One-way, two-way, intermediate, dimmer, key, PIR, pull-cord, timer, emergency stop, isolator and fan-isolator switch symbols to BS EN 60617.
One-Way Switch
A single switch that breaks or makes the live conductor to a load from one position. The most common domestic switch — used for a single lighting circuit controlled from one location.
Used in: Most lighting circuits, fans, immersion heaters, fixed loads with single control.
See all switch symbols →Two-Way Switch
A switch with two fixed contacts and one common, allowing control of the same load from two locations. Always used in pairs with a second 2-way switch (e.g. staircase, hall-and-landing).
Used in: Staircases, halls with two entries, long corridors, bedrooms with both door and bedhead switches.
See all switch symbols →Intermediate Switch
A four-terminal switch wired between two 2-way switches to give control from three or more locations. The strappers cross over inside the switch.
Used in: Long corridors with three or more entries, large open-plan areas, stairs with mid-landing switch.
See all switch symbols →Dimmer Switch
A switch with a variable resistor or electronic dimming module that controls light output. Specify type — leading-edge for incandescent, trailing-edge or LED-rated for modern LED drivers.
Used in: Living areas, dining rooms, bedrooms; check the dimmer is compatible with the driver type.
See all switch symbols →Double Switch (Two-Gang)
Two switches in one plate, each controlling a separate circuit. Often shown as a single symbol with two action lines or as two adjacent switch symbols on the drawing.
Used in: Bathrooms (light + extractor fan), kitchens (main light + over-cooker light), living rooms (two zones).
See all switch symbols →Pull-Cord Switch
A ceiling-mounted switch operated by a hanging cord. Required in zone 1 and zone 2 of bathrooms where wall switches inside the room are not permitted under BS 7671 Section 701.
Used in: Bathrooms (BS 7671 701.512.3 compliant), shower rooms, en-suites; also used for high-level switches.
See all switch symbols →Fan Isolator (3-Pole)
A 3-pole isolating switch that disconnects live, neutral and switched-live to a bathroom extractor fan. Required for safe maintenance — must be accessible but outside the bathroom zones.
Used in: Outside bathroom door, above the fan or in an adjacent room; needed on every extractor fan installation.
See all switch symbols →PIR Switch (Occupancy Sensor)
A switch incorporating a passive infrared movement sensor. Turns the load on when motion is detected and off after a programmed time-out. Often combined with a manual override.
Used in: Toilets, corridors, stairwells, loft hatches, security lighting; reduces energy use in low-occupancy areas.
See all switch symbols →Timer Switch
A switch that controls load duration — either a momentary push-to-time or a 24-hour/weekly programmable timer. Common for immersion heaters, towel rails, and outdoor lighting.
Used in: Hot water tanks, towel rails, security lights, irrigation systems, signage lighting.
See all switch symbols →Key Switch
A switch operated only with a key — used where unauthorised operation must be prevented. Common in schools, retail, plant rooms and emergency override circuits.
Used in: School halls, server rooms, retail shutters, emergency overrides, alarm bypass switches.
See all switch symbols →Emergency Stop (E-Stop)
A latching push-button that immediately disconnects supply to dangerous equipment. Mushroom head, red on yellow background. Must be reset deliberately — twist-release or key-reset.
Used in: Workshops, kitchens (cooker isolation), production lines, lifts, swimming pool plant rooms.
See all switch symbols →Isolator (Switch-Disconnector)
A switching device that fully isolates a circuit or item of equipment for maintenance. Must be lockable in the OFF position per BS 7671 Section 537. Different from a functional switch.
Used in: Boilers, immersion heaters, EV chargers, solar PV DC isolators, sub-mains, plant equipment.
See all switch symbols →Heater Switch (45A DP)
A 45A double-pole switch with a neon indicator, used for high-load fixed appliances. Switches both live and neutral. Often labelled with the load it controls.
Used in: Electric showers, panel heaters, immersion tanks, towel rails — anything above 13A.
See all switch symbols →Single 13A, double 13A, fused spur, switched fused spur, cooker, shaver, USB, data, telephone, TV, EV charger and outdoor IP66 socket symbols.
Single 13A Socket Outlet
A single 13A switched socket to BS 1363. The basic socket symbol — a semicircle with a line indicating switched. UK standard for general-purpose socket circuits.
Used in: General-purpose outlets, behind appliances, individual radial circuits, kitchen specifics.
See all socket outlet symbols →Double 13A Socket Outlet
A twin 13A switched socket — two outlets on one back box. Drawn as two semicircles back-to-back. Standard outlet for living spaces, bedrooms and offices.
Used in: Bedrooms (typically 2-4 doubles), living rooms, kitchens, offices — the workhorse outlet.
See all socket outlet symbols →Fused Spur (Unswitched)
A Fused Connection Unit (FCU) with internal fuse providing local protection for a fixed appliance. Unswitched version — no front rocker. Used where switching is not needed at the spur.
Used in: Boilers, extractor fans, central heating pumps, doorbells, fixed wireless access points.
See all socket outlet symbols →Switched Fused Spur
A Fused Connection Unit with a front-panel switch + neon indicator. Allows local isolation of the fixed appliance without resorting to the consumer unit. Most common FCU type.
Used in: Towel rails, immersion heaters, garden lighting, alarms, garage door operators.
See all socket outlet symbols →Unswitched Spur (Non-Fused)
A connection outlet without integral fuse — relies on the upstream circuit fuse or breaker for protection. Often a flex outlet plate for permanently-wired flex-connected appliances.
Used in: Flex outlets behind built-in ovens (separately fused), wall-hung TVs, fixed kitchen kit.
See all socket outlet symbols →Cooker Outlet (45A)
A 45A cooker connection point — usually a 45A DP switch with optional 13A socket above the worktop, feeding the cooker outlet plate behind the appliance.
Used in: Electric range cookers, double ovens, hobs over 7.2 kW; supplied on its own radial circuit.
See all socket outlet symbols →Shaver Socket
A bathroom-compliant socket with built-in isolating transformer to BS EN 61558-2-5. Permitted in bathroom zone 2 because the transformer galvanically isolates the user from earth.
Used in: Bathrooms, en-suites, hotel rooms — the only socket type permitted in bathroom zones.
See all socket outlet symbols →USB Socket
A 13A socket outlet with integrated USB-A or USB-C charging ports. Combines mains and low-voltage charging in one back box. Specify USB-C PD for modern devices.
Used in: Bedside, desks, hotel rooms, kitchen islands — anywhere phones and tablets need charging.
See all socket outlet symbols →Data Socket (RJ45)
A structured cabling outlet to BS EN 50173. Cat 5e (1 Gb/s), Cat 6 (1 Gb/s longer reach), or Cat 6A (10 Gb/s). Terminated in an RJ45 module.
Used in: Office desks, WiFi access points, CCTV camera locations, hard-wired smart home devices.
See all socket outlet symbols →Telephone Socket
A telephone master or extension socket. UK master socket has BT engineer test socket; extensions are wired to the master. Increasingly replaced by RJ45 data sockets.
Used in: Legacy phone wiring, fax machines, alarm phone diallers, FTTC modems.
See all socket outlet symbols →TV Aerial Socket
A coaxial outlet for TV aerial, FM/DAB radio or satellite. Multi-output back boxes can combine TV + FM + satellite in one face plate.
Used in: Living rooms, bedrooms, kitchens; satellite outlets need separate F-type connectors.
See all socket outlet symbols →Comms Cabinet Outlet
A communications/networking cabinet — typically a 12U or 18U wall-mounted rack housing the patch panel, network switch, router and structured-cabling termination.
Used in: Loft, plant room, under-stairs; central termination point for all data sockets in a building.
See all socket outlet symbols →EV Charger Outlet
An electric vehicle charge point to BS 7671 Section 722. Typically 7.2 kW single-phase or 22 kW three-phase, with Type 2 (Mennekes) socket or tethered lead.
Used in: Driveways, car parks, fleet depots; needs dedicated circuit + Type A RCD or RDC-DD per 722.531.
See all socket outlet symbols →Outdoor IP66 Socket
A weatherproof socket to IP66 ingress protection. Hinged cover seals against dust and powerful water jets. Must be RCD protected per BS 7671.
Used in: Gardens, sheds, outdoor power tools, Christmas lights, pond pumps, EV charging from a standard socket.
See all socket outlet symbols →Floor Socket (Floor Box)
A flush-mounted socket installed in the floor — typically a floor box with two 13A sockets and data outlets. Used in open-plan offices where wall outlets are too distant.
Used in: Open-plan offices, conference rooms, retail floor displays, exhibition halls.
See all socket outlet symbols →Pendant, ceiling, downlight, wall, bulkhead, high bay, fluorescent, LED strip, emergency, twin-emergency, exit sign, outside light and PIR sensor symbols.
Pendant Light
A ceiling-mounted light suspended on a flex or chain from a rose. The most common domestic light fitting — drawn as a circle with a cross.
Used in: Living rooms, bedrooms, dining rooms, hallways; the default UK domestic light point.
See all lighting symbols →Ceiling Light (Flush)
A flush-mounted ceiling light — the fitting sits directly against the ceiling rather than suspended. Common in kitchens, bathrooms and low-ceiling rooms.
Used in: Kitchens, bathrooms, hallways with low ceilings, loft conversions.
See all lighting symbols →Downlight (Recessed)
A recessed downlight set into the ceiling void. Fire-rated downlights are required where they breach a fire-rated ceiling (e.g. flats, loft conversions, above habitable rooms).
Used in: Kitchens, bathrooms (zone-rated), corridors, retail; the modern UK lighting default.
See all lighting symbols →Wall Light
A wall-mounted light fitting. Symbol drawn against the wall line of the plan. Often used with dimming or two-way switching for ambience.
Used in: Bedrooms (bedside), living rooms, hallways, staircases, restaurants.
See all lighting symbols →Bulkhead Light
A robust enclosed light fitting designed for outdoor or utility use. Typically IP65 with a polycarbonate diffuser. Common with integrated PIR sensor for security.
Used in: External walls, garages, sheds, plant rooms, communal stairwells.
See all lighting symbols →Outside Light
An external light fitting, typically IP44 or higher. Includes wall lights, post lights, ground-mounted spike spots, soffit downlights and porch lights.
Used in: Front and rear of houses, gardens, pathways, garages; usually with PIR or photocell control.
See all lighting symbols →PIR Sensor (Lighting)
A passive infrared sensor that detects movement and switches connected lights on. Separate from a PIR switch — the sensor is the input to a relay or control module.
Used in: Security lighting, corridors with extended throw, large rooms with multiple zones.
See all lighting symbols →Emergency Light
A non-maintained emergency light to BS 5266. Off in normal use; switches on automatically when the mains supply fails. Tested monthly and annually per BS 5266-1.
Used in: Escape routes, stairwells, plant rooms, kitchens, places of assembly.
See all lighting symbols →Twin Emergency Spot
A self-contained emergency luminaire with two adjustable spotlights and an internal battery. Provides high-output emergency illumination of escape routes on mains failure.
Used in: Open-plan offices, retail floors, plant rooms, warehouses, large halls.
See all lighting symbols →Exit Sign
A maintained or non-maintained emergency exit sign to BS EN 1838. Indicates the direction of escape; runs on battery during mains failure for at least 3 hours per BS 5266.
Used in: Above doors on escape routes, change-of-direction points, top of staircases.
See all lighting symbols →Fluorescent Fitting (Batten)
A linear fluorescent or LED-batten fitting. Most modern installations now use LED battens — same symbol applies. Lamp length specified separately (typically 1.2 m or 1.5 m).
Used in: Garages, plant rooms, workshops, kitchens, commercial corridors, retail back-of-house.
See all lighting symbols →LED Strip Lighting
A linear LED tape or strip light. Requires a constant-voltage driver (usually 12 V or 24 V DC). Often dimmable via the driver or via 0-10V / DALI control.
Used in: Under-cabinet kitchens, cove lighting, stairs, bathroom mirrors, retail display shelves.
See all lighting symbols →High Bay Light
A high-output LED or HID light fitting designed for high-ceiling industrial spaces (typically 6-15 m mounting height). Wide-beam or narrow-beam reflectors depending on layout.
Used in: Warehouses, factories, gymnasiums, indoor sports halls, large retail spaces.
See all lighting symbols →Consumer unit, distribution board, sub-main, MCB, MCCB, RCD, RCBO, SPD, meter, contactor, main isolator, busbar chamber, changeover and generator changeover symbols.
Consumer Unit
A domestic consumer unit (fuseboard) to BS EN 61439-3. Houses the main switch, RCD/RCBO/MCB protective devices, and (since 2018) SPD and AFDD where required.
Used in: Domestic origin of the installation — typically meter cupboard, under-stairs, garage or hallway.
See all distribution board symbols →Distribution Board
A three-phase or single-phase distribution board to BS EN 61439-3 (commercial). Holds MCBs, RCBOs and MCCBs serving final circuits in commercial and industrial buildings.
Used in: Commercial buildings, offices, schools, retail; one per floor or department typically.
See all distribution board symbols →Sub-Main Board
A distribution board fed by a sub-main from the main switchboard. Sub-divides the installation into manageable zones; reduces voltage drop on long runs.
Used in: Large buildings, multi-tenant offices, plant rooms, lift motor rooms, sub-zones.
See all distribution board symbols →MCB (Miniature Circuit Breaker)
A Miniature Circuit Breaker to BS EN 60898. Protects against overload and short-circuit fault current. Types B, C and D differentiate by magnetic trip characteristic.
Used in: Every domestic + commercial final circuit; standard protection device on distribution boards.
See all distribution board symbols →MCCB (Moulded Case CB)
A Moulded Case Circuit Breaker to BS EN 60947-2. Higher current ratings (typically 100-1600 A) and higher breaking capacity than MCBs. Used as main incomers or for large feeders.
Used in: Main switchgear, sub-main feeders, large motor circuits, three-phase distribution.
See all distribution board symbols →RCD (Residual Current Device)
A Residual Current Device to BS EN 61008. Detects imbalance between live and neutral (earth-fault leakage) and trips. 30 mA RCDs provide additional protection against electric shock.
Used in: Bathrooms, kitchens, outdoor sockets, EV chargers — anywhere BS 7671 requires additional protection.
See all distribution board symbols →RCBO (RCD + MCB Combined)
A Residual Current Breaker with Overcurrent protection to BS EN 61009. Combines RCD + MCB in one device. Each circuit has individual earth fault and overload protection.
Used in: Modern consumer units — preferred to split-load RCD arrangements; one trip = one circuit affected only.
See all distribution board symbols →SPD (Surge Protection Device)
A Surge Protective Device to BS EN 61643-11. Type 1 (lightning current), Type 2 (transient overvoltage), Type 3 (point of use). BS 7671 443.4 risk assessment usually requires Type 2 at origin.
Used in: New installations + rewires — Type 2 at consumer unit origin; Type 1 where lightning protection is fitted.
See all distribution board symbols →Contactor
An electromagnetically-operated switch for high-current loads. Coil energised = contacts close. Used to control motors, heating, lighting circuits and timed loads remotely.
Used in: Immersion heaters with off-peak timer, motor starters, large lighting banks, HVAC plant.
See all distribution board symbols →Main Switch / Isolator
A main switch-disconnector at the origin of the installation. Disconnects all live conductors (including neutral on TT/IT) and must be lockable in OFF position.
Used in: Origin of every installation — domestic consumer unit, commercial main switchboard.
See all distribution board symbols →Electricity Meter
The utility electricity meter — point of supply, owned by the meter operator. Modern smart meters communicate consumption to the supplier automatically.
Used in: Meter cupboard, garage external wall, riser cupboard; the boundary of utility responsibility.
See all distribution board symbols →Changeover Switch
A switch that transfers a load between two sources (typically mains and generator). Manual or automatic (ATS). Always break-before-make to prevent backfeeding the grid.
Used in: Standby generators, UPS bypass, dual-supply critical loads, farms, remote homes.
See all distribution board symbols →Generator Changeover (ATS)
An Automatic Transfer Switch that detects mains failure and switches to a standby generator without manual intervention. Synchronised return-to-mains when supply restored.
Used in: Hospitals, data centres, telecoms, agricultural sites with standby plant.
See all distribution board symbols →Busbar Chamber
A metal enclosure containing busbars to interconnect multiple sub-main cables — typically at the main switchboard. Allows tap-offs to feed distribution boards without joint boxes.
Used in: Main switchboards, riser shafts, multi-tenant feeder distribution.
See all distribution board symbols →Smoke detector, heat detector, CO detector, fire alarm, sounder beacon, break-glass, emergency call point, CCTV, access control, door entry, motion detector, junction box symbols.
Smoke Detector
An optical or ionisation smoke detector to BS EN 14604 (single-station, domestic) or BS 5839-1 (fire alarm system). Interlinked types signal one another via wire or RF.
Used in: Every level of a domestic property, escape routes, places of assembly per regulations.
See all safety + fire + security symbols →Heat Detector
A fire detector that triggers on a fixed temperature (typically 58°C) or rate-of-rise. Used where smoke detectors would false-alarm (kitchens, garages, dusty areas).
Used in: Kitchens, garages, lofts, plant rooms, smoking areas; never in dwellings without an SD elsewhere.
See all safety + fire + security symbols →CO Detector
A carbon monoxide detector to BS EN 50291. Required in rooms with combustion appliances under the Smoke and CO Alarm Regs 2022 (England) and similar in Wales/Scotland.
Used in: Living rooms with gas fires, bedrooms above garages, rooms with solid-fuel stoves or boilers.
See all safety + fire + security symbols →Fire Alarm Sounder
A fire alarm sounder to BS EN 54-3. Produces minimum 65 dB at the bedhead per BS 5839-1, with the fire-alarm tone defined in BS 5839 Annex E.
Used in: Commercial premises, HMOs, places of assembly; covered by fire risk assessment.
See all safety + fire + security symbols →Sounder + Beacon
A combined audible + visual alarm device to BS EN 54-23. The visual indicator is required for the hearing impaired and in high-noise environments where audible signals alone may not be heard.
Used in: WCs, plant rooms, factories, schools, disabled refuge areas, swimming pools.
See all safety + fire + security symbols →Manual Call Point (Break Glass)
A manual call point to BS EN 54-11. The break-glass/press-glass element used to manually trigger the fire alarm system. Sited near exits and on escape routes.
Used in: Every fire-alarm system; on escape routes, at exits, at landing levels.
See all safety + fire + security symbols →Emergency Call Point (Disabled WC)
A disabled-toilet emergency assistance alarm to BS 8300. Pull-cord activator + reset button + indicator outside the WC. Required under Building Regs Part M.
Used in: Accessible WCs in commercial buildings, hospitality, public buildings.
See all safety + fire + security symbols →Disabled Refuge Alarm
A two-way emergency voice communication point at a disabled refuge to BS 5839-9. Allows people awaiting evacuation to communicate with the main control room.
Used in: Stairwells in multi-storey commercial buildings, evacuation lift lobbies.
See all safety + fire + security symbols →Motion Detector (Security)
A PIR or microwave motion detector for an intruder alarm system to BS EN 50131. Typically wall-mounted at 2.0-2.4 m with coverage of 12 m × 12 m for standard PIR.
Used in: Hallways, large rooms, garages; works with door contacts to form a complete zone.
See all safety + fire + security symbols →CCTV Camera
A CCTV camera — typically IP (PoE-powered, RJ45) or analogue HD. Modern installations are IP cameras over Cat 6 with PoE+ for pan-tilt-zoom models.
Used in: Building entrances, car parks, retail floors, secure perimeters; data + power on one Cat 6 cable.
See all safety + fire + security symbols →Access Control Reader
A proximity card, fob or biometric reader controlling a maglock or electric strike. Networked to a central controller. Often integrated with the fire alarm for auto-release on alarm.
Used in: Office entrances, server rooms, restricted-access plant rooms, multi-tenant lobbies.
See all safety + fire + security symbols →Door Entry Panel
An audio or video door entry panel at a main entrance. Connects to handset stations inside the building. Modern systems are IP-based over Cat 6.
Used in: Flats, apartments, gated developments, offices with controlled entry.
See all safety + fire + security symbols →Door Release Button
A green push-button that releases an electrically-locked door from inside (the egress side). Required where access control restricts movement out of a space.
Used in: Inside doors with maglocks/strikes, server rooms, secure office areas.
See all safety + fire + security symbols →Bell / Door Chime
A domestic bell or chime triggered by a push-button at the door. Often supplied via a 12 V transformer in modern wired systems, or battery for wireless.
Used in: Front door, back door, tradesperson entrance; symbol used on domestic drawings.
See all safety + fire + security symbols →Thermostat
A room thermostat controlling heating. Mechanical, electronic or smart (Wi-Fi). Wired thermostats need a 230 V supply or a low-voltage transformer.
Used in: Living room or hallway typically; one zone per heating loop.
See all safety + fire + security symbols →Junction Box
A wiring junction box where cables are joined. Must be accessible per BS 7671 526.3 unless maintenance-free (MF) type. Modern MF boxes use spring terminals.
Used in: Loft cables, behind sockets, lighting circuits, above accessible ceilings.
See all safety + fire + security symbols →Conduit, trunking, busbar trunking, cable tray, cable tray drop, floor trunking, underfloor trunking, riser and floor box symbols.
Conduit
A round metal or PVC conduit containing cables. Sizes 16, 20, 25, 32 mm OD per BS EN 61386. Symbol drawn as a single line, often labelled with size and number of cables.
Used in: Surface or buried; commercial wiring, plant rooms, industrial, where cables need protection.
See all containment symbols →Trunking
A rectangular cable enclosure with removable lid. PVC, metal or compartmented. Higher fill capacity than conduit; allows easy cable additions without rewiring.
Used in: Offices, commercial corridors, server rooms; mini-trunking for surface-wired domestic installations.
See all containment symbols →Busbar Trunking
A factory-built busbar system to BS EN 61439-6. Tap-off boxes connect distribution boards or large loads along the run. High current capacity, low impedance.
Used in: High-rise risers, factories, large commercial buildings — replaces multiple sub-main cables.
See all containment symbols →Cable Tray
A perforated metal tray supporting cables along its length. Open-top, allowing heat dissipation. Common sizes 50-600 mm wide.
Used in: Plant rooms, service corridors, ceiling voids in commercial; supports SWA and multi-core cables.
See all containment symbols →Cable Tray Drop
A vertical section of cable tray dropping from a horizontal run to floor level or equipment. Drawn as a tray with directional indication of descent.
Used in: Drops from ceiling-mounted tray to equipment, riser corners, multi-storey transitions.
See all containment symbols →Floor Trunking
Trunking installed on the floor surface, typically with a low-profile ramp section. Used where furniture layouts demand power and data at floor level.
Used in: Open-plan offices with fixed desk grids, exhibition halls, retail floor displays.
See all containment symbols →Underfloor Trunking
Trunking cast into the floor screed with periodic outlet boxes for floor sockets. Allows discrete power and data delivery without surface-mounted runs.
Used in: Open-plan offices, conference rooms, retail concourses — installed at the screed pour.
See all containment symbols →Vertical Riser
A vertical shaft containing sub-main cables, busbar trunking, and other services running between floors. Fire-stopped at every floor penetration.
Used in: Multi-storey commercial buildings, hotels, hospitals, residential blocks.
See all containment symbols →Floor Box (Multi-Service)
A flush-mounted floor outlet housing two 13A sockets, one or two RJ45 data outlets, and optional audio/video connections. Hinged lid keeps the floor flush.
Used in: Open-plan offices, conference rooms, restaurant floors — discreet desk-level access.
See all containment symbols →Motor, transformer, UPS, generator, fan, pump, AHU, lift, sub-main and panel board symbols for installation drawings.
Electric Motor
An electric motor — typically three-phase induction. Symbol shows a circle with "M" inside. Specify phase, voltage, kW and starter type (DOL, star-delta, soft starter, VFD).
Used in: HVAC fans, pumps, lift drives, escalators, industrial machinery.
See all equipment symbols →Transformer
A two-winding transformer — symbol shows two coupled coils. Step-up or step-down depending on turns ratio. Used for LV-LV (e.g. 230-12V) or HV-LV (e.g. 11kV-415V).
Used in: Doorbells, garden lighting (low voltage), 11 kV-415 V substations, isolating transformers.
See all equipment symbols →UPS (Uninterruptible Power Supply)
An online or line-interactive UPS. Maintains supply to critical loads during mains failure (typically 10-30 minutes) until generator starts or supply restored.
Used in: Data centres, server rooms, hospital ITU, telephone exchanges, security systems.
See all equipment symbols →Sub-Main
A sub-main supply — a cable feeding a distribution board from a higher-level board. Sized to handle the maximum demand of all downstream final circuits.
Used in: Multi-storey commercial, large dwellings, outbuildings, garages; sized for voltage drop on long runs.
See all equipment symbols →Industrial Fan
A large-volume fan — axial, centrifugal or in-line. Drawn on plans where the electrical supply termination is shown. Often supplied via local isolator.
Used in: Mechanical extract, HVAC plant rooms, smoke ventilation, industrial process exhaust.
See all equipment symbols →Pump
A pump driven by an electric motor — water, heating circulator, condensate, sewage. Symbol typically shows pump body with electrical termination point.
Used in: Boiler plant, water boosting, pond / pool plant, lift hydraulics, fire-fighting wet risers.
See all equipment symbols →Air Handling Unit (AHU)
An air handling unit containing fans, filters, coils and dampers. Electrically intensive — fan motors, heating/cooling coil pumps, controls all need supply.
Used in: Plant rooms serving HVAC for commercial buildings, hospitals, retail, hotels.
See all equipment symbols →Lift / Elevator
A lift drive — supplied from a dedicated three-phase circuit with its own isolation per BS 7671 Section 530. Lift motor rooms require lockable disconnection.
Used in: Multi-storey commercial + residential; needs locked main isolator inside motor room.
See all equipment symbols →Panel Board (Motor Control Centre)
A motor control centre or control panel housing multiple motor starters, contactors, and overload protection. PLC-controlled in modern installations.
Used in: Industrial plant rooms, water treatment, factory production lines, large HVAC plant.
See all equipment symbols →Boiler, water heater, panel heater, air conditioning, fan coil unit, towel rail, heater and hand dryer symbols where electrical supply is required.
Boiler
A heating boiler — gas, oil, or electric. Even gas/oil boilers need a 230 V supply for pumps, controls, and ignition. Supplied via switched fused spur.
Used in: Kitchens, utility rooms, garages, lofts; needs local 3A fused isolation per BS 7671.
See all mechanical + hvac symbols →Water Heater (Immersion)
An electric water heater — usually a 3 kW immersion in a hot water cylinder, or instantaneous undersink/handwash unit. Supplied from a dedicated radial.
Used in: Hot water cylinders (in airing cupboard), under sinks, point-of-use in remote washrooms.
See all mechanical + hvac symbols →Panel Heater
A wall-mounted electric panel heater — convection, fan-assisted, or radiant. Sizes typically 0.5-2.5 kW. Often timer/thermostat controlled.
Used in: Offices, holiday lets, supplementary heating, garages — wherever wet heating is impractical.
See all mechanical + hvac symbols →Air Conditioning Unit
An air conditioning unit — split system or VRV/VRF. Indoor unit + outdoor condenser. Electrical supply usually fed to the outdoor unit which powers the indoor head.
Used in: Server rooms, offices, retail; needs F-gas certified installer; isolator local to outdoor unit.
See all mechanical + hvac symbols →Fan Coil Unit (FCU)
A fan coil unit — local fan + heating/cooling coil supplied from a central plant. Provides zone-level temperature control in commercial HVAC.
Used in: Offices, hotels, hospitals; typically ceiling-mounted with low-voltage controls + 230 V fan supply.
See all mechanical + hvac symbols →Electric Towel Rail
A heated towel rail with an integral element. Typically 100-600 W. Supplied via switched fused spur outside the bathroom; must be RCD-protected.
Used in: Bathrooms, en-suites, utility rooms; FCU outside the bathroom or zone 3 with IPX4.
See all mechanical + hvac symbols →Heater (General)
A general-purpose electric heater symbol — covers radiant, convection, fan and oil-filled portable heaters. Supplied via switched fused spur or socket.
Used in: Domestic supplementary heating, offices, workshops, garages.
See all mechanical + hvac symbols →Hand Dryer
A commercial hand dryer — typically 1.5-2.5 kW. Supplied via switched fused spur with local isolation. RCD protected per BS 7671 411.3.3.
Used in: Commercial WCs, restaurants, schools, hospitality; needs 2.5 kW supply on its own spur.
See all mechanical + hvac symbols →Solar panel, inverter, battery storage, generator and EV distribution symbols for prosumer installations (BS 7671 Section 712).
Solar PV Panel
A solar photovoltaic panel. Typical residential modules 360-450 W. Arrays wired in series strings (matching inverter MPPT voltage window) and parallel to scale capacity.
Used in: Roof-mounted residential + commercial PV; BS 7671 Section 712 + MCS standards apply.
See all solar pv + renewables symbols →PV Inverter
A solar PV inverter converting DC from the array to AC for grid synchronisation. Single-phase up to ~3.68 kW (G98), three-phase above (G99). Hybrid types include battery interface.
Used in: Loft, plant room, garage wall; close to consumer unit for short AC tails.
See all solar pv + renewables symbols →Battery Storage
A battery energy storage system (BESS) — typically lithium iron phosphate (LFP). Sizes 5-15 kWh domestic, up to MWh commercial. AC-coupled or DC-coupled to PV.
Used in: Domestic time-shifting, off-grid systems, commercial peak-shaving; MCS Battery Storage required.
See all solar pv + renewables symbols →EV Distribution Board
A dedicated distribution board for one or more EV chargers — usually with load management, dynamic load balancing, and Type A RCDs or RDC-DD per BS 7671 722.531.
Used in: Multi-bay car parks, fleet depots, apartment block charging; serves 3-100+ chargers.
See all solar pv + renewables symbols →Generator
An on-site generator — diesel, gas or biogas. Used as standby for grid failure or as primary supply off-grid. Symbol shows a circle with "G".
Used in: Standby for hospitals, data centres; primary for remote off-grid sites; CHP for industrial.
See all solar pv + renewables symbols →BMS controller, control panel, lighting control, sensor and humidity sensor symbols for smart building installations.
BMS Controller
A Building Management System (BMS) controller — central or distributed unit that schedules HVAC, lighting and other plant. BACnet, Modbus or proprietary protocols.
Used in: Commercial offices, hospitals, schools; centralises control of all building services.
See all controls + bms symbols →Control Panel
A local control panel — typically housing a PLC, contactors, overloads, and HMI for a discrete piece of plant or process line.
Used in: Industrial plant, water treatment, packaging lines, kitchen extract control.
See all controls + bms symbols →Lighting Control Module
A lighting control module — DALI gateway, KNX dimmer, Lutron QS module, or wireless mesh controller. Schedules, scenes, daylight harvesting and occupancy linkage.
Used in: Offices, retail, hospitality, schools; smart lighting saves 30-50% on energy vs static control.
See all controls + bms symbols →Generic Sensor
A generic BMS sensor input — temperature, CO2, occupancy, light level. Wired back to a BMS controller or PLC. 0-10 V, 4-20 mA or digital bus.
Used in: Above ceiling, in ducts, on walls; BMS scheduling depends on accurate sensor placement.
See all controls + bms symbols →Humidity Sensor
A relative humidity sensor — typically 0-100% RH range. Used to control extract fans, HVAC dampers, dehumidifiers; common in bathrooms, swimming pools, archives.
Used in: Bathroom fan control, indoor air quality monitoring, art gallery + archive HVAC.
See all controls + bms symbols →Door (left/right/double), window, stairs and north arrow symbols used on electrical installation drawings to show building context.
Door (Hinged Left)
An architectural door symbol showing a left-hinged swing. Used on electrical layout drawings to show building context — wall switch positions relate to door swing.
Used in: Electrical layout plans, fire alarm zone plans, emergency lighting drawings.
See all architectural symbols →Door (Hinged Right)
An architectural door symbol showing a right-hinged swing. Used to indicate the door swing direction relative to electrical accessories on the drawing.
Used in: All electrical layout drawings; tells the installer which side of the door switches go.
See all architectural symbols →Double Door
A double-door symbol — both leaves shown. Used for main entrances, large reception doors, fire exits and accessible-width openings.
Used in: Main entrances, lobbies, fire escapes, accessible refuge points.
See all architectural symbols →Window
A window symbol shown on the wall line. Helps the installer locate fittings relative to natural light, identify external walls, and avoid cabling routes through openings.
Used in: External walls on layout drawings, daylight-harvesting lighting plans.
See all architectural symbols →Stairs
An architectural stairs symbol showing tread direction. Two-way switching at top and bottom of stairs is the textbook BS 7671 use case for the symbol.
Used in: Stairwells; emergency lighting + two-way switching are the obvious requirements.
See all architectural symbols →North Arrow
A compass north indicator. Critical on solar PV drawings (orientation determines yield), CCTV camera plans (sun glare avoidance), and general drawing orientation.
Used in: Solar PV system designs, CCTV / external lighting plans, all professional electrical drawings.
See all architectural symbols →