INSTALLATION GUIDE

SWA Cable Installation
Armoured Cable Guide UK

Steel Wire Armoured (SWA) cable is the standard choice for outdoor, underground, and exposed wiring in UK electrical installations. This guide covers cable selection, burial depth, gland types and termination, bonding the steel wire armour, testing procedures, and full BS 7671 compliance requirements.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1SWA cable must be terminated using the correct cable gland (CW, CX, or BW type) to maintain the mechanical and earth continuity of the steel wire armour. Incorrect glands compromise both protection and the CPC path.
  • 2BS 7671 requires a minimum burial depth of 500 mm for cables without additional mechanical protection, or shallower with cable tiles, duct, or other protection. Route marker tape must be placed 150 mm above the cable.
  • 3The steel wire armour can serve as the circuit protective conductor (CPC) provided the armour cross-sectional area meets the requirements of BS 7671 Table 54.7 or the adiabatic equation.
  • 4SWA cable does not require RCD protection when used in walls, as the earthed metallic covering satisfies BS 7671 Regulation 411.3.4 — this is a key advantage over twin and earth cable.
  • 5Elec-Mate includes cable sizing calculators with SWA current-carrying capacity tables, voltage drop verification, and the adiabatic equation check for armour as CPC.
01 · Installation Guide

What Is SWA Cable?

Steel Wire Armoured (SWA) cable is a heavy-duty power cable with an outer layer of galvanised steel wires providing mechanical protection and an earth continuity path. It is the standard cable type for underground installations, outdoor wiring, and any situation where the cable is exposed to potential mechanical damage.

SWA cable construction consists of several layers: copper (or aluminium) conductors, PVC or XLPE insulation on each conductor, an inner PVC bedding sheath, the steel wire armour layer, and an outer PVC oversheath. The steel wire armour provides substantial mechanical protection against impact, crushing, and penetration — making the cable suitable for direct burial, surface mounting on walls, and installation in exposed locations.

SWA cable is available in a wide range of sizes from 1.5 mm squared to 400 mm squared and above, in 2-core, 3-core, 4-core, and 5-core configurations. For most domestic and light commercial installations, 2-core and 3-core SWA in sizes from 2.5 mm squared to 25 mm squared covers the majority of applications — including supplies to outbuildings, garages, EV chargers, garden offices, and external lighting.

The key advantage of SWA cable over standard twin and earth (T&E) cable is its mechanical protection and the earthed metallic covering. Under BS 7671, cables with an earthed metallic covering are exempt from the requirement for additional RCD protection when installed in walls (Regulation 411.3.4), and the armour provides an inherent CPC that does not rely on a separate earth conductor.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

Cable Selection and Sizing

Selecting the correct SWA cable follows the same BS 7671 cable sizing process as any other cable type, but with specific tables for SWA current-carrying capacity and voltage drop values.

The installation method determines which current-carrying capacity table to use. SWA cable is commonly installed using Reference Method D (direct buried), Reference Method C (clipped direct to a surface), or Reference Method B (in trunking or conduit). Each method has different current ratings because the cable's ability to dissipate heat varies with the installation method.

Key Sizing Considerations for SWA

  • Insulation type — PVC-insulated SWA (BS 5467) has a maximum conductor temperature of 70 degrees Celsius. XLPE-insulated SWA (BS 5467) has a maximum of 90 degrees Celsius and carries significantly higher current for the same conductor size.
  • Number of cores — 2-core SWA is used for single-phase circuits (line and neutral, with the armour as CPC). 3-core SWA is used where a separate CPC conductor is needed or for three-phase supplies. 4-core is used for three-phase with neutral.
  • Voltage drop — SWA cables are often used for longer runs (to outbuildings, across sites). Longer runs mean higher voltage drop, which may require upsizing the cable beyond the minimum for current-carrying capacity. Always verify voltage drop using the mV/A/m values from BS 7671 Appendix 4.
  • Ground temperature — For direct burial, the soil temperature and thermal resistivity affect the cable rating. BS 7671 assumes a ground temperature of 20 degrees Celsius and a soil thermal resistivity of 2.5 K.m/W for standard ratings. Different conditions require correction factors.

SWA Cable Sizing Calculator

Elec-Mate's cable sizing calculator includes all BS 7671 Appendix 4 tables for SWA cable — PVC and XLPE insulation, all installation methods…

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · Installation Guide

Burial Depth Requirements

When installing SWA cable underground, BS 7671 and the IET On-Site Guide provide guidance on minimum burial depth. The requirements depend on the location and whether additional mechanical protection is provided.

Without Protection

Minimum 500 mm burial depth below finished ground level. This applies to general areas such as gardens, driveways, and fields where the cable is direct-buried with no additional mechanical protection.

Route marker tape (yellow warning tape marked "CAUTION — ELECTRIC CABLE BELOW") must be placed at least 150 mm above the cable to warn anyone digging in the area.

With Protection

Where additional mechanical protection is provided — such as cable tiles, concrete troughs, or duct — the cable may be installed at a shallower depth. Cable tiles placed directly above the cable provide impact resistance and a visual warning during excavation.

Under roads and areas subject to heavy vehicular traffic, a minimum depth of 600 mm is recommended even with SWA cable, due to the increased risk of damage from construction vehicles and resurfacing work.

The cable route should be recorded on the installation drawings and provided to the client. For domestic installations, a simple sketch showing the cable route, depth, and key reference points (distance from walls, fences, and other permanent features) is essential. This prevents future damage when the client or their gardener digs in the area.

Where SWA cable crosses under a road, driveway, or patio, it should be installed in a duct (typically 63 mm or 100 mm diameter MDPE or PVC duct) to allow future replacement without excavation. The duct should extend at least 300 mm beyond the edge of the hard surface on each side.

Earthing arrangements for outdoor installations — check PME restrictions for supplies extending outside the main equipotential zone.
04 · Installation Guide

Cable Glands and Termination

Correct termination of SWA cable is critical for both mechanical integrity and earth continuity. The cable gland grips the steel wire armour, provides strain relief, and maintains the electrical connection between the armour and the enclosure or earth system.

There are three main types of cable gland used with SWA cable in UK installations:

CW Gland (Indoor Use)

The CW (Cable Wire) gland is the standard indoor gland for SWA cable. It consists of a body, a compression ring (cone), an armour lock ring, and a back nut. The compression ring bites into the steel wire armour to provide mechanical grip and earth continuity. CW glands are rated IP40 and are suitable for dry indoor environments. They are the most commonly used gland type for consumer unit and distribution board entries.

CX Gland (Outdoor / Weatherproof)

The CX gland adds a neoprene shroud (outer seal) to the CW gland design, providing weatherproof sealing to IP68 when fully assembled. CX glands are used for outdoor installations, underground cable entries, and any location where the gland may be exposed to moisture. The shroud seals around the cable oversheath, preventing water ingress at the termination point.

BW Gland (Lead-Sheathed Cable)

BW glands are designed for cable types with a continuous metallic sheath rather than wire armour — such as MICC cable or older lead-sheathed cables. They are not used with standard SWA cable but are mentioned here to avoid confusion when sourcing glands.

Correct SWA Gland Installation

  • Strip the outer sheath to expose the wire armour. Strip length depends on gland size — typically 30 to 50 mm for domestic sizes.
  • Cut the wire armour cleanly with SWA cutters (not a hacksaw, which leaves jagged edges). Fan out the wires evenly around the inner bedding sheath.
  • Fit the gland body through the enclosure knockout. Tighten the locknut on the outside to secure the gland body to the enclosure.
  • Feed the cable into the gland body. Position the compression ring over the fanned armour wires and tighten the back nut to compress the ring onto the armour. This must be tight enough to grip securely but not so tight that it damages the armour wires.
  • For CX glands, slide the shroud over the cable oversheath and tighten to create the weatherproof seal.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
05 · Installation Guide

Bonding the Steel Wire Armour

The steel wire armour of SWA cable serves as an earth continuity path and must be bonded at both ends to ensure effective fault protection. The gland provides the primary bonding connection between the armour and the metallic enclosure (consumer unit, distribution board, junction box, or metal accessory).

For the armour to serve as the sole CPC for the circuit, its cross-sectional area must meet the requirements of BS 7671. Table 54.7 sets out the minimum CPC size based on the line conductor size, and the adiabatic equation (k squared S squared greater than or equal to I squared t) must be verified to ensure the armour can withstand the prospective fault current for the disconnection time of the protective device.

When Is a Separate CPC Needed?

In most domestic installations using 2-core SWA cable (sizes up to 16 mm squared), the steel wire armour cross-sectional area is sufficient to act as the CPC. However, there are situations where an additional CPC conductor may be required:

  • Where the adiabatic equation check shows the armour cannot withstand the prospective fault current — typically with larger cables and high fault levels.
  • Where the armour resistance is too high to achieve the required earth fault loop impedance (Zs) for the protective device to disconnect within the required time.
  • Where the installation specification requires a separate CPC for additional reliability — some commercial and industrial specifications mandate this.

In these cases, use 3-core SWA cable and connect the third core as the CPC, bonded in parallel with the armour at both ends.

At the supply end, ensure the gland makes a solid connection to the metallic consumer unit or distribution board enclosure. At the load end, if the cable terminates at a non-metallic enclosure (such as a plastic isolator or junction box), an earth tail must be connected from the gland earth tag to the circuit earth terminal.

06 · Installation Guide

Outdoor and Underground Installation

SWA cable is the cable of choice for outdoor and underground wiring in the UK. Its mechanical armour provides protection against accidental damage during gardening, landscaping, and construction work, and the cable is rated for direct burial without additional ducting (though ducting is recommended under hard surfaces for future maintenance access).

Trench preparation

Dig the trench to the required depth (minimum 500 mm) with a flat bottom. Remove any sharp stones, rocks, or debris that could damage the cable oversheath. Place a 50 mm layer of fine sand or sifted soil at the bottom of the trench as a bedding layer. Lay the cable on the bedding, then cover with another 50 mm layer of sand or sifted soil before backfilling.

Warning tape and markers

Place yellow warning tape marked "CAUTION — ELECTRIC CABLE BELOW" at least 150 mm above the cable. This provides an early warning to anyone digging in the area. At cable route changes of direction and at each end, install permanent route markers (posts, plaques, or indelible markings on adjacent structures) so the cable route can be traced in future.

Building entry

Where the cable enters a building, use a duct through the wall to prevent damage from building movement and to maintain the building's weather seal. The duct should be sealed at both ends with duct sealant to prevent moisture and vermin entry. The cable should rise vertically from ground level to the entry point — avoid running horizontally along the outside of the building at low level where it is vulnerable to damage.

For EV charger installations, SWA cable from the consumer unit to an external charge point is the standard approach. Check PME restrictions if the supply is TN-C-S — a separate earth electrode may be required for the charge point installation.

AI Installation Guide for SWA Cable

Elec-Mate's AI installer agent provides step-by-step guidance for SWA cable installations. Describe your job — garage supply, garden office, EV charger…

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · Installation Guide

Testing SWA Cable Installations

Testing an SWA cable installation follows the standard BS 7671 testing sequence, but with specific attention to the armour continuity, insulation resistance between cores and armour, and the earth fault loop impedance through the armour CPC.

SWA Cable Test Sequence

  • Continuity of the armour CPC — Measure the resistance of the armour between both glands using a low-resistance ohmmeter. This verifies the glands are making good contact with the armour and the armour is continuous. Record the R2 value (armour resistance) for the R1+R2 calculation.
  • Insulation resistance — Test between all conductors and between each conductor and the armour at 500V DC (for circuits up to 500V). Minimum acceptable reading is 1 megaohm, but new SWA cable should read well above 100 megaohms. Low readings between a conductor and the armour indicate insulation damage — possibly caused during installation (over-bending, crushing, or damage from gland installation).
  • Earth fault loop impedance (Zs) — Measure Zs at the far end of the SWA cable circuit with the circuit energised. The Zs value includes the armour resistance as the CPC return path. Verify the measured Zs does not exceed 80% of the maximum permitted Zs for the protective device (to account for temperature variation).
  • Polarity — Verify correct polarity at all points. For 2-core SWA, confirm that the brown core is connected to line and the blue core to neutral at both ends.

Record all test results on the Electrical Installation Certificate schedule of test results. For SWA circuits, note the armour resistance separately as this is a useful reference for future periodic inspection — an increase in armour resistance may indicate corrosion or deterioration of the gland connections.

Digital Test Result Recording

Record SWA cable test results directly into Elec-Mate's digital certificate forms. The app validates readings against BS 7671 limits…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size and Certify SWA Installations

Elec-Mate's cable sizing calculator, AI installer, and digital certificates cover every SWA cable job. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy