Armoured Cable Design

SWA Cable Size Calculator — Steel Wire Armoured Sizing for Submains and Outbuildings

Enter the load current, run length, and installation method — buried, ducted, clipped, or on tray. The calculator sizes the steel wire armoured cable, applies the correction factors, and checks voltage drop over the long runs SWA is usually asked to make. Select the SWA cable type in the calculator for armoured ratings.

SWA RatingsBuried RunsVoltage DropOutbuilding Submains

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-07-02Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Cable Sizing Calculator

Professional cable sizing with BS 7671 compliance validation

Current Specification

Cable sizing parameters
Installation method (BS 7671)
Selected method
Clipped direct to surface (Method C)
Cable type
Environmental conditions

Standard: 30°C

Affects current rating

Lighting: 3%, Power: 5%

Load characteristics

1.0 = 100% simultaneous load

System parameters

For voltage drop calculation. Typical: 0.8-0.9

Cable selection factors

Cable sizing depends on multiple factors beyond current rating alone:

  • Current-carrying capacity
  • Voltage drop over distance
  • Installation method & ambient temperature
  • Grouping factors when multiple cables run together
  • Short circuit protection requirements

Always consult relevant electrical codes and standards for your specific application.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1SWA (steel wire armoured) cable is the standard choice for buried and external runs — BS 7671 requires a cable buried in the ground to incorporate an earthed armour or metal sheath, or be installed in a duct giving equivalent protection.
  • 2Voltage drop usually governs SWA sizing, not current-carrying capacity — outbuilding runs of 25-60 metres routinely push the size up a step or two beyond what the load current alone would need.
  • 3Buried cables must be marked by cable covers or marker tape and buried deep enough to avoid foreseeable disturbance — accepted practice is around 450mm under gardens and 600mm under driveways, though BS 7671 states no fixed figure.
  • 4The steel armour can serve as the circuit protective conductor where its conductance is adequate — verify it for the size and length, or run a separate CPC.
  • 5A typical 10kW outbuilding at 40m works out at 43.5A, pointing to a 10mm² SWA submain once voltage drop is checked — the calculator confirms the size for your actual load and length.

What Is SWA Cable?

Steel wire armoured cable is a multicore cable with a layer of galvanised steel wires wound around the insulated cores, under an outer PVC sheath. The armour does two jobs: it protects the cable from mechanical damage — spades, rodents, ground movement, impacts — and it can act as an earthed metallic layer around the live conductors, which is what makes SWA suitable for burial.

SWA is available with PVC or XLPE insulation (XLPE runs at a higher conductor temperature and carries more current for the same size), in 2-core, 3-core, 4-core, and 5-core configurations. For a single-phase submain, 3-core is common (line, neutral, and a core used as CPC, or armour as CPC with the third core spare); for three-phase, 4-core or 5-core.

The calculator above includes SWA cable types with their tabulated ratings — select the armoured option and the installation method (buried, in duct, clipped, on tray) to size from the correct table.

When to Use SWA

The jobs where SWA is the standard answer:

  • Outbuilding submains — garages, garden offices, workshops, summer houses. Usually buried across the garden. See the garage supply calculator for the load-assessment side.
  • EV charger runs — external or buried sections to driveway charging points. The EV charger cable size calculator covers the circuit design.
  • Hot tubs and outdoor equipment — hardwired outdoor supplies where the cable needs mechanical protection. See the hot tub electrical calculator.
  • Commercial and industrial distribution — submains on tray or ladder, external plant, and anywhere the cable is exposed to mechanical risk.

The common thread is exposure: outdoors, underground, or anywhere twin and earth would be vulnerable. BS 7671 requires that a cable buried in the ground incorporates an earthed armour or metal sheath suitable for use as a protective conductor — or is installed in a conduit or duct that provides equivalent protection against mechanical damage. SWA is the simplest way to meet that.

What Governs the Size: Capacity, Volt Drop, and the Ground

Four things decide an SWA size, and on long runs it is rarely the first one:

  • Current-carrying capacity — the tabulated rating for the cable type and installation method, derated where needed. Buried cables have their own ratings, affected by soil thermal resistivity and burial depth; cables in ducts are rated differently from direct-buried.
  • Voltage drop — the usual governing factor for outbuilding submains. A 40-60 metre run at 40A+ eats into the 5% limit fast, and the submain should not use the whole allowance — the final circuits in the outbuilding need their share too.
  • Earth fault loop impedance — a long submain adds impedance, and the protective device at the origin still has to disconnect in time. Check with the disconnection time calculator.
  • Grouping — where several SWA cables share a trench or tray, grouping factors reduce each cable's capacity.

A useful habit for submains: size for voltage drop first, then confirm capacity. The calculator runs both checks together and tells you which one governed.

Size an SWA Run in Seconds

Select the SWA cable type, enter the load and length, choose buried or clipped, and get the size with voltage drop verified.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Worked Example: 10kW Outbuilding at 40 Metres

A garden workshop needs a submain for an assessed demand of 10kW — a small consumer unit feeding sockets, lighting, and a 3kW heater. The trench run is 40 metres:

  1. Design current: I = P / V = 10000 / 230 = 43.5A → a 45A or 50A protective device at the origin
  2. First-pass size: on current alone, a 6mm² or 10mm² SWA might carry it depending on method — but check voltage drop before settling
  3. Voltage drop at 10mm²: using the published figure of approximately 4.4 mV/A/m for 10mm² copper: 43.5A x 40m x 4.4 mV/A/m = 7,656mV = 7.66V. As a percentage: 7.66 / 230 = 3.3%
  4. Judgement: 3.3% passes the 5% limit, but leaves only 1.7% for the final circuits inside the workshop. For a workshop with a heavily loaded socket circuit, stepping up to 16mm² (approximately 2.8 mV/A/m, giving 4.87V = 2.1%) buys comfortable headroom for the whole installation

This is the classic SWA sizing story: the load says 10mm², the distance says think bigger. The calculator shows the voltage drop at each size so the trade-off is explicit rather than guessed.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

Burying SWA: Depths, Marker Tape, and Ducting

BS 7671 sets the principles for buried cables: the cable must incorporate an earthed armour or metal sheath suitable for use as a protective conductor (or be in a duct with equivalent mechanical protection), the route must be marked by cable covers or suitable marker tape, and the cable must be buried at a depth sufficient to avoid damage from any reasonably foreseeable disturbance of the ground.

BS 7671 deliberately does not state a fixed depth — "sufficient" depends on what happens above. Accepted practice in the trade:

  • Around 450mm under lawns and flower beds — below spade and rotavator depth
  • Around 600mm under driveways, vehicle routes, and cultivated ground
  • Sand bed and marker tape — lay the cable on a bed free of sharp stones, cover, then marker tape part-way up the backfill

Ducting is worth serious consideration even where direct burial is permitted: a duct with a draw cord makes the inevitable future upgrade — a bigger outbuilding load, an EV charger, three-phase — a pull-through rather than a re-dig. Note that cables in ducts have lower tabulated ratings than direct-buried cables of the same size, so re-check the capacity if you switch from direct burial to duct. The calculator covers both methods.

Glands, Armour, and Earthing

SWA is terminated with mechanical glands that clamp the armour, providing strain relief and electrical continuity from the armour to the gland plate. Getting the termination right matters for safety, not just neatness:

  • The armour must be earthed. It is an exposed (or extraneous) metallic layer around live conductors — the gland and banjo/earth tag connect it to the earthing arrangement at the supply end as a minimum.
  • Armour as CPC — BS 7671 recognises the earthed armour of a buried cable as suitable for use as a protective conductor. Whether it is adequate on its own depends on its conductance for the size and length of the run, verified against the adiabatic requirement — use the adiabatic equation calculator or run a dedicated CPC core where in doubt.
  • Outdoor glands — use weatherproof glands with shrouds for external terminations, and maintain the enclosure's IP rating.
  • Earthing at the outbuilding — decide deliberately whether the outbuilding takes the origin's earthing arrangement or a local TT electrode; on PME supplies this decision needs particular care for outdoor and water-associated equipment.

How to Size an SWA Cable

Five steps from load assessment to a buried, terminated, verified submain.

1

Assess the load

Total the demand the SWA run will supply, with diversity where appropriate. For an outbuilding, list the circuits it will feed and use a realistic assessed demand, not the sum of every breaker.

2

Measure the route

Measure the actual trench or tray route including both ends inside the buildings. Note the installation method for each section — direct buried, in duct, clipped — the worst case governs.

3

Size for voltage drop first

On runs over about 25 metres, voltage drop usually governs. Keep the submain drop low enough to leave allowance for the final circuits beyond it.

4

Confirm current-carrying capacity

Check the tabulated SWA rating for the method, derated for grouping and ground conditions where applicable. The calculator applies these automatically.

5

Plan the burial and terminations

Trench to an appropriate depth (accepted practice around 450-600mm), lay marker tape, and specify glands with the armour earthed — verifying the armour if it serves as the CPC.

SWA Calculator Features

Armoured cable sizing for the runs that twin and earth cannot make.

SWA Ratings Built In

Steel wire armoured cable types with their tabulated ratings — multicore and single-core armoured options.

Buried and Ducted Methods

Direct-buried and in-duct installation methods with the correct rating basis for each.

Long-Run Voltage Drop

The governing check for most submains — calculated from tabulated mV/A/m values over your actual route length.

Submain Design Workflow

Pairs with the diversity and maximum demand calculators to go from outbuilding loads to a finished submain spec.

Adiabatic and Zs Checks

Verify the armour as CPC and the disconnection times with the adiabatic and earth fault loop tools in the same app.

70+ Calculators in One App

Every design calculation an electrician needs, in one place, on the phone in the van.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size SWA submains with confidence

Join 1,000+ UK electricians using Elec-Mate for armoured cable sizing, voltage drop, and certification. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

Cookie Preferences

Manage your privacy settings

We use cookies to enhance your experience and analyse platform usage. Cookie Policy