TECHNICAL GUIDE

Reference Methods: How Cable Installation Affects Capacity

The same cable can carry 20 A or 27 A depending on how it is installed. Reference methods A to G define the installation arrangement and directly determine the current-carrying capacity from the BS 7671 Appendix 4 tables. This guide explains each method, when it applies, and how to choose correctly.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is Reference Method C in BS 7671?

Reference Method C is "clipped direct" — a cable fixed directly to a non-metallic surface or run on a cable tray, with free air around it. It is one of the installation methods in Appendix 4 (Tables 4A1 and 4A2) that determines which column of the current-carrying capacity tables you read. Method C gives higher ratings than enclosed methods because heat dissipates more easily.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Installation reference methods (A to G) describe how a cable is physically installed and directly determine the current-carrying capacity from the Appendix 4 tables in BS 7671.
  • 2The same cable can have vastly different current-carrying capacities depending on the reference method — for example, 2.5 mm² T+E is rated at 20 A under Method A but 27 A under Method C.
  • 3The most restrictive section of the cable run determines the reference method for the entire run, even if that restrictive section is only a short distance.
  • 4Method C (clipped direct) is the most common for domestic T+E cable. Method A (enclosed in conduit in an insulating wall) is used when cables are chased into masonry with conduit.
  • 5OSG Methods 100, 101, and 102 apply when flat twin-and-earth cable is in contact with plasterboard or joists inside a stud wall or ceiling void — these require derating using Tables 7.1(iii) and 7.1(iv) of the IET On-Site Guide.
  • 6Reg 622.85 of BS 7671 requires inspectors to verify that cables are adequate for current-carrying capacity, including the installation reference method and all applicable correction and grouping factors, as part of every EICR inspection.
  • 7Elec-Mate handles reference method selection as part of its cable sizing calculator, automatically applying the correct column from the Appendix 4 tables across its suite of 70+ calculators.
01 · Technical Guide

What Are Installation Reference Methods?

Installation reference methods are standardised descriptions of how a cable is physically installed in a building or site. They are listed in Table 4A2 of Appendix 4 of BS 7671:2018+A4:2026 and are fundamental to the cable sizing process. The reference method you select determines which column of the Appendix 4 current-carrying capacity tables you read, and therefore the maximum current the cable can safely carry.

The reason reference methods matter is heat dissipation. A cable generates heat when it carries current (I²R losses). How effectively that heat can escape into the surrounding environment depends entirely on the physical installation arrangement. A cable in free air on an open tray can shed heat freely in all directions. The same cable enclosed in conduit inside a masonry wall, surrounded by plaster and possibly thermal insulation, cannot dissipate heat nearly as well — so its safe current-carrying capacity is lower.

There are seven main reference methods: A1, A2, B, C, D, E, F, and G. Each represents a different installation arrangement, from the most restrictive (enclosed in insulation) to the least restrictive (open air on a perforated tray). Selecting the correct reference method is not optional — it is a required step in every cable sizing calculation.

BS 7671 Reference Method C: Current Capacity

BS 7671 Reference Method C for cables clipped direct to surface. Check Appendix 4:2026 current ratings in seconds. Avoid undersizing on site.

Try it free for 7 days
Download on the App StoreGet it on Google Play
Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Technical Guide

Methods A1 and A2: Enclosed in Conduit in an Insulating Wall

Method A covers cables installed in conduit or trunking that is itself enclosed in a thermally insulating wall — typically PVC conduit chased into masonry and then plastered over, or cables directly in a thermally insulating wall.

  • Method A1: Cables in conduit in a thermally insulating wall. Single-core cables in conduit chased into masonry. This is the most restrictive common reference method and gives the lowest current-carrying capacities.
  • Method A2: Multicore cable in conduit in a thermally insulating wall. Similar to A1 but for multicore cables (such as T+E in conduit chased into a wall). Also gives low current-carrying capacities.

When it applies: Any time you chase conduit into a masonry or stud wall and plaster over it. This is common for switch drops, socket feeds through walls, and any cable run that needs to be concealed in a solid wall with conduit protection. The surrounding masonry and plaster act as thermal insulation, restricting heat dissipation.

Capacity example: A 2.5 mm² T+E cable under Method A has a current-carrying capacity of just 20 A. Compare this with 27 A under Method C. That 7 A difference can determine whether you need to use 4 mm² cable instead of 2.5 mm².

03 · Technical Guide

Method B: Enclosed in Conduit on a Wall or in Trunking

Method B covers cables enclosed in conduit or trunking that is mounted on a wall or ceiling surface — not buried in the wall. The conduit or trunking is exposed and can dissipate some heat into the surrounding air, but the cable inside is still partially restricted.

  • Surface-mounted PVC conduit on a wall or ceiling
  • Surface-mounted steel conduit on a wall or ceiling
  • Surface-mounted PVC or metal trunking
  • Cables in conduit or trunking running along the surface of a plasterboard ceiling

Method B gives slightly higher current-carrying capacities than Method A because the conduit or trunking is not embedded in insulating material — it is on the surface and can radiate heat into the air. However, the capacity is still lower than Method C (clipped direct) because the conduit or trunking restricts airflow around the cable.

Common use: Commercial and industrial installations where cables are run in surface-mounted conduit or trunking for protection and appearance. Also used in domestic garages, workshops, and utility rooms where surface wiring is acceptable.

04 · Technical Guide

Method C: Clipped Direct to a Surface

Method C is the most common reference method for domestic installations using flat twin-and-earth (T+E) cable. It covers cables fixed directly to a wall, ceiling, joist, or other surface using clips, without any conduit or trunking enclosure.

  • T+E cable clipped to joists in a loft
  • T+E cable clipped to battens on a wall
  • Cables clipped to the surface of a stud wall or ceiling
  • SWA cable clipped to a wall with saddle clips

Method C provides good heat dissipation because the cable is in contact with the mounting surface on one side and exposed to air on the other. The mounting surface (wood, masonry, plaster) absorbs and conducts some heat away from the cable, while the exposed side radiates and convects heat into the air.

Capacity example: A 2.5 mm² T+E cable under Method C has a current-carrying capacity of 27 A — a 35% increase over Method A (20 A) for the same cable. This is why the reference method selection has such a significant impact on cable sizing decisions.

Important note: If a cable that is mostly clipped to joists (Method C) passes through a section of conduit in a wall (Method A) at any point, the more restrictive Method A applies to the entire run. Design for the worst case.

05 · Technical Guide

Method D: Buried in the Ground

Method D covers cables installed directly in the ground. This is the standard method for armoured cable (SWA) runs supplying outbuildings, garages, garden offices, external lighting, and any other installation that requires an underground cable route.

  • Standard burial depth: At least 500 mm below finished ground level for areas with no vehicular traffic. 600 mm or more where vehicles may cross. Deeper burial under roads or driveways.
  • Cable protection: SWA cable provides its own mechanical protection via the steel wire armour. The cable is typically laid on a bed of fine sand or sieved fill, covered with more sand, and then protected with yellow cable warning tiles or tape before backfilling.
  • Soil thermal resistivity: The standard tables assume a soil thermal resistivity of 2.5 K.m/W. Dry sandy soils may have a higher resistivity (less heat dissipation), requiring derating. Wet clay soils dissipate heat better.

Method D is unique because the thermal environment (soil) is very different from air. The current-carrying capacities for Method D are given in separate columns in the Appendix 4 tables — usually in the 4E series (XLPE/SWA). Grouping of buried cables (multiple circuits in the same trench) also has a significant impact and uses specific grouping factors from Table 4A1.

06 · Technical Guide

Methods E, F, and G: Free Air Installation

Methods E, F, and G cover cables installed in free air — on open trays, ladders, or cleats — where air can circulate freely around the cable. These methods give the highest current-carrying capacities because heat dissipation is maximised.

Method E: Perforated Cable Tray

Cables on a horizontal or vertical perforated tray. The perforations allow air to circulate beneath and around the cables. Common in commercial and industrial cable management for distribution cables and submains.

Method F: Cable Ladder or Cleats

Cables on horizontal or vertical cable ladders, or secured to wall-mounted cleats. Maximum air circulation around the cables. Used for large power cables in industrial installations, switchrooms, and plant rooms.

Method G: Spaced from a Surface

Cables spaced from a wall or ceiling surface in free air, not touching the surface. Provides slightly better heat dissipation than touching the surface (Method C) because air can circulate on all sides.

These methods are rarely used in domestic work but are essential for commercial and industrial installations. The higher current-carrying capacities they provide can mean smaller (and cheaper) cables for the same circuit, which makes a significant cost difference on large installations with many long cable runs.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
07 · Technical Guide

OSG Methods 100, 101, and 102: Cables in Contact with Plasterboard or Joists

In addition to the lettered reference methods (A to G) in BS 7671 Table 4A2, the IET On-Site Guide defines three numbered reference methods — 100, 101, and 102 — specifically for flat twin-and-earth cable installed inside stud walls and ceiling voids where the cable is in contact with plasterboard or joists.

  • Method 100: Flat twin-and-earth cable clipped to or lying on the surface of a joist inside a floor or ceiling void, in contact with the joist. The joist conducts heat away on one side but the overall thermal environment is more restrictive than open-air Method C.
  • Method 101: Flat twin-and-earth cable touching the inner face of plasterboard inside a stud wall or ceiling void, with thermal insulation present on the other side. The plasterboard contact and proximity to insulation reduce heat dissipation, requiring derating relative to Method C.
  • Method 102: Flat twin-and-earth cable touching plasterboard or joists where thermal insulation is in contact with the cable. This is the most restrictive of the three numbered methods and may require significant derating or a larger cable cross-section.

The detailed current-carrying capacity values and correction factors for Methods 100, 101, and 102 are given in Tables 7.1(iii) and 7.1(iv) of the IET On-Site Guide (OSG 9th Edition, 2022, incorporating A4:2026). These tables reference Table 4D5 for the base cable ratings. Failing to apply these numbered methods when cables are in contact with plasterboard or joists — and instead using the higher Method C ratings — results in undersized cables that may overheat in service.

Practical note: These scenarios are very common in domestic rewires and first-fix work. Any T+E cable that runs through a stud wall or across joists in a void containing thermal insulation must be assessed against Methods 100–102 rather than simply defaulting to Method C.

08 · Technical Guide

How to Choose the Right Reference Method

Selecting the correct reference method is a three-step process:

  1. Survey the entire cable route. Walk the route from the distribution board to the final point. Note every section: through the wall in conduit, clipped to joists, through a floor void, passing through insulation, on a tray, etc.
  2. Identify the reference method for each section. Refer to Table 4A2 in Appendix 4 of BS 7671 (or Table 7.1(ii) of the IET On-Site Guide for domestic final circuits). Match the physical installation arrangement of each section to the correct reference method.
  3. Use the most restrictive method for the whole run. If the cable passes through multiple installation arrangements, the section with the lowest current-carrying capacity determines the reference method for the entire cable. Design for the worst case.

In practice, for most domestic work, the choice is between Method A (conduit in wall) and Method C (clipped direct). If any section of the cable route is in conduit in a wall, Method A applies. For commercial work with tray and trunking, you may be choosing between Method B (trunking) and Method E (perforated tray). Always document your reference method choice — it forms part of the design records required by BS 7671.

70+ calculators built for UK electricians

Cable sizing, voltage drop, max demand, Zs, PFC, adiabatic equation, conduit fill, trunking fill, power factor, diversity factor…

Try it free for 7 days
Download on the App StoreGet it on Google Play
09 · Technical Guide

Impact on Current-Carrying Capacity

The difference in current-carrying capacity between reference methods is substantial. Here is a comparison for common cable sizes using Table 4D5 (multicore PVC copper T+E):

Cable SizeMethod A (A)Method B (A)Method C (A)
1.5 mm²14.517.520
2.5 mm²202427
4 mm²273237
6 mm²344047
10 mm²465464
16 mm²617385

As you can see, the difference between Method A and Method C is approximately 25 to 40% for the same cable. This can easily mean the difference between a 2.5 mm² and a 4 mm² cable, or a 6 mm² and a 10 mm² cable. The cost and physical size difference is significant — especially for long runs or when conduit sizing is a constraint.

These tabulated values are before correction factors for grouping, ambient temperature, and thermal insulation are applied. After applying those factors, the effective capacity is lower still. The Elec-Mate cable sizing calculator handles all of this in one step.

10 · Technical Guide

Common Installation Scenarios

Here are the reference methods for the most common cable installation scenarios you will encounter:

Domestic Ring Final Circuit

T+E cable clipped to joists under the floor and dropping down through conduit in the wall to socket outlets. The section in conduit in the wall is Method A; the section clipped to joists is Method C. Use Method A for the whole run.

Shower Circuit

Dedicated circuit from the consumer unit to the shower. Cable typically clipped to joists (Method C) then drops through the bathroom wall in conduit (Method A). Use Method A. Given the high current (40 A+), the reference method has a significant impact on the cable size required.

SWA to Outbuilding

Armoured cable from the main distribution board, through the wall, buried in the ground across the garden, and into the outbuilding. The buried section is Method D; the section inside each building clipped to the wall is Method C. Use Method D for the buried section (usually the most restrictive for SWA cable).

Commercial Distribution

Submain cables on perforated cable tray from the main switchboard to a sub-distribution board. Method E for the tray section. If the cable enters trunking at any point, that section becomes Method B. Use the most restrictive method — or size each section individually if the design allows.

Frequently Asked Questions About Reference Methods

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Cable Sizing with Automatic Reference Methods

Join 1,000+ UK electricians using Elec-Mate's 70+ calculators. Select the installation method, enter the conditions — cable sizing is done in seconds with the correct Appendix 4 table applied automatically. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy