-lightning protection): install Type 2 SPDs as close as possible to the origin of the installation — the consumer unit or main distribution board.

Reg 534.4.1.3

External lightning protection fitted (or direct-lightning protection required): install Type 1 SPDs as close as possible to the origin, at the LPZ 0/1 boundary on the incoming service.

SPDs with RCDs (Reg 534.4.7): where an SPD sits on the load side of an RCD, that RCD shall have an immunity to surge currents of at least 3 kA 8/20 — a Type S time-delayed RCD satisfies this. Installing a Type 1 SPD downstream of an RCD is not recommended.

For the full set of distribution symbols, see the Distribution Symbols reference page — covering every related symbol with the same level of installation context.

Drop this symbol into a circuit drawing

The Elec-Mate Diagram Builder gives you every BS EN 60617 symbol on a draggable canvas — perfect for EIC schedules, EICR observation diagrams…

Open the Diagram Builder
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · Symbol Reference

SPD Connecting Conductor Sizing (Reg 534.4.10)

Reg 534.4.10 sets minimum cross-sectional areas for SPDs installed at or near the origin of the installation. The protective (earthing) connection and the live-side connection have separate minimums:

SPD type (at/near origin)PE / earthing conductorLive conductor
Type 2≥ 6 mm² copper or equivalent≥ 2.5 mm² copper or equivalent
Type 1≥ 16 mm² copper or equivalent≥ 6 mm² copper or equivalent

The live-side conductors connecting the SPD and its overcurrent protective device must also be rated to withstand the prospective short-circuit current expected at that point (Reg 534.4.10, referring to Reg 433.3.1(b)).

Keep the leads short. Reg 534.4.8 requires all conductors and interconnections between the SPD, the line to be protected and any external overcurrent device to be kept as short and straight as possible, with unnecessary loops avoided. Long leads add inductive voltage drop that raises the effective let-through at the equipment.

06 · Symbol Reference

Voltage Protection Level (Up) and Coordination

The voltage protection level (Up) is the let-through voltage an SPD allows to pass. Reg 534.4.4.2 requires Up to be selected against impulse withstand voltage Category II of Table 443.2 and, in no case, to exceed the equipment's required rated impulse voltage. For a standard 230/400 V installation the installed SPD assembly's voltage protection level shall not exceed 2.5 kV.

The 2.5 kV ceiling lines up with the Category II rated impulse voltage for a 230/400 V system in Table 443.2:

Overvoltage categoryExample equipmentRated impulse voltage (Uw)
Category IVOrigin of installation, energy meter6 kV
Category IIIDistribution boards, fixed wiring4 kV
Category IIAppliances, tools (SPD target)2.5 kV
Category ISensitive electronic equipment1.5 kV

Values for a 230/400 V nominal installation, Table 443.2.

Protective distance > 10 m. If the distance between the SPD and the equipment it protects exceeds 10 m, oscillation can raise the voltage at the equipment terminals to as much as twice the SPD's voltage protection level. Add a further coordinated SPD closer to the equipment, or select a device with a lower Up (Reg 534.4.4.2).

FAQ — SPD (Surge Protection Device) Symbol

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Use this symbol in real drawings

Drag and drop BS EN 60617 symbols into circuit diagrams, EICR observation drawings, and EIC distribution schedules. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy