INSTALLATION GUIDE

Three Phase Installation: The Complete BS 7671 Guide

Three phase supplies are essential for commercial premises, industrial sites, and increasingly for domestic properties with high electrical demand. This guide covers everything from load balancing and TPN board selection to cable sizing, testing, and certification — all referenced to BS 7671:2018+A2:2022.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Three phase supplies are required when single phase cannot deliver enough power — typically above 100A or where large motors, commercial kitchens, or EV charging banks are installed.
  • 2Load balancing across all three phases is critical: an imbalance greater than 10-15% causes neutral overloading, voltage fluctuations, and potential overheating of the neutral conductor.
  • 3TPN (Triple Pole and Neutral) distribution boards must be selected carefully — BS 7671 requires correct discrimination, RCD protection, and labelling of all circuits by phase.
  • 4Cable sizing for three phase circuits uses the same BS 7671 correction factors as single phase but the current per phase is lower for the same total power, often allowing smaller conductor sizes.
  • 5Elec-Mate's cable sizing calculator handles three phase calculations instantly, applying grouping, ambient temperature, and thermal insulation correction factors per BS 7671 Appendix 4.
01 · Installation Guide

What Is a Three Phase Electrical Supply?

A three phase electrical supply uses three live conductors — designated L1, L2, and L3 — each carrying an alternating current at 50Hz but offset from each other by 120 degrees. This arrangement delivers significantly more power than a single phase supply for the same conductor size and current rating.

The voltage between any two phases (line-to-line voltage) is 400V. The voltage between any single phase and the neutral conductor (line-to-neutral voltage) is 230V. The relationship between these voltages is governed by the square root of 3 (approximately 1.732): 400V / 1.732 = 230V.

In the UK, the Distribution Network Operator (DNO) provides three phase supplies as standard to commercial and industrial premises. Domestic properties typically receive a single phase supply, but three phase can be requested where the maximum demand justifies it — for example, properties with multiple EV chargers, heat pumps, or high-power electric cooking appliances.

Three phase power is calculated as P = sqrt(3) x V_line x I_line x power factor. For a balanced load drawing 100A per phase at unity power factor, the total power is 1.732 x 400 x 100 = 69.3kW — compared with 23kW from a single phase 100A supply.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Installation Guide

When Is a Three Phase Supply Needed?

The decision to install a three phase supply depends on the total electrical demand of the premises. A single phase supply in the UK is typically rated at 60A or 100A (depending on the service fuse), providing a maximum of approximately 14kW to 23kW. When the calculated maximum demand exceeds this, three phase becomes necessary.

  • Commercial kitchens — multiple three phase ovens, induction hobs, and high-power dishwashers can demand 50kW or more.
  • Industrial motors — motors above 3kW are almost always three phase. They run more efficiently and produce smoother torque than single phase equivalents.
  • Multiple EV chargers — a bank of 7kW or 22kW EV chargers for a car park or multi-dwelling development requires three phase to distribute the load.
  • Large domestic properties — homes with underfloor heating, heat pumps, EV charging, electric cooking, and hot tubs can exceed single phase capacity.
  • New build developments — the 2022 Building Regulations requiring EV charge points and the increasing adoption of heat pumps are pushing more new builds towards three phase supplies.

To determine whether three phase is needed, calculate the maximum demand using diversity factors from BS 7671 and the IET On-Site Guide. If the total demand after diversity exceeds the single phase supply capacity, three phase is required. Elec-Mate's max demand calculator applies the correct diversity factors automatically and tells you whether single or three phase is appropriate.

03 · Installation Guide

Balancing Loads Across All Three Phases

Load balancing is one of the most important aspects of three phase installation design. In a perfectly balanced system, each phase carries the same current and the neutral conductor carries zero current. In practice, perfect balance is rarely achieved, but the goal is to get as close as possible.

An unbalanced three phase system causes current to flow in the neutral conductor. The greater the imbalance, the higher the neutral current. In extreme cases, the neutral current can exceed the phase current, which risks overheating the neutral conductor — particularly dangerous in older installations where the neutral may be undersized relative to the phase conductors.

Practical Load Balancing Strategy

  • List every circuit with its design current and allocate them across L1, L2, and L3.
  • Place large single phase loads (cookers, showers, EV chargers) on different phases.
  • Distribute lighting circuits, socket circuits, and small power evenly across all three phases.
  • Consider the diversity of each circuit — a socket circuit on a phase with a large motor will balance better than two large fixed loads on the same phase.
  • Aim for no more than 10-15% difference in current between the most heavily loaded and least heavily loaded phase.

Elec-Mate's AI circuit designer can assist with phase allocation by analysing the connected load on each phase and suggesting redistribution to minimise imbalance. This is particularly useful on complex commercial installations with dozens of circuits.

Design balanced three phase boards with AI

Elec-Mate's AI circuit designer analyses your load schedule, allocates circuits across phases for optimal balance, and sizes cables automatically.

Try it free for 7 days
Download on the App StoreGet it on Google Play
04 · Installation Guide

TPN Distribution Boards: Selection and Wiring

A TPN (Triple Pole and Neutral) distribution board is the heart of a three phase installation. Unlike a single phase consumer unit with one busbar, a TPN board has three phase busbars (L1, L2, L3) and a neutral bar. Each outgoing way can be connected to any one phase (for single phase circuits) or across all three phases (for three phase loads).

When selecting a TPN distribution board, consider the following requirements under BS 7671:

  • Main switch rating — the main switch (or main isolator) must be rated for the maximum demand of the installation. For a 100A per phase supply, a 100A 4-pole isolator is standard. For larger installations, 125A, 200A, or 400A switches may be required.
  • Number of ways — count every circuit (including spares) and select a board with sufficient ways. TPN boards typically come in 12, 18, 24, or 36 way configurations. Allow at least 20% spare ways for future expansion.
  • RCD arrangement — decide between a split-load board (with one or more RCDs protecting groups of circuits) or individual RCBOs on every circuit. RCBOs provide the best discrimination — a fault on one circuit does not trip other circuits.
  • SPD (Surge Protection Device) — BS 7671 Regulation 443.4.1 requires an SPD where the consequence of a transient overvoltage could result in (a) serious injury to, or loss of, human life, or (c) significant financial or data loss (limb (b) was deleted by the A2:2022 Corrigendum of May 2023). For all other cases, an SPD must be provided unless the owner of the installation declares it is not required because any loss or damage is tolerable and they accept the risk. In practice, most new three phase installations should include a Type 2 SPD as a minimum.

Labelling is essential on TPN boards. Every circuit must be clearly labelled with its function, phase allocation, and protective device rating. The circuit chart must show which phase each circuit is connected to. Under BS 7671 Regulation 514.9, the circuit chart must be fixed inside or adjacent to the distribution board and kept up to date.

05 · Installation Guide

Cable Sizing for Three Phase Circuits

Cable sizing for three phase circuits follows the same principles as single phase — you must ensure the cable can carry the design current (Ib), withstand the prospective fault current, and keep the voltage drop within BS 7671 limits. The key difference is that the current per phase is lower for a given total power, because the power is shared across three conductors.

For a balanced three phase load, the current per phase is calculated as: I = P / (sqrt(3) x V_line x pf), where P is the total power in watts, V_line is 400V, and pf is the power factor. For example, a 30kW balanced load at unity power factor draws 30,000 / (1.732 x 400 x 1.0) = 43.3A per phase.

The cable sizing process then applies the standard correction factors from BS 7671 Appendix 4:

  • Ca (ambient temperature) — derate the cable if the ambient temperature exceeds 30 degrees C (the reference temperature for most cable types).
  • Cg (grouping) — derate the cable if it is grouped with other cables. Three phase cables running together count as one circuit for grouping purposes, but multiple three phase circuits in the same trunking or tray must be derated.
  • Ci (thermal insulation) — derate the cable if it passes through or is in contact with thermal insulation.
  • Voltage drop — BS 7671 limits voltage drop to 3% for lighting circuits and 5% for other circuits (from the origin to the load). For three phase, use the three phase mV/A/m values from the voltage drop tables.

Size three phase cables in seconds

Elec-Mate's cable sizing calculator handles single and three phase circuits. Enter the load, cable type, installation method…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Installation Guide

Testing a Three Phase Installation

Testing a three phase installation requires the same sequence of tests as single phase, but with additional measurements between phases. The testing sequence under BS 7671 Chapter 64 and GN3 is:

  1. Continuity of protective conductors — test R1+R2 for every circuit on every phase. For three phase circuits, test each phase conductor to the CPC.
  2. Continuity of ring final circuits — if there are ring circuits on any phase, perform the standard figure-of-eight test for each ring.
  3. Insulation resistance — test at 500V DC between all live conductors and earth (L1-E, L2-E, L3-E, N-E) and between live conductors (L1-L2, L2-L3, L1-L3, L1-N, L2-N, L3-N). Each reading must be at least 1 megohm. Disconnect sensitive electronic equipment before testing.
  4. Polarity — verify correct polarity on all single phase circuits and correct phase rotation on three phase circuits. Use a phase rotation meter.
  5. Earth fault loop impedance (Zs) — measure Zs at the furthest point of each circuit. For three phase circuits, measure Zs for each phase.
  6. Prospective fault current (PSCC) — measure at the origin between each phase and neutral, and between phases. The highest value determines the required breaking capacity of the protective devices.
  7. RCD operation — test every RCD at rated residual current (30mA for most domestic/commercial RCDs). Test at 1x and 5x rated current. Verify trip time is within BS 7671 limits (300ms at 1x, 40ms at 5x for Type AC/A).

Phase rotation is particularly important for three phase motor installations. Incorrect phase rotation causes motors to run in reverse, which can damage driven equipment. Always verify phase rotation at the distribution board and at the motor terminals before energising.

Record all test results on the Schedule of Test Results form. Elec-Mate's EIC certificate app includes the full schedule of test results and supports three phase circuit entries with per-phase readings.

07 · Installation Guide

Earthing and Bonding for Three Phase Installations

Earthing and bonding requirements for three phase installations follow the same BS 7671 regulations as single phase, but the conductor sizes are often larger due to the higher fault currents associated with three phase supplies.

The main earthing conductor size is determined by BS 7671 Table 54.7 based on the largest phase conductor size. For a 100A three phase supply with 25mm2 phase conductors, the main earthing conductor must be at least 16mm2 (copper). The main protective bonding conductors must be at least half the size of the main earthing conductor, with a minimum of 6mm2 for supplies up to 35mm2 phase conductors and 10mm2 for larger supplies.

  • Main earthing terminal — must be accessible for inspection and testing. Label it clearly.
  • Protective bonding — bond to incoming gas, water, oil, and any other extraneous-conductive-parts within 600mm of the point of entry to the building.
  • Earth electrode — for TT earthing arrangements, the earth electrode resistance must be low enough to ensure the disconnection time is met. For three phase TT installations, this often means multiple electrodes or a ring electrode.

For detailed guidance on earthing arrangements including TN-S, TN-C-S, and TT systems, see our dedicated guide.

08 · Installation Guide

Certification for Three Phase Installations

Every new three phase installation requires an Electrical Installation Certificate (EIC) under BS 7671 Part 6. The EIC must include the full schedule of test results for every circuit on every phase, the schedule of items inspected, and the designer, installer, and inspector declarations.

For three phase installations, the EIC must record:

  • The supply type (three phase, four wire), voltage (400/230V), and earthing arrangement (TN-S, TN-C-S, or TT).
  • The prospective fault current at the origin — measured between phases and between each phase and neutral.
  • The external earth fault loop impedance (Ze) for each phase.
  • Test results for every circuit, showing which phase each circuit is connected to.

If the three phase installation is notifiable under Part P of the Building Regulations (for example, a new installation in a dwelling or the installation of a new consumer unit), the work must be either carried out by a registered competent person who can self-certify, or notified to Building Control before work starts.

Frequently Asked Questions About Three Phase Installation

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Size Cables and Design Boards Faster

Elec-Mate's cable sizing calculator, voltage drop calculator, and AI circuit designer handle three phase calculations instantly. Join 1,000+ UK electricians. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy