BS 7671 CABLE SIZING

BS 7671 Correction Factors Ca, Cg, Ci & Cf Explained

The complete guide to cable sizing correction factors under BS 7671. Ambient temperature (Ca from Table 4B1), grouping (Cg from Tables 4C1-4C6), thermal insulation (Ci from Regulation 523.9), and semi-enclosed fuse factor (Cf = 0.725). Worked examples, common mistakes, and how to apply the formula It = In / (Ca x Cg x Ci x Cf).

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

14 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What are correction factors in cable sizing (BS 7671)?

Correction factors reduce a cable’s tabulated current-carrying capacity to allow for the real installation conditions. The four BS 7671 factors are: Ca for ambient temperature (Table 4B1, 1.0 at 30°C), Cg for grouping with other cables (Tables 4C1–4C6), Ci for thermal insulation (Reg 523.9 — 0.5 if totally surrounded over 0.5m), and Cf for a BS 3036 semi-enclosed fuse (0.725). Apply them so the required tabulated rating It ≥ In ÷ (Ca × Cg × Ci × Cf) — the more onerous the conditions, the larger the cable you need.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1The correction factor formula is It = In / (Ca x Cg x Ci x Cf) — you must calculate the tabulated current rating before selecting a cable from BS 7671 Appendix 4.
  • 2Ca (ambient temperature) comes from Table 4B1 and accounts for temperatures above the standard 30 degrees Celsius reference — at 40 degrees Celsius, Ca drops to 0.87 for PVC cables, requiring a larger cable.
  • 3Cg (grouping) from Tables 4C1 to 4C6 is the most commonly applied factor — three circuits bunched and touching have Cg of 0.70, meaning each cable can only carry 70% of its tabulated current.
  • 4Ci (thermal insulation) under Reg 523.9 is the most punishing factor — a cable totally surrounded by thermal insulation for more than 0.5 metres drops to Ci = 0.50, which is 0.5 times the current-carrying capacity for that cable clipped direct and open (Reference Method C).
  • 5When a cable is totally enclosed in thermal insulation for less than 0.5 metres, the derating depends on three factors: conductor size, length in insulation, and the thermal conductivity of the insulation material — not length alone (Reg 523.9 and OSG Reg 2.6).
  • 6Elec-Mate's cable sizing calculator applies all four correction factors automatically with every BS 7671 table built in — no manual lookups, no calculation errors.
01 · BS 7671 Cable Sizing

What Are Correction Factors?

Correction factors are multipliers used in the cable sizing process to account for real-world installation conditions that reduce a cable's ability to carry current safely. The current-carrying capacity values in BS 7671 Appendix 4 are based on a set of reference conditions — a single circuit, installed in an ambient temperature of 30 degrees Celsius, with no thermal insulation, and protected by an MCB or HRC fuse. When the actual conditions differ from these references, correction factors must be applied to derate the cable accordingly.

There are four correction factors in the BS 7671 cable sizing methodology: Ca for ambient temperature, Cg for grouping (multiple circuits installed together), Ci for thermal insulation, and Cf for semi-enclosed fuses. Each factor is a decimal value less than or equal to 1.0. Multiplying them together gives the overall derating, and dividing the protective device rating by this product gives the minimum tabulated current rating the cable must have.

The fundamental formula is:

It = In ÷ (Ca × Cg × Ci × Cf)

It = minimum tabulated current rating | In = rated current of protective device | Ca, Cg, Ci, Cf = correction factors

You then select a cable from the appropriate Appendix 4 table where the tabulated current-carrying capacity Iz is equal to or greater than It. If any factor is missed or applied incorrectly, the cable will be undersized for the actual conditions, leading to overheating, insulation degradation, and a potential fire risk.

Cable sizing calculator with all correction factors built in

Enter your load, installation conditions, and cable route. Elec-Mate applies Ca, Cg, Ci, and Cf automatically using every BS 7671 Appendix 4 table.

Try it free for 7 days
Download on the App StoreGet it on Google Play
Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Cable Sizing

Ca — Ambient Temperature Correction Factor

The ambient temperature correction factor Ca accounts for the fact that cable current-carrying capacity tables in Appendix 4 are based on an ambient temperature of 30 degrees Celsius. When cables are installed in environments hotter than 30 degrees Celsius, their ability to dissipate heat is reduced, and the cable must be derated. Ca values are found in Table 4B1 of BS 7671 Appendix 4.

Table 4B1 — Key Ca Values (70 degrees Celsius PVC)

25°C

1.03

30°C

1.00

35°C

0.94

40°C

0.87

45°C

0.79

50°C

0.71

55°C

0.61

60°C

0.50

Thermosetting cables (XLPE, LSF) have different Ca values because they have a higher maximum conductor temperature of 90 degrees Celsius compared to 70 degrees Celsius for PVC. This means thermosetting cables are less affected by elevated ambient temperatures — the same Table 4B1 gives a separate column for 90 °C thermosetting insulation.

Table 4B1 — Key Ca Values (90 degrees Celsius thermosetting / XLPE)

25°C

1.02

30°C

1.00

35°C

0.96

40°C

0.91

45°C

0.87

50°C

0.82

55°C

0.76

60°C

0.71

At 40 °C, 90 °C thermosetting cable derates to 0.91 versus 0.87 for 70 °C PVC — one reason thermosetting is favoured for hot routes.

Common situations where Ca must be applied include loft spaces (35 to 50 degrees Celsius in summer), plant rooms, airing cupboards, near hot water cylinders, commercial kitchens, server rooms, and South-facing roof voids. If the ambient temperature is 30 degrees Celsius or below, Ca = 1.0 and has no effect on the calculation.

Solar PV installations — Reg 712.523.101

Cables routed directly beneath photovoltaic modules are subjected to heating from the underside of the module. Reg 712.523.101 requires that for the design and sizing of such cables, the ambient temperature shall be considered to be at least 70 °C. At 70 °C the Ca factor for a 70 °C PVC cable drops to 0.50 — the same magnitude as total thermal insulation enclosure. XLPE or LSOH cables with a 90 °C conductor operating temperature are standard for under-module strings precisely because their Ca value at 70 °C is significantly less severe.

03 · BS 7671 Cable Sizing

Cg — Grouping Correction Factor

The grouping correction factor Cg accounts for the mutual heating effect when multiple circuits are installed together. Each current-carrying cable generates heat, and when cables are bunched or touching, they share that heat, raising the temperature of every cable in the group. This reduces the safe current each individual cable can carry.

Cg values are found in Tables 4C1 to 4C6 of BS 7671 Appendix 4. The correct table depends on the installation arrangement. Table 4C1 is the one you reach for most often — it covers a single circuit or a group bunched in air, on a surface, embedded or enclosed (including cables in the same conduit or trunking), and also single-layer arrangements on a wall, floor or cable tray. Tables 4C2 to 4C6 cover specialised cases such as cables buried directly in the ground, single cables in buried ducts, groups of multicore cables, groups of single-core cables, and cables in in-floor concrete troughs.

Table 4C1 — Key Cg Values (Bunched or Same Conduit/Trunking)

1 circuit

1.00

2 circuits

0.80

3 circuits

0.70

4 circuits

0.65

5 circuits

0.60

6 circuits

0.57

7 circuits

0.54

9+ circuits

0.50

An important exception comes from Regulation 523.5: where a cable in a group is expected to carry not more than 30% of its grouped current-carrying capacity, it may be ignored when obtaining the rating factor for the rest of the group. This allows diversity to be taken into account at the cable sizing stage, reducing the impact of grouping in installations where not all circuits are fully loaded at the same time. The 30% allowance must not then be applied a second time to any adjacent cable grouping calculation.

Grouping is the correction factor most frequently encountered in practice because cables commonly share routes — leaving a consumer unit through a common hole, running through shared voids, or installed together in conduit or trunking. Every electrician must count the number of circuits sharing a route and apply the correct Cg factor for the worst-case section of the cable run.

04 · BS 7671 Cable Sizing

Ci — Thermal Insulation Correction Factor

The thermal insulation correction factor Ci is the most punishing of all correction factors. Thermal insulation prevents a cable from dissipating the heat generated by current flow, causing the conductor temperature to rise above its safe operating limit. BS 7671 Regulation 523.9 sets out the requirements. Note that Reg 523.7 covers parallel conductors and equal load sharing — some older guides incorrectly cite it for thermal insulation. The correct reference is Reg 523.9 alone.

Cable touching insulation on one side only

Ci = 0.89 — This is the common scenario where cables are clipped to joists or studwork with insulation laid between the joists or packed into the stud wall. The cable has insulation on one side but can still dissipate some heat from the other side. This is by far the most frequently applied Ci value in domestic installations.

Cable totally surrounded by thermal insulation (>0.5m)

Ci = 0.50 — If the cable is completely enclosed in thermal insulation for a continuous length of more than 0.5 metres, the current-carrying capacity shall be taken as 0.5 times the capacity for that cable clipped direct to a surface and open (Reference Method C). This is an extremely severe derating that typically forces a significant increase in cable size. It applies when cables are run through insulation in lofts, walls, or floors where the insulation completely surrounds the cable.

Important: If the cable is installed in conduit or trunking (Reference Method A or B), the base Iz is already lower than Method C. You must still work from the Method C figure when applying the 0.5 factor per Reg 523.9 — using the conduit rating as the base would result in systematic under-sizing.

Cable in insulation for less than 0.5m

Appendix 4 Section 2.6 of BS 7671 provides Ci derating factors for cables totally surrounded by thermal insulation for short lengths (up to 10 mm² conductors, insulation thermal conductivity above 0.04 W m⁻¹ K⁻¹). Typical values: 50 mm in insulation Ci = 0.88; 100 mm Ci = 0.78; 200 mm Ci = 0.63; 400 mm Ci = 0.51; 500 mm or more Ci = 0.50.

The derating for cables in insulation for less than 0.5 m depends on three factors, not length alone: the size of the conductor, the length of cable within the insulation, and the thermal conductivity of the insulation material (OSG Reg 2.6). Different insulation products — mineral wool, rigid foam board, and blown fibre — have different thermal conductivities, so the published derating factors assume insulation with a thermal conductivity above 0.04 W m⁻¹ K⁻¹. For conductors above 10 mm² or insulation with lower conductivity, more precise information is required.

Ci by Length in Insulation (≤10 mm², Appendix 4 Section 2.6)

50 mm

0.88

100 mm

0.78

200 mm

0.63

400 mm

0.51

≥500 mm

0.50

These factors apply to conductors up to 10 mm² in insulation with a thermal conductivity (λ) greater than 0.04 W m⁻¹ K⁻¹. Above 0.5 m of full enclosure, Reg 523.9 fixes the worst case at 0.5 × the Reference Method C rating, in the absence of more precise information.

The Ci factor is the one most commonly forgotten by electricians, particularly in domestic loft installations where insulation depths have increased from 100mm to 270mm or more in recent years. A cable that was adequately sized when the loft had 100mm of insulation may now be undersized if additional insulation has been laid over it, totally enclosing the cable.

Never forget a derating factor again

Elec-Mate's cable derating calculator prompts you for ambient temperature, grouping, and insulation conditions.

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · BS 7671 Cable Sizing

Cf — Semi-Enclosed Fuse Correction Factor

The semi-enclosed fuse correction factor Cf = 0.725 applies only when the circuit is protected by a BS 3036 semi-enclosed (rewirable) fuse. This factor compensates for the poor fusing characteristics of BS 3036 fuses, which have a fusing factor of approximately 2.0 — meaning they may not blow until the current reaches twice their rated value.

By comparison, an MCB to BS EN 60898 has a much tighter operating characteristic — BS 7671 treats the conventional operating current (I2) of an MCB, RCBO or cartridge fuse as not exceeding 1.45 times the device rating (Reg 433.1.1). HRC fuses to the BS 88 series are similarly precise. Because a BS 3036 fuse can allow significantly higher currents to flow for longer before it blows, the cable must be rated to handle those currents without overheating — hence the 0.725 derating factor (which is 1.45 / 2, restoring the same degree of protection afforded by other devices).

Cf by Protective Device Type

BS 3036 semi-enclosed (rewirable) fuse

0.725

MCB — BS EN 60898

1.00

RCBO — BS EN 61009-1

1.00

HRC fuse — BS 88 series

1.00

Cartridge fuse — BS 88-3 / BS 1362

1.00

MCCB — BS EN 60947-2

1.00

Only the BS 3036 rewirable fuse attracts a Cf below 1.0. For every other device on this list Cf = 1.0 and drops out of the calculation.

When does Cf apply?

Cf = 0.725 applies only when the protective device is a BS 3036 semi-enclosed fuse. For MCBs (BS EN 60898), RCBOs (BS EN 61009-1), HRC fuses (BS 88 series), and cartridge fuses (BS 88-3), Cf = 1.0 and has no effect on the calculation. BS 3036 fuses are rarely installed in new work but are commonly encountered during periodic inspection of older installations, particularly those with rewirable fuse boards.

If you are assessing an existing installation with BS 3036 fuses during an EICR, you must apply Cf = 0.725 when verifying the existing cable sizes. If the cable was originally sized without this factor (as was common in older installations designed before this requirement was introduced), the cable may be undersized for the fuse protecting it. This is a common finding on older installations and the appropriate EICR observation code depends on the magnitude of the shortfall and the actual loading of the circuit.

EICR obligation — Section 523

The BS 7671 Schedule of Inspections requires the inspector to confirm the “adequacy of cables for current-carrying capacity with regard for the type and nature of installation” — verified against Section 523 (item 8.10 on the model schedule of inspections). That assessment implicitly covers the applicable correction factors: ambient temperature, grouping, and thermal insulation. An existing circuit whose conductor cross-sectional area does not stand up once the relevant correction factors are applied is a verifiable shortfall against Section 523, not merely a legacy sizing decision. Record it with an appropriate EICR observation code and cross-reference the correction factor calculation.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · BS 7671 Cable Sizing

Applying All Correction Factors Together

In practice, multiple correction factors often apply simultaneously. A cable leaving a consumer unit may be grouped with other circuits (Cg), pass through a loft space at elevated temperature (Ca), and be in contact with thermal insulation (Ci). All applicable factors must be multiplied together, and the protective device rating divided by this product to determine the minimum tabulated current rating.

It = In ÷ (Ca × Cg × Ci × Cf)

The combined effect of multiple correction factors can be dramatic. Consider a circuit protected by a 32A MCB with three circuits grouped (Cg = 0.70), ambient temperature of 35 degrees Celsius (Ca = 0.94), and cable touching insulation on one side (Ci = 0.89):

It = 32 ÷ (0.94 × 0.70 × 0.89 × 1.0)

It = 32 ÷ 0.5855 = 54.7A

Without any correction factors, a 32A circuit would need a cable rated for just 32A. With all three factors applied, the cable must be rated for 54.7A — a massive increase that could mean the difference between 4mm² and 10mm² cable, with significant cost and installation implications.

This is precisely why cable sizing must be done correctly at the design stage. An electrician who skips the correction factor calculation and simply selects a cable based on the MCB rating alone is likely to install an undersized cable that will overheat under full load conditions. Over time, this overheating degrades the cable insulation and increases the risk of fire.

Automatic derating with every BS 7671 table

Elec-Mate's cable sizing calculator applies all correction factors and shows you the calculation step by step.

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · BS 7671 Cable Sizing

Worked Examples

Example 1: Domestic Shower Circuit

A 9.5kW electric shower is to be installed on a dedicated radial circuit. The cable route runs through a loft space at 35 degrees Celsius, grouped with 2 other circuits, touching insulation on one side. Protected by an MCB.

Design current: Ib = 9,500 ÷ 230 = 41.3A

Protective device: 45A Type B MCB (next standard rating above 41.3A)

Correction factors: Ca = 0.94 (35°C, 70°C PVC) | Cg = 0.70 (3 circuits bunched and touching, Table 4C1 row 1) | Ci = 0.89 (in contact with insulation on one side) | Cf = 1.0 (MCB)

Combined factor: 0.94 × 0.70 × 0.89 × 1.0 = 0.586

Required It: 45 ÷ 0.586 = 76.8A

Cable selection: the cable must be chosen from the correct Appendix 4 table so that its tabulated Iz meets or exceeds 76.8A under the chosen reference method. The grouping and insulation conditions push this circuit well beyond the cable a 45A MCB alone would suggest — the difference between an installed cable that survives and one that overheats.

Example 2: Ring Final Circuit in Insulated Wall

A ring final circuit protected by a 32A Type B MCB. Cable runs through an insulated timber-frame wall where it is totally enclosed in insulation for 2 metres. Ambient temperature 30 degrees Celsius, no other circuits grouped at the insulated section.

Correction factors: Ca = 1.00 (30°C) | Cg = 1.00 (single circuit at worst point) | Ci = 0.50 (totally enclosed >0.5m) | Cf = 1.0 (MCB)

Combined factor: 1.00 × 1.00 × 0.50 × 1.0 = 0.50

Required It: 32 ÷ 0.50 = 64.0A

Result: the ring would need each leg to carry an effective It of 64A through the enclosed section — far beyond what a standard 2.5mm² twin and earth ring leg can deliver once halved by Ci = 0.50. The practical fix is to reroute the cable so it is not totally surrounded by insulation, or to redesign the circuit. This is exactly why Reg 523.9 advises that cables should preferably not be installed where they are liable to be covered by thermal insulation.

08 · BS 7671 Cable Sizing

Common Mistakes with Correction Factors

Forgetting to apply any correction factors at all

The most common and most dangerous mistake. Many electricians select cables based solely on the MCB rating without considering the installation conditions. A 32A MCB does not mean a 32A-rated cable is sufficient — it means you need a cable that can carry at least 32A after all derating factors have been applied. Under adverse conditions, this could require a cable rated for 50A or more.

Using the wrong grouping count

Grouping must be assessed at the worst point along the cable route — typically where the most cables are bundled together, such as at the consumer unit or where cables pass through a common hole in a joist. Counting only the cables at the load end rather than at the point of maximum grouping leads to an incorrect (too high) Cg value.

Ignoring thermal insulation in loft spaces

With modern loft insulation depths of 270mm or more, cables laid on ceiling joists can be completely buried in insulation. This triggers the Ci = 0.50 factor, halving the cable capacity. Many electricians fail to check whether insulation has been added since the original installation, particularly during periodic inspections.

Applying correction factors to the design current instead of the protective device rating

The formula divides the protective device rating (In) by the correction factors, not the design current (Ib). Dividing Ib by the factors would give a lower value than required, potentially resulting in an undersized cable. The correct approach is: It = In / (Ca x Cg x Ci x Cf), then select a cable with Iz equal to or greater than It.

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Cable sizing with automatic derating

Join 1,000+ UK electricians using Elec-Mate for on-site cable sizing, 70+ calculators, and 16 certificate types — all built to BS 7671:2018+A4:2026. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy