BS 7671 Appendix 4 Tables Current Carrying Capacity
The complete guide to BS 7671 Appendix 4, with the full current-carrying capacity tables on the page. Read off Table 4D1A (PVC) and Table 4D5A (XLPE) for every conductor size, choose the right reference method (A–G), apply correction factors, and check voltage drop — all to BS 7671:2018+A4:2026.
Appendix 4 of BS 7671 contains the current-carrying capacity tables for every cable type and installation method — the core reference for all cable sizing. Tables are named by cable type (e.g. Table 4D1A for 70°C PVC twin and earth, 4D5A for 90°C XLPE) and a reference-method column (A, B, C…). Voltage drop (mV/A/m values and the 3%/5% limits) sits in Appendix 4, Section 6.4, unchanged by Amendment 4 (A4:2026).
Use the correct table for your cable type and the correct column for your reference method — getting either wrong gives the wrong current-carrying capacity.
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Appendix 4 contains the current-carrying capacity tables for every cable type and installation method in BS 7671 — it is the core reference for all cable sizing calculations.
2Tables are numbered systematically: the letter indicates cable type (D for multicore thermoplastic, E for multicore thermosetting), and the column indicates the reference method (A, B, C, etc.).
3Voltage drop (mV/A/m values and the 3% lighting / 5% other limits) lives in Appendix 4, Section 6.4 of BS 7671:2018+A4:2026 — the same place as the current-carrying capacity tables. Amendment 4 did not move it.
4You must use the correct table for your cable type AND the correct column for your reference method — getting either wrong gives the wrong current-carrying capacity.
5When sizing cables for underground or buried runs, apply the Cs (soil thermal resistivity) correction factor in addition to Ca (ambient), Cg (grouping), and Ci (thermal insulation) — Cs is required by Appendix 4 for Method D installations and is listed in the underground tables (e.g. Table 4D4A).
6Elec-Mate has every Appendix 4 table built into the cable sizing calculator. Select cable type and reference method, and the app looks up the correct value instantly — no more flicking through the brown book.
01 · BS 7671 Appendix 4
What Is Appendix 4?
Looking for Amendment 4 (the A4:2026 update to BS 7671) rather than Appendix 4 (the cable tables)? See the BS 7671 Amendment 4:2026 guide for every change and what it means for your work.
Appendix 4 of BS 7671 is the section that every electrician turns to most frequently. It contains the current-carrying capacity tables for all standard cable types used in UK electrical installations. When you are sizing a cable, Appendix 4 is where you look up the maximum current a cable can carry under specific installation conditions.
The tables cover every combination of cable type (PVC, XLPE, MICC, SWA, flexible), conductor material (copper, aluminium), conductor configuration (single-core, multicore), and installation method (Reference Methods A through G). The values in these tables are based on defined reference conditions: an ambient temperature of 30 degrees Celsius, a single circuit (no grouping), no thermal insulation in contact with the cable, and the cable operating at its maximum conductor temperature (70 degrees Celsius for PVC, 90 degrees Celsius for XLPE/LSF).
When the actual installation conditions differ from these references — as they almost always do — correction factors must be applied. Appendix 4 also contains the correction factor tables: Table 4B1 for ambient temperature and Tables 4C1 to 4C5 for grouping.
BS 7671 Appendix 4 Tables: Cable Current Ratings & Volt Drop
BS 7671 Appendix 4 explained: current-carrying capacity, volt drop (mV/A/m) and correction factors (Ca, Cg, Ci) for every cable type and method.
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · BS 7671 Appendix 4
Understanding the Table Numbering System
The Appendix 4 table numbering follows a systematic pattern that, once understood, makes navigation much faster. The pattern is:
Table 4D5A / Table 4D5B
The suffix is what matters most day to day: A = current-carrying capacity (amps), B = voltage drop (mV/A/m). The number identifies a specific cable construction — so always read the table heading for insulation type and operating temperature rather than guessing from the letter.
The single most important point: the letter alone does not tell you the insulation. Table 4D1A is 70°C thermoplastic (PVC) twin and earth, while Table 4D5A — still in the 4D series — is 90°C thermosetting (XLPE) twin and earth. Both are “4D”. Pick the table by what is printed in its heading.
The tables you will actually use
Table 4D1A — 70°C thermoplastic (PVC) flat twin and earth, current-carrying capacity. The standard domestic cable.
Table 4D5A — 90°C thermosetting (XLPE) flat twin and earth, current-carrying capacity. Roughly 25% more capacity than 4D1A for the same size.
Table 4E / 4F series — thermosetting multicore and armoured (SWA) cables.
Table 4G / 4H — mineral insulated (MICC) cables; 4J — flexible cables and cords.
03 · BS 7671 Appendix 4
Current-Carrying Capacity Table: 4D1A (PVC) and 4D5A (XLPE)
This is the table most electricians come to Appendix 4 for: the current-carrying capacity (Iz) of twin and earth cable. The values below are for Reference Method C (clipped direct), two loaded conductors, at the standard reference conditions — 30°C ambient, single circuit, no grouping and no thermal insulation. Apply correction factors for any condition that differs.
Values per BS 7671:2018+A4:2026 Appendix 4, Tables 4D1A and 4D5A, Reference Method C. Iz is the tabulated capacity before correction factors — always compare against the required It once Ca, Cg, Ci and Cf are applied.
The XLPE (4D5A) column is consistently around 25% higher than the PVC (4D1A) column for the same conductor size, because the 90°C insulation tolerates more heat than 70°C PVC. For any installation method other than clipped direct, the capacity changes — read the correct column for your reference method.
Every Appendix 4 table built in
Skip the lookup — Elec-Mate's cable sizing calculator reads off the right table and column, applies correction factors and checks volt drop in one go.
A cable's current-carrying capacity depends as much on how it is installed as on its size — the same 2.5mm² T&E carries very different currents clipped to a wall versus buried in loft insulation. BS 7671 calls the installation arrangement the reference method, and it sets which column of the Appendix 4 table you read.
Regulation 521.201 of BS 7671:2018+A4:2026 requires the installation method to be in accordance with Table 4A1 of Appendix 4, and Table 4A2 illustrates each numbered method. The two methods you will meet most often are:
Method C — clipped direct
Cable clipped direct to a non-metallic surface, or run on a cable tray. This is the column used for the capacity values in the table above (e.g. 2.5mm² PVC T&E = 24A, XLPE = 30A).
Method D — buried in the ground
Cable in a duct or directly buried underground — the standard method for SWA submains and supplies to outbuildings. Method D also requires the Cs (soil thermal resistivity) correction factor in addition to Ca and Cg.
Methods A, B, E, F and G cover conduit in a thermally insulating wall, conduit or trunking on a surface, and cables in free air. The full A–G breakdown, with the Table 4A2 illustrations, is in our cable reference methods guide. Choosing the wrong method is one of the most common cable-sizing errors — a cable rated for clipping direct can be significantly overloaded once it is enclosed in insulation.
05 · BS 7671 Appendix 4
Thermoplastic (PVC) Cable Tables — The 4D Series
The 4D series of tables covers thermoplastic insulated cables — by far the most commonly used cable type in UK domestic and light commercial installations. PVC-insulated cables include twin and earth (flat profile cable with earth), singles for use in conduit and trunking, and PVC-insulated flexible cables.
PVC cables have a maximum conductor operating temperature of 70 degrees Celsius. All current-carrying capacity values in the 4D tables are calculated on the basis that the conductor does not exceed this temperature under sustained full-load conditions at an ambient temperature of 30 degrees Celsius.
Most commonly used PVC tables
Table 4D1A — PVC/copper twin and earth (70°C) cable clipped direct (Method C). Values: 1.0mm²=13A, 1.5mm²=16A, 2.5mm²=24A, 4mm²=32A, 6mm²=41A.
Table 4D2A — Single-core PVC/copper cables, clipped direct or on cable tray. Used for large singles on cable tray installations.
Table 4D5A — XLPE/copper twin and earth (90°C) cable clipped direct (Method C). Higher capacity than 4D1A for the same size. Values: 1.0mm²=16A, 1.5mm²=20A, 2.5mm²=30A, 4mm²=40A, 6mm²=51A.
When using Table 4D5A for twin and earth cable, the column you select depends on the reference method. Column 6 (two loaded conductors) is the standard column for single-phase circuits in twin and earth cable under the various reference methods.
T+E in thermal insulation (stud walls, ceiling voids)
Where flat twin and earth cable is in contact with, or enclosed within, thermal insulation — for example in a stud wall containing insulation or above an insulated ceiling — the standard Method C ratings do not apply. In these circumstances, the installer must apply the derating factors and reduced current-carrying capacities set out in BS 7671 Appendix 4 Table 4D5 for the relevant contact/enclosure condition (OSG Reg 13.5). Failure to derate for thermal insulation is one of the most common cable sizing errors in domestic work.
06 · BS 7671 Appendix 4
Thermosetting (XLPE/LSF) Cable Tables — The 4E Series
The 4E series covers thermosetting insulated cables — cables with XLPE (cross-linked polyethylene) or LSF (low smoke and fume) insulation. Thermosetting cables have a higher maximum conductor operating temperature of 90 degrees Celsius, compared to 70 degrees Celsius for PVC. This 20-degree advantage translates directly into higher current-carrying capacity for the same conductor size.
Thermosetting cables are used in several common scenarios: where higher current capacity is needed without increasing cable size (reducing material cost and conduit fill), in locations where the fire performance of PVC is inadequate (escape routes, public buildings), and where ambient temperatures are elevated and PVC derating would be excessive.
Capacity comparison: PVC T+E (Table 4D1A) vs XLPE T+E (Table 4D5A), Method C clipped direct
Size
mm²
PVC 70°C
Table 4D1A
XLPE 90°C
Table 4D5A
2.5
24
30
4.0
32
40
6.0
41
51
The capacity advantage of XLPE over PVC is approximately 25% for the same conductor size and installation method — for example, 2.5mm² T+E clipped direct: 30A (XLPE) vs 24A (PVC). This means that in situations where PVC cable sizing leads to an impractically large cable, switching to XLPE T+E of the same size may provide sufficient capacity without increasing the conductor cross-section.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
The voltage drop tables provide mV/A/m (millivolts per ampere per metre) values for each cable type and size. These values are used to calculate the voltage drop across a cable run using the formula:
VD = mV/A/m × Ib × L ÷ 1000
VD = voltage drop (volts) | Ib = design current (A) | L = cable length (m)
Where voltage drop sits in the standard
Voltage drop stays in Appendix 4. The mV/A/m values are listed in the cable tables, and the numeric limits are in Appendix 4, Section 6.4 — which Regulation 525.202 and 525.203 of BS 7671:2018+A4:2026 point to directly. This is unchanged by Amendment 4. There is no separate “Appendix 12” for voltage drop; if you have seen that claimed, it is incorrect.
BS 7671 Regulation 525 limits voltage drop to 3% for lighting circuits and 5% for all other circuits, measured from the origin of the installation. From a 230V single-phase supply, this gives maximum permissible voltage drops of 6.9V for lighting and 11.5V for power. From a 400V three-phase supply, the limits are 12V for lighting and 20V for power.
The voltage drop tables provide separate values for single-phase (two-core) and three-phase circuits. For three-phase calculations, the three-phase mV/A/m values are used, which account for the different phase relationships in a balanced three-phase system. The voltage drop for three-phase is calculated as: VD = mV/A/m (3-phase) x Ib x L / 1000.
Voltage drop calculated automatically
Elec-Mate's cable sizing calculator checks voltage drop as part of every cable sizing calculation.
Understanding which table to use for each cable type is essential for accurate cable sizing. Here are the most commonly encountered cable types and their corresponding Appendix 4 tables.
Twin and Earth (T&E)
The standard domestic cable. Flat profile with line, neutral, and CPC. Use Table 4D5A for XLPE 90°C T+E (clipped direct, Method C) or Table 4D1A for PVC 70°C T+E. Available in 1.0, 1.5, 2.5, 4.0, 6.0, 10, and 16mm². The most commonly used sizes are 1.5mm² for lighting, 2.5mm² for ring circuits, and 6mm² or 10mm² for cookers and showers.
Singles in Conduit
Single-core PVC-insulated cables drawn into conduit or trunking. Standard in commercial and industrial work. Note that Table 4D1A covers PVC twin and earth 70°C clipped direct — for singles in conduit, refer to the appropriate conduit installation column within the 4D series tables and check the column header for your reference method. The capacity is lower than T+E clipped direct for the same conductor size because the conduit restricts airflow around the cables.
SWA (Steel Wire Armoured)
Multicore armoured cable with mechanical protection from the steel wire armouring. Use Table 4D4A for 3-core XLPE-insulated (90°C) SWA cable. Standard for underground burial, external runs, and submain distribution. When buried (Method D), always apply the Cs soil thermal resistivity correction factor as well as Ca and Cg. The armouring also serves as the circuit protective conductor (CPC) in many installations.
Flexible Cables
Flexible cables for appliance connections and temporary installations. Use the 4J series tables. Flexible cables have different current-carrying capacities from fixed wiring cables because of their construction — finer conductor strands, different insulation thickness, and typically different ambient temperature assumptions.
09 · BS 7671 Appendix 4
How to Use the Tables Step by Step
Using the Appendix 4 tables correctly is the core skill of cable sizing. Here is the step-by-step process for looking up a current-carrying capacity value.
1
Identify the cable type
Determine whether you are using PVC (thermoplastic) or XLPE/LSF (thermosetting) cable, whether it is single-core or multicore, and whether it is armoured or non-armoured. This determines the table letter (D, E, F, H, J) and number.
2
Identify the reference method
Assess the installation method — how the cable will be physically installed. This determines the column of the table you use. The column headers in each table indicate which reference method each column covers.
3
Calculate the required It
Apply all correction factors (Ca, Cg, Ci, Cf, and Cs for buried cables) to calculate the minimum tabulated current rating: It = In / (Ca × Cg × Ci × Cf). For underground installations, include Cs (soil thermal resistivity) in the denominator.
4
Select the cable
Find the row in the table where the current-carrying capacity (Iz) is equal to or greater than It. That row gives you the minimum cable size for the installation. Then verify voltage drop and fault current withstand.
Instant Appendix 4 lookup on site
Skip the manual table lookup. Elec-Mate's cable sizing calculator selects the correct table, applies correction factors…
Here are the most frequently needed values from Appendix 4 for everyday domestic and light commercial work. These are for XLPE (90°C) twin and earth cable from Table 4D5A, Reference Method C (clipped direct), two loaded conductors. For PVC (70°C) T+E use Table 4D1A — values are lower (e.g. 2.5mm²=24A, 4mm²=32A, 6mm²=41A).
Remember: these are the tabulated values under reference conditions. Once you apply correction factors, the effective capacity of the cable is reduced. A 2.5mm² XLPE T+E cable with Iz = 30A may only be able to carry around 21A after derating for grouping and insulation. Always calculate the required It before selecting from the table.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Every Appendix 4 table, always in your pocket
Join 1,000+ UK electricians using Elec-Mate for instant cable sizing with every BS 7671 table built in. 70+ calculators, 16 certificate types — all BS 7671:2018+A4:2026. 7-day free trial, cancel anytime.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy