The maximum acceptable earth electrode resistance depends on the type of protective device and its rated residual operating current. The fundamental condition for TT systems comes from BS 7671 Regulation 411.5.3:
RA x IΔn ≤ 50 V
Where RA is the sum of the resistances of the earth electrode and the protective conductor connecting it to the exposed-conductive-parts (in ohms), and IΔn is the rated residual operating current of the RCD (in amps). 50 V is the touch voltage limit for normal dry conditions. Regulation 411.5.3 also confirms the requirement is met where the earth fault loop impedance meets Table 41.5.
Maximum Earth Fault Loop Impedance (Zs) by RCD Rating
BS 7671 Table 41.5 — non-delayed and time-delayed ‘S’ type RCDs to BS EN 61008-1 / 61009-1, U0 = 230 V. Disconnection within the times of Table 41.1.
RCD rating (IΔn)
Max Zs (ohms)
RA = 50 / IΔn
30 mA
1667*
1667 Ω
100 mA
500*
500 Ω
300 mA
167
167 Ω
500 mA
100
100 Ω
* Note 2 to Table 41.5: the resistance of the installation earth electrode should be as low as practicable — a value exceeding 200 Ω may not be stable (see Regulation 542.2.4). So although the arithmetic limit for a 30 mA RCD is 1667 Ω, the practical target is far lower.
While the tabulated maximums look generous (especially for 30 mA RCDs), there are good reasons to aim much lower. An earth electrode with RA comfortably below 200 ohms provides a margin of safety and keeps the reading stable across the seasons. Electrodes in the range of 20 to 100 ohms are common in clay and loam soils; sandy, rocky, or chalk soils may produce higher values that need longer electrodes or multiple rods in parallel. Regulation 542.2.4 also requires the type and embedded depth of the electrode to be chosen so that soil drying and freezing will not raise its resistance above the required value.
Clay & loam
Lowest and most stable resistivity. A single 1.2 m rod will often read well within limits and hold its value through dry spells.
Sandy & gravelly
Higher resistivity and drains quickly, so readings swing with the weather. Expect to need a longer rod or two rods in parallel.
Chalk & rock
Highest resistivity and hardest to drive into. Multiple electrodes, deep driving, or an earth mat with conductive backfill may be required.
Parallel rods
Space rods at least twice their driven length apart — closer than that and the resistance zones overlap, so the second rod adds little benefit.
Use the earth loop impedance calculator in Elec-Mate to check whether your measured RA value meets the disconnection time requirements for each circuit.