Outbuilding Submains

Garage Supply Calculator — Load Assessment, Submain Sizing, and Consumer Unit Selection

Add the garage's loads — sockets, lighting, heating, machinery, a future EV charger — and the calculator applies diversity to produce a realistic assessed demand, then recommends the main protective device. From there, size the SWA submain and pick the consumer unit. No more guessing between a 32A and a 63A feed.

Load AssessmentSWA SubmainsSmall Consumer UnitsEV-Ready Design

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

11 min readUpdated 2026-07-02Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Diversity Factor Calculator

Calculate electrical demand after applying IET On-Site Guide diversity allowances

Input Mode

Circuit Loads

Add loads for comprehensive diversity calculation

Load 1

Choose the type of electrical load for accurate diversity calculation

A

Full load current of the circuit

Quantity of identical loads

Ready to Calculate

Add your circuit loads and click "Calculate Diversity" to see results

• Configure installation type and voltage

• Add circuit loads with their types

• Choose between kW or Amperage input

• Get IET On-Site Guide compliant diversity calculations

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1A garage supply is a submain feeding a small consumer unit — the design starts with a realistic assessed demand, not the sum of every breaker in the garage board.
  • 2Diversity is what separates a sensible 40A submain from an unnecessary 80A one: not everything in a garage runs at once, and the assessment should reflect how the space is actually used.
  • 3A typical workshop garage — socket circuit, lighting, and a 2kW heater — assesses to around 30A, pointing to a 40A submain with headroom.
  • 4Voltage drop governs most garage submains: the run is long and the submain must leave allowance within the 5% limit for the final circuits beyond it.
  • 5Adding an EV charger changes everything — a 32A continuous load on top of the garage demand usually decides the submain size, so design for it now even if the charger comes later.

What a Garage Supply Involves

Feeding a detached garage or outbuilding properly means installing a submain: a suitably protected circuit from the house consumer unit (or a dedicated switch fuse) out to a small consumer unit in the garage, which then serves the garage's own final circuits — sockets, lighting, and whatever the space is really for.

The parts of the job:

  • Load assessment — what will the garage actually demand? This page and the calculator above.
  • The submain cable — normally buried SWA, sized for the assessed demand and the run length.
  • The garage consumer unit — a small board with RCD/RCBO protection for the final circuits.
  • The earthing decision — export the house earth or install a TT electrode at the garage.

A single socket on a spur will do for a lawnmower; anything resembling a workshop, gym, office, or EV charging point deserves the full treatment.

Assessing the Load: Realistic, Not Theoretical

The wrong way to size a garage supply is to add up the ratings of every protective device in the garage board — a 32A socket circuit plus a 6A lighting circuit plus a 16A heater circuit does not mean a 54A demand. The right way is to assess what actually runs simultaneously:

  • Sockets — assess by use: a hobby workshop might realistically see one big power tool plus a dust extractor and battery chargers at once, not a fully loaded circuit.
  • Lighting — LED workshop lighting is a small, steady load; apply standard lighting diversity.
  • Heating — the load most likely to run continuously; take fixed heating at full rating in cold months.
  • Fixed machinery — compressors, welders, and saws by their duty: a welder's demand is intermittent but high, and motor starting matters for device selection. See the motor starting current calculator.
  • EV charging — the exception to diversity: a single charger is a continuous full-current load. Take it at 100%.

The calculator above lets you add each load with its type, applies the appropriate diversity, and recommends the main device rating — the number the submain is then designed around.

Assess the Garage Demand in Seconds

Add sockets, lighting, heating, and machinery as separate loads. The calculator applies diversity by load type and recommends the submain protective device.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Worked Example: Workshop Garage at 25 Metres

A detached double garage used as a workshop: one socket circuit, LED lighting, and a 2kW fixed heater. The trench run from the house board is 25 metres:

  1. Sockets: assessed at 20A — realistic simultaneous workshop use, not the 32A device rating
  2. Lighting: 460W of LED battens = 2A; with standard lighting diversity, take 2A
  3. Heater: 2000 / 230 = 8.7A at full rating
  4. Assessed demand: 20 + 2 + 8.7 = 30.7A → a 40A submain device gives sensible headroom
  5. Submain cable: for a 40A buried run, 10mm² SWA is the typical choice. Voltage drop using the published figure of approximately 4.4 mV/A/m for 10mm² copper: 30.7A x 25m x 4.4 mV/A/m = 3,377mV = 3.4V = 1.5% — leaving ample allowance for the final circuits beyond the garage board

Add a 32A EV charger to the same garage and the picture changes completely: 30.7 + 32 = 62.7A assessed, pushing the design to a 63A/80A submain in 16mm² or 25mm² SWA — which is why the future-proofing conversation belongs at the start of the job, not after the trench is backfilled.

The SWA Submain

The submain itself is almost always buried SWA. The full sizing detail lives on the SWA cable size calculator page; the submain-specific points:

  • Size for voltage drop first — the submain should use only part of the 5% total allowance, because the garage's final circuits add their own drop after the garage board. Keeping the submain under about 2% is a sound working habit.
  • Burial requirements — BS 7671 requires buried cables to incorporate an earthed armour or metal sheath (or equivalent duct protection), marked with cable covers or marker tape, at a depth sufficient to avoid foreseeable disturbance. Accepted practice is around 450mm in gardens, 600mm under drives.
  • Duct it if you can — a duct with a draw cord turns the future EV-charger upgrade into a cable pull instead of a second trench.
  • Protect it properly at the origin — the submain device in the house board protects the cable; check disconnection times over the full run with the disconnection time calculator.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

The Garage Consumer Unit and the Earthing Decision

At the garage end, a small consumer unit distributes to the final circuits. Design points:

  • Main switch and ways — a compact two-to-six-way board covers most garages: sockets, lighting, heating, and a spare way or two for the future.
  • RCD protection — socket outlets up to 32A require 30mA RCD additional protection (Regulation 411.3.3). RCBOs per circuit avoid a workshop freezer defrosting because a power tool tripped a shared RCD.
  • Discrimination with the house board — think about what trips first: RCD protection at the garage board serving the garage circuits, with the submain arranged so a garage fault does not take out house circuits.
  • The earthing arrangement — either export the house earthing system to the garage via the submain, or create a TT island with a local earth electrode at the outbuilding. On PME supplies, the decision needs particular care where the garage has outdoor equipment, water, or an EV charger — assess, decide deliberately, and record it on the certificate.

The whole-house picture matters too: the garage's assessed demand lands on the house supply, so check it against the installation's maximum demand before finalising the design.

Future-Proofing: The EV Charger Question

The single most common regret on garage supplies installed in the last decade is sizing them before EV charging arrived. A 7.4kW charger adds a continuous 32A — usually more than the entire rest of the garage — and it cannot share capacity by diversity, because it genuinely draws full current for hours.

Practical future-proofing, in ascending order of cost:

  • Duct the route — even if today's cable is modest, a duct makes the upgrade a pull-through.
  • Oversize the submain cable — the labour of the trench dwarfs the cost difference between 10mm² and 16mm² SWA. Install the bigger cable now.
  • Design the submain for the charger — a 63A submain feeding a garage board with a 32A EV way and the general circuits, with load management if the house supply is tight. The EV charger load calculator covers the supply-capacity side, and the EV charger cable size calculator the circuit itself.

Have the conversation with the customer before quoting — "will this garage ever charge a car?" is a one-line question that changes the whole design.

How to Design a Garage Supply

Five steps from load list to a certified outbuilding submain.

1

List the garage loads

Sockets, lighting, heating, machinery, and any planned EV charger. Use realistic simultaneous figures for socket circuits, full rating for fixed heating, and 100% for EV charging.

2

Apply diversity and assess the demand

The calculator applies diversity by load type and produces the assessed demand with a recommended main device rating — the number the submain is designed around.

3

Size the SWA submain

Size for voltage drop first over the actual trench run (keep the submain portion around 2%), then confirm current-carrying capacity for the burial method.

4

Specify the garage consumer unit

A small board with RCBO-protected final circuits, sized with a spare way or two. Decide the earthing arrangement — exported earth or local TT — deliberately.

5

Check the house end and certify

Confirm the house maximum demand can take the garage, verify disconnection times over the submain, then test and certify the installation.

Garage Supply Calculator Features

From load list to submain spec, with the EV question answered up front.

Multi-Load Diversity Assessment

Add each garage load by type and get a realistic assessed demand with the diversity applied automatically.

Main Device Recommendation

The calculator recommends the submain protective device rating from the assessed demand.

Submain Sizing Workflow

Carry the assessed demand into the SWA and cable sizing calculators for the trench run design.

EV-Ready Planning

Model the garage with and without a 32A charger to see how the submain requirement changes.

Voltage Drop Allocation

Check the submain leaves allowance within the 5% limit for the garage final circuits.

70+ Calculators in One App

Diversity, maximum demand, cable sizing, adiabatic, and Zs — the complete outbuilding design chain.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design garage supplies with confidence

Join 1,000+ UK electricians using Elec-Mate for load assessment, submain sizing, and certification. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

Cookie Preferences

Manage your privacy settings

We use cookies to enhance your experience and analyse platform usage. Cookie Policy