BS 7671 APPENDIX 4

BS 7671 Appendix 4 Tables Current Carrying Capacity

The complete guide to BS 7671 Appendix 4. Find the right table from Table 4A3 — 4D1A for single-core PVC, 4D2A for multicore PVC, 4D5 for flat twin and earth, the 4E series for 90°C thermosetting — then choose the right reference method column, apply correction factors, and check voltage drop, all to BS 7671:2018+A4:2026.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-08-06Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is BS 7671 Appendix 4?

Appendix 4 of BS 7671 contains the current-carrying capacity tables for every cable type and installation method — the core reference for all cable sizing. Table 4A3 indexes each construction to its table: 4D1A is single-core 70°C PVC, 4D2A is multicore 70°C PVC, 4D5 is flat twin and earth, and the 4E series covers 90°C thermosetting. You then read the column for your reference method. Voltage drop (mV/A/m values and the 3%/5% limits) sits in Appendix 4, Section 6.4, unchanged by Amendment 4 (A4:2026).

Use the correct table for your cable type and the correct column for your reference method — getting either wrong gives the wrong current-carrying capacity.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Appendix 4 contains the current-carrying capacity tables for every cable type and installation method in BS 7671 — it is the core reference for all cable sizing calculations.
  2. 02Tables are numbered systematically, and Table 4A3 of Appendix 4 is the index: the letter group gives conductor material and insulation (4D = 70°C thermoplastic copper, 4E = 90°C thermosetting copper, 4F = flexible, 4G = mineral insulated, 4H and 4J = aluminium), the number gives the construction, the A/B suffix separates current-carrying capacity (A) from voltage drop (B), and the column you read gives the reference method.
  3. 03Voltage drop (mV/A/m values and the 3% lighting / 5% other limits) lives in Appendix 4, Section 6.4 of BS 7671:2018+A4:2026 — the same place as the current-carrying capacity tables. Amendment 4 did not move it.
  4. 04You must use the correct table for your cable type AND the correct column for your reference method — getting either wrong gives the wrong current-carrying capacity.
  5. 05When sizing cables for underground or buried runs, apply the Cs (soil thermal resistivity) factor from Table 4B3 and the Cd (depth of laying) factor from Table 4B4, in addition to Ca (ambient), Cg (grouping) and Ci (thermal insulation). Appendix 4, Section 5.1.1 also applies Cc = 0.9 where the cable is buried direct or run in a duct in the ground.
  6. 06Elec-Mate has every Appendix 4 table built into the cable sizing calculator. Select cable type and reference method, and the app looks up the correct value instantly — no more flicking through the brown book.

01 · BS 7671 Appendix 4

What Is Appendix 4?

Looking for Amendment 4 (the A4:2026 update to BS 7671) rather than Appendix 4 (the cable tables)? See the BS 7671 Amendment 4:2026 guide for every change and what it means for your work.

Appendix 4 of BS 7671 is the section that every electrician turns to most frequently. It contains the current-carrying capacity tables for all standard cable types used in UK electrical installations. When you are sizing a cable, Appendix 4 is where you look up the maximum current a cable can carry under specific installation conditions.

The tables cover every combination of cable type (PVC, XLPE, MICC, SWA, flexible), conductor material (copper, aluminium), conductor configuration (single-core, multicore), and installation method (Reference Methods A through G). The values in these tables are based on defined reference conditions: an ambient temperature of 30 degrees Celsius, a single circuit (no grouping), no thermal insulation in contact with the cable, and the cable operating at its maximum conductor temperature (70 degrees Celsius for PVC, 90 degrees Celsius for XLPE/LSF).

When the actual installation conditions differ from these references — as they almost always do — correction factors must be applied. Appendix 4 also contains the correction factor tables: Table 4B1 for ambient air temperature, Table 4B2 for ambient ground temperature, Table 4B3 for soil thermal resistivity (Cs), Table 4B4 for depth of laying (Cd), Table 4B5 for cables with more than four loaded cores, and Tables 4C1 to 4C6 for grouping (Cg).

In the app

BS 7671 Appendix 4 Tables: Cable Current Ratings & Volt Drop

BS 7671 Appendix 4 explained: current-carrying capacity, volt drop (mV/A/m) and correction factors (Ca, Cg, Ci) for every cable type and method.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Appendix 4

Understanding the Table Numbering System

The Appendix 4 table numbering follows a systematic pattern that, once understood, makes navigation much faster. The pattern is:

Table 4D2A  /  Table 4D2B

The suffix is what matters most day to day: A = current-carrying capacity (amps), B = voltage drop (mV/A/m). The letter group gives the insulation and conductor material, and the number gives the construction — so 4D2A and 4D2B are the capacity and volt-drop tables for the same cable.

The single most important point: you do not have to guess. Appendix 4 opens with Table 4A3, which lists every cable construction against the table that gives its current rating. Read the series letter as the insulation and conductor material — 4D is 70°C thermoplastic (PVC) with copper conductors, 4E is 90°C thermosetting (XLPE/LSF) with copper conductors — and the number as the construction within that series.

The tables you will actually use

  • Table 4D1A — single-core 70°C thermoplastic (PVC) cables, non-armoured, with or without sheath. This is the table for singles in conduit or trunking, not for twin and earth.
  • Table 4D2A — multicore 70°C thermoplastic insulated and sheathed cables, non-armoured.
  • Table 4D5 — 70°C thermoplastic insulated and sheathed flat cable with protective conductor. This is the twin and earth table, and it is the one the On-Site Guide sends you to for T&E in contact with thermal insulation.
  • Table 4D4A / 4E4A — multicore armoured (SWA): 4D4A for 70°C thermoplastic, 4E4A for 90°C thermosetting.
  • Table 4E series — 90°C thermosetting (XLPE/LSF) copper cables: 4E1A single-core, 4E2A multicore, 4E3A single-core armoured, 4E4A multicore armoured.
  • Table 4F — flexible cables and cords; 4G — mineral insulated (MICC); 4H / 4J — aluminium conductors (70°C and 90°C thermoplastic respectively).

03 · BS 7671 Appendix 4

Current-Carrying Capacity: Which Table, and Which Column

This is what most electricians come to Appendix 4 for: the current-carrying capacity (Iz) of a cable. Before you read a number, fix two things — the table (from Table 4A3, by construction and insulation) and the column (your reference method). For flat twin and earth the table is Table 4D5; for 90°C thermosetting multicore it is Table 4E2A. The indicative figures below are for two loaded conductors clipped direct at the standard reference conditions — 30°C ambient, single circuit, no grouping and no thermal insulation. Always read the actual value off the printed table for your exact construction and reference method, then apply correction factors for any condition that differs.

Indicative Iz (A) — clipped direct, two loaded conductors

70°C thermoplastic (PVC) vs 90°C thermosetting (XLPE/LSF), same conductor size. Confirm against the printed table for your construction.

Conductor
70°C PVC
90°C XLPE
1.0mm²
13
16
1.5mm²
16
20
2.5mm²
24
30
4.0mm²
32
40
6.0mm²
41
51
10mm²
57
70
16mm²
76
94
25mm²
101
125
35mm²
125
156
50mm²
151
188

Indicative only — read the tabulated figure from BS 7671:2018+A4:2026 Appendix 4 for your construction (Table 4A3 tells you which table) and your reference method. Iz is the tabulated capacity before correction factors — always compare against the required It once Ca, Cg, Ci and Cf are applied.

The 90°C thermosetting column is consistently higher than the 70°C PVC column for the same conductor size, because the 90°C insulation tolerates more heat. For any installation method other than clipped direct, the capacity changes — read the correct column for your reference method.

In the app

Every Appendix 4 table built in

Skip the lookup — Elec-Mate's cable sizing calculator reads off the right table and column, applies correction factors and checks volt drop in one go.

04 · BS 7671 Appendix 4

Which Reference Method (Installation Method)?

A cable's current-carrying capacity depends as much on how it is installed as on its size — the same 2.5mm² T&E carries very different currents clipped to a wall versus buried in loft insulation. BS 7671 calls the installation arrangement the reference method, and it sets which column of the Appendix 4 table you read.

Regulation 521.1 of BS 7671:2018+A4:2026 requires the installation method of a wiring system, in relation to the type of conductor or cable used, to be in accordance with Table 4A1 of Appendix 4, provided external influences are taken into account under Section 522. Regulation 521.2 then requires the installation method in relation to the situation to be in accordance with Table 4A2, which is where each numbered installation method is illustrated and mapped to its reference method. The two methods you will meet most often are:

Method C — clipped direct

Cable clipped direct to a wooden or masonry wall or ceiling — Installation Method 20 of Table 4A2 is the worked example given in Appendix 4. This is the column used for the clipped-direct figures in the table above.

Methods D1 and D2 — buried in the ground

Amendment 4 split these out: Reference Method D1 is a cable in a conduit or duct in the ground, and Reference Method D2 is a cable buried in direct contact with soil. Distinct current-carrying capacities now apply to each, and Tables 4A2, 4D4A, 4E4A, 4H4A and 4J4A were revised for A4:2026 to reflect it — so check you are reading an A4:2026 copy. Buried cables also need the Cs (soil thermal resistivity) factor from Table 4B3 and the Cd (depth of laying) factor from Table 4B4 in addition to Ca and Cg, plus Cc = 0.9 under Appendix 4, Section 5.1.1.

Methods A, B, E, F and G cover conduit in a thermally insulating wall, conduit or trunking on a surface, and cables in free air. The full A–G breakdown, with the Table 4A2 illustrations, is in our cable reference methods guide. Choosing the wrong method is one of the most common cable-sizing errors — a cable rated for clipping direct can be significantly overloaded once it is enclosed in insulation.

05 · BS 7671 Appendix 4

Thermoplastic (PVC) Cable Tables — The 4D Series

The 4D series of tables covers thermoplastic insulated cables — by far the most commonly used cable type in UK domestic and light commercial installations. PVC-insulated cables include twin and earth (flat profile cable with earth), singles for use in conduit and trunking, and PVC-insulated flexible cables.

PVC cables have a maximum conductor operating temperature of 70 degrees Celsius. All current-carrying capacity values in the 4D tables are calculated on the basis that the conductor does not exceed this temperature under sustained full-load conditions at an ambient temperature of 30 degrees Celsius.

Most commonly used PVC tables

  • Table 4D1A — single-core 70°C thermoplastic (PVC) cables, non-armoured, with or without sheath, copper conductors. The table for singles drawn into conduit or trunking.
  • Table 4D2A — multicore 70°C thermoplastic insulated and thermoplastic sheathed cables, non-armoured, copper conductors.
  • Table 4D3A / 4D4A — armoured 70°C thermoplastic cables: 4D3A single-core (non-magnetic armour), 4D4A multicore armoured.
  • Table 4D5 — 70°C thermoplastic insulated and sheathed flat cable with protective conductor: standard flat twin and earth. As well as the ordinary reference-method columns it carries Installation Methods 100 to 103 for cable above an insulated ceiling or in an insulated stud wall.

Whichever table you are in, the column you select depends on the reference method and on the number of loaded conductors — the two-loaded-conductor columns are the ones for single-phase circuits, the three- or four-loaded-conductor columns for three-phase. Read the column headings; do not count columns across from another table.

T+E in thermal insulation (stud walls, ceiling voids)

Where flat twin and earth cable is in contact with, or enclosed within, thermal insulation — for example in a stud wall containing insulation or above an insulated ceiling — the standard Method C ratings do not apply. In these circumstances, the installer must apply the derating factors and reduced current-carrying capacities set out in BS 7671 Appendix 4 Table 4D5 for the relevant contact/enclosure condition — Installation Methods 100 to 103 of Table 4A2, which the On-Site Guide section 13.5 also directs you to. Failure to derate for thermal insulation is one of the most common cable sizing errors in domestic work.

06 · BS 7671 Appendix 4

Thermosetting (XLPE/LSF) Cable Tables — The 4E Series

The 4E series covers thermosetting insulated cables with copper conductors — cables with XLPE (cross-linked polyethylene) or LSF (low smoke and fume) insulation. It mirrors the 4D series construction for construction: 4E1A single-core non-armoured, 4E2A multicore non-armoured, 4E3A single-core armoured, 4E4A multicore armoured (XLPE/SWA). Thermosetting cables have a higher maximum conductor operating temperature of 90 degrees Celsius, compared to 70 degrees Celsius for PVC. This 20-degree advantage translates directly into higher current-carrying capacity for the same conductor size.

Thermosetting cables are used in several common scenarios: where higher current capacity is needed without increasing cable size (reducing material cost and conduit fill), in locations where the fire performance of PVC is inadequate (escape routes, public buildings), and where ambient temperatures are elevated and PVC derating would be excessive.

Indicative capacity comparison: 70°C PVC vs 90°C XLPE, clipped direct

Size

mm²

PVC 70°C

4D series

XLPE 90°C

4E series

2.5

24

30

4.0

32

40

6.0

41

51

The capacity advantage of thermosetting over thermoplastic is meaningful for the same conductor size and installation method, so where PVC cable sizing leads to an impractically large cable, switching to a 90°C thermosetting cable of the same size may provide sufficient capacity without increasing the conductor cross-section. Two cautions. First, the gain is only usable if every terminal and accessory in the circuit is rated for the higher operating temperature: the introduction to Appendix 4 lists the limiting temperatures for the terminals of equipment (Section 526) as one of the considerations that affects conductor size. Second, Regulation 523.1 NOTE 3 expressly allows the 70°C tables (4D1 to 4D5) to be used for 90°C thermosetting cables where the rating is to be based on 70°C, which is often what you must do for that reason.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

07 · BS 7671 Appendix 4

Voltage Drop Tables (mV/A/m)

The voltage drop tables provide mV/A/m (millivolts per ampere per metre) values for each cable type and size. These values are used to calculate the voltage drop across a cable run using the formula:

VD = mV/A/m × Ib × L ÷ 1000

VD = voltage drop (volts) | Ib = design current (A) | L = cable length (m)

Where voltage drop sits in the standard

Voltage drop stays in Appendix 4. The mV/A/m values are listed in the cable tables, and the numeric limits are in Appendix 4, Section 6.4 — which Regulation 525.202 and 525.203 of BS 7671:2018+A4:2026 point to directly. This is unchanged by Amendment 4. There is no separate “Appendix 12” for voltage drop; if you have seen that claimed, it is incorrect.

BS 7671 Regulation 525 limits voltage drop to 3% for lighting circuits and 5% for all other circuits, measured from the origin of the installation. From a 230V single-phase supply, this gives maximum permissible voltage drops of 6.9V for lighting and 11.5V for power. From a 400V three-phase supply, the limits are 12V for lighting and 20V for power.

The voltage drop tables provide separate values for single-phase (two-core) and three-phase circuits. For three-phase calculations, the three-phase mV/A/m values are used, which account for the different phase relationships in a balanced three-phase system. The voltage drop for three-phase is calculated as: VD = mV/A/m (3-phase) x Ib x L / 1000.

In the app

Voltage drop calculated automatically

Elec-Mate's cable sizing calculator checks voltage drop as part of every cable sizing calculation.

08 · BS 7671 Appendix 4

Key Cable Types and Their Tables

Understanding which table to use for each cable type is essential for accurate cable sizing. Here are the most commonly encountered cable types and their corresponding Appendix 4 tables.

Twin and Earth (T&E)

The standard domestic cable. Flat profile with line, neutral, and CPC. Use Table 4D5 — “70°C thermoplastic insulated and sheathed flat cable with protective conductor”. That is the only table in Appendix 4 written specifically for flat T&E, and it is the one Table 4A3 and the On-Site Guide both point you to. Available in 1.0, 1.5, 2.5, 4.0, 6.0, 10, and 16mm². The most commonly used sizes are 1.5mm² for lighting, 2.5mm² for ring circuits, and 6mm² or 10mm² for cookers and showers.

Singles in Conduit

Single-core PVC-insulated cables drawn into conduit or trunking. Standard in commercial and industrial work. This is what Table 4D1A is for — single-core 70°C thermoplastic cables, non-armoured, with or without sheath. Pick the column for your reference method (Method A for conduit in a thermally insulating wall, Method B for conduit or trunking on a wall, and so on) and for the number of loaded conductors. The capacity is lower than the clipped-direct columns for the same conductor size because the conduit restricts airflow around the cables.

SWA (Steel Wire Armoured)

Multicore armoured cable with mechanical protection from the steel wire armouring. Pick the table by insulation: Table 4D4A for multicore armoured 70°C thermoplastic, and Table 4E4A for multicore armoured 90°C thermosetting — 4E4A is the one for the XLPE/SWA normally specified in the UK. Standard for underground burial, external runs, and submain distribution. When buried, apply the Cs soil thermal resistivity factor (Table 4B3) and the Cd depth factor (Table 4B4) as well as Ca and Cg, and use the correct buried reference method — D1 in a duct, D2 in direct contact with soil. The armouring also serves as the circuit protective conductor (CPC) in many installations.

Flexible Cables

Flexible cables for appliance connections and temporary installations. Use the 4F series tables — 4F1A for 60°C thermosetting insulated flexible cables, 4F2A for 90°C and 180°C thermosetting, and 4F3A for flexible cables generally (Regulation 559.5.2 points to 4F3A for flexible cord to luminaires). Flexible cables have different current-carrying capacities from fixed wiring cables because of their construction — finer conductor strands, different insulation thickness, and typically different ambient temperature assumptions.

09 · BS 7671 Appendix 4

How to Use the Tables Step by Step

Using the Appendix 4 tables correctly is the core skill of cable sizing. Here is the step-by-step process for looking up a current-carrying capacity value.

1

Identify the cable type

Determine whether you are using PVC (thermoplastic) or XLPE/LSF (thermosetting) cable, whether it is single-core or multicore, and whether it is armoured or non-armoured. Table 4A3 of Appendix 4 maps that description straight to the table letter (D, E, F, G, H, J) and number.

2

Identify the reference method

Assess the installation method — how the cable will be physically installed. This determines the column of the table you use. The column headers in each table indicate which reference method each column covers.

3

Calculate the required It

Apply all correction factors (Ca, Cg, Ci, Cf, and Cs for buried cables) to calculate the minimum tabulated current rating: It = In / (Ca × Cg × Ci × Cf). For underground installations, include Cs (soil thermal resistivity) in the denominator.

4

Select the cable

Find the row in the table where the current-carrying capacity (Iz) is equal to or greater than It. That row gives you the minimum cable size for the installation. Then verify voltage drop and fault current withstand.

In the app

Instant Appendix 4 lookup on site

Skip the manual table lookup. Elec-Mate's cable sizing calculator selects the correct table, applies correction factors…

10 · BS 7671 Appendix 4

Common Lookups Electricians Need

Here are the sizes most often needed for everyday domestic and light commercial work, with indicative capacities for a 90°C thermosetting cable clipped direct with two loaded conductors. Read the tabulated value from Appendix 4 for the cable you are actually using — Table 4D5 for 70°C flat twin and earth, the 4E series for 90°C thermosetting — and remember the protective device rating (In) must sit between the design current and the cable capacity: Ib ≤ In ≤ Iz, per Regulation 433.1.1.

Indicative Iz — 90°C thermosetting, clipped direct, 2 loaded conductors

Size
Iz (A)
Typical use
1.0mm²
16
Lighting
1.5mm²
20
Lighting
2.5mm²
30
Ring circuit
4.0mm²
40
Immersion
6.0mm²
51
Cooker/shower
10mm²
70
Large cooker
16mm²
94
Sub-main

Remember: tabulated values apply under reference conditions only. Once you apply correction factors, the effective capacity of the cable is reduced — a cable grouped with others and in contact with insulation can lose a third of its tabulated capacity or more. Always calculate the required It before selecting from the table.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Every Appendix 4 table, always in your pocket

Join 1,000+ UK electricians using Elec-Mate for instant cable sizing with every BS 7671 table built in. 70+ calculators, 16 certificate types — all BS 7671:2018+A4:2026. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy