kVA Calculator

Transformer Sizing Calculator — Get the Right kVA Rating Every Time

Enter the connected load, power factor, and diversity. The calculator determines the correct transformer kVA rating for single-phase or three-phase installations, applies standard oversize factors, and selects from standard transformer ratings. No more undersized or oversized transformers.

kVA RatingLoad CalculationSingle & Three PhaseOversize Factor

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Transformer Calculator

Comprehensive transformer calculations with BS 7671 18th Edition compliance

V
V

Load power factor (0.1–1.0)

Transformer impedance at rated voltage

Transformer Calculations
Is = (kVA × 1000) / (√3 × Vs)
Is= Secondary current (A)
kVA= Transformer rating
Vs= Secondary voltage (V)
Z%= Impedance percentage
Isc= Prospective fault current (A)

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Transformer kVA rating is calculated as: kVA = Total Load (kW) / Power Factor for single-phase, or kVA = Total Load (kW) / Power Factor for three-phase — the formula is the same, but the load calculation differs.
  • 2Diversity factors reduce the calculated maximum demand to reflect the fact that not all loads operate simultaneously — typically reducing the required transformer size by 20-40%.
  • 3An oversize factor of 20-25% is commonly applied to allow for future load growth, motor starting currents, and non-linear load harmonics.
  • 4Standard transformer ratings (kVA) follow a preferred range: 25, 50, 100, 200, 315, 500, 750, 1000, 1500, 2000 — always select the next standard size above the calculated requirement.
  • 5Elec-Mate calculates transformer sizing instantly on your phone, with built-in diversity tables and standard rating selection.

What Is Transformer Sizing?

Transformer sizing is the process of selecting a transformer with the correct kilovolt-ampere (kVA) rating to supply an electrical installation. The transformer must be large enough to supply the maximum demand of the connected loads without overheating or exceeding its rated capacity, but not so oversized that it operates inefficiently at a fraction of its rating.

In the UK, transformers are used in a wide range of applications. Distribution transformers step down the 11kV or 33kV supply to 400V three-phase for commercial and industrial premises. Isolation transformers provide separated supplies for special locations under BS 7671. Control transformers provide reduced voltages for building management systems, lighting controls, and industrial control circuits.

Selecting the correct transformer size requires calculating the total connected load, applying diversity factors, accounting for power factor, and adding an appropriate oversize allowance for future growth and transient loads. An undersized transformer will overheat, trip on overload, or fail prematurely. An oversized transformer wastes capital and operates less efficiently due to higher iron losses at light load.

Single-Phase Transformer Sizing

For single-phase transformers, the kVA rating is calculated from the total load in kilowatts and the power factor of the load:

kVA = kW / Power Factor

kW = total diversified load in kilowatts

Power Factor = overall power factor of the load (typically 0.8 to 0.95)

The current drawn from a single-phase transformer is:

I = kVA x 1000 / V

I = current in amperes

V = secondary voltage (typically 230V or 110V)

For example, a single-phase load of 15kW at a power factor of 0.85 requires a transformer rated at: 15 / 0.85 = 17.6 kVA. The next standard rating above this is 25 kVA.

Three-Phase Transformer Sizing

For three-phase transformers, the kVA rating calculation uses the same fundamental relationship between real power and apparent power:

kVA = kW / Power Factor

The line current drawn from a three-phase transformer is:

I = kVA x 1000 / (root 3 x VL)

I = line current in amperes

VL = line-to-line voltage (typically 400V)

For a three-phase load of 80kW at a power factor of 0.9, the required transformer rating is: 80 / 0.9 = 88.9 kVA. The next standard rating is 100 kVA. The line current on the secondary side would be: 100,000 / (1.732 x 400) = 144.3A. This determines the cable size and switchgear ratings needed on the secondary side.

When sizing three-phase transformers, it is important to consider the phase balance. If the load is significantly unbalanced, the transformer must be sized for the highest loaded phase, not the average. Use the three-phase power calculator to assess phase balance before sizing the transformer.

Diversity and Oversize Factor

The connected load of an installation is rarely the same as the maximum demand. Diversity factors account for the fact that not all loads operate simultaneously. After applying diversity, an oversize factor is added to allow for future load growth and transient conditions.

Diversity Considerations

  • Lighting loads — typically 90% diversity for commercial buildings (not all areas are illuminated simultaneously).
  • Socket outlet loads — typically 40-60% diversity depending on the number of outlets and building use.
  • Motor loads — the largest motor is taken at 100%, with remaining motors at 80% or as determined by the process requirements.
  • Heating/cooling loads — typically 100% for the dominant system (heating or cooling, not both simultaneously).

Oversize Factors

  • 20% oversize — standard allowance for future load growth and normal operational headroom.
  • 25% oversize — recommended where significant motor loads exist (motor starting currents can be 6-8 times full load current).
  • 30% or more — for installations with high harmonic content (VFDs, UPS systems, LED drivers) where the transformer must handle additional heating from harmonic currents.

The Elec-Mate diversity factor calculator can help determine the diversified maximum demand before feeding the result into the transformer sizing calculation.

Transformer sizing with built-in diversity

Elec-Mate's transformer sizing calculator includes IET diversity tables and standard oversize factors. Enter your load breakdown and get the correct kVA rating in seconds. Works offline on site.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play

Standard Transformer Ratings (kVA)

Transformers are manufactured in standard kVA ratings. After calculating the required kVA, you must select the next standard rating above the calculated value. The standard ratings for oil-filled distribution transformers commonly available in the UK are:

25kVA
50kVA
100kVA
160kVA
200kVA
250kVA
315kVA
400kVA
500kVA
630kVA
750kVA
800kVA
1000kVA
1250kVA
1500kVA
2000kVA

Dry-type transformers (cast resin) are available in similar ratings and are used where oil-filled transformers are not permitted — for example, inside buildings, in basements, or in areas where fire risk from transformer oil is unacceptable. Dry-type transformers are typically more expensive but require less maintenance and have no oil leakage risk.

For site supply transformers (110V centre-tapped earth for construction sites), common ratings are 3 kVA, 5 kVA, 10 kVA, and 15 kVA single-phase, and 10 kVA, 15 kVA, and 25 kVA three-phase.

Worked Examples

Example 1: Small Commercial Unit

A small office building has the following connected loads: lighting 12kW, socket outlets 25kW, air conditioning 15kW, server room 8kW. Overall power factor is 0.85.

Total connected load = 12 + 25 + 15 + 8 = 60kW

After diversity (estimated 0.7): 60 x 0.7 = 42kW

kVA = 42 / 0.85 = 49.4 kVA

With 20% oversize: 49.4 x 1.2 = 59.3 kVA

Select the next standard rating: 100 kVA (or 63 kVA if available from the manufacturer).

Example 2: Industrial Workshop

An industrial unit has: lighting 8kW, socket outlets 15kW, three-phase motors totalling 75kW (largest motor 30kW), heating 20kW. Overall power factor is 0.8.

Motor diversity: largest at 100% (30kW) + remainder at 80% (45 x 0.8 = 36kW) = 66kW

Other loads after diversity: (8 + 15 + 20) x 0.8 = 34.4kW

Total diversified load = 66 + 34.4 = 100.4kW

kVA = 100.4 / 0.8 = 125.5 kVA

With 25% oversize (motors): 125.5 x 1.25 = 156.9 kVA

Select the next standard rating: 200 kVA.

How to Size a Transformer

Follow these six steps to calculate the correct transformer kVA rating for any installation. The Elec-Mate calculator performs steps 2-6 automatically once you enter the load breakdown.

1

List all connected loads

Identify every electrical load that will be supplied by the transformer. Group them by type — lighting, socket outlets, motors, heating/cooling, specialist equipment. Record the rated power in kW for each load.

2

Apply diversity factors

Apply appropriate diversity factors to each load group to determine the maximum demand. Use IET On-Site Guide diversity tables or site-specific diversity based on the building usage pattern.

3

Determine the power factor

Estimate the overall power factor of the installation. Use 0.8 as a conservative default for mixed loads. For predominantly motor loads, use 0.75-0.85. For predominantly resistive loads, use 0.95-1.0.

4

Calculate the kVA requirement

Divide the total diversified load (kW) by the power factor to get the required kVA. This gives the apparent power that the transformer must be rated to deliver.

5

Apply the oversize factor

Add an oversize factor — typically 20% for general loads, 25% where significant motor loads exist, or 30% for installations with high harmonic content from VFDs and non-linear loads.

6

Select the standard transformer rating

Choose the next standard transformer kVA rating above the calculated requirement. Verify the secondary current is compatible with the available switchgear and cable sizes.

Transformer Sizing Calculator Features

Everything you need to size transformers correctly on site, with no internet connection required.

Instant kVA Calculation

Enter connected loads by type and the calculator applies diversity, power factor, and oversize to determine the correct transformer kVA rating.

Single-Phase and Three-Phase

Handles both single-phase and three-phase transformer sizing with the correct formulas and standard rating tables for each configuration.

Built-In Diversity Tables

IET On-Site Guide diversity factors are built in. Select the building type and the calculator applies the correct diversity to each load group…

Load Breakdown Display

Visual breakdown showing how each load group contributes to the total demand. Instantly see which loads are driving the transformer size.

Adjustable Oversize Factor

Set the oversize factor from 10% to 50% based on the installation requirements. The calculator recommends a default based on the load mix.

Standard Rating Selection

Automatically selects the next standard transformer kVA rating above the calculated requirement. Shows the full load secondary current for cable sizing.

Frequently Asked Questions About Transformer Sizing

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size Transformers in Seconds on Your Phone

Join 1,000+ UK electricians using Elec-Mate for on-site calculations. 70+ calculators, 16 certificate types, and AI tools. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy