TECHNICAL GUIDE

Reference Methods: How Cable Installation Affects Capacity

The same cable can carry 20 A or 27 A depending on how it is installed. Reference methods A to G define the installation arrangement and directly determine the current-carrying capacity from the BS 7671 Appendix 4 tables. This guide explains each method, when it applies, and how to choose correctly.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

13 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What is Reference Method C in BS 7671?

Reference Method C is "clipped direct" — a single-core or multicore cable fixed on, or spaced less than 0.3 times its diameter from, a wooden or masonry wall (Table 4A2, Installation Method 20). It also covers cable on an unperforated tray, cable on a floor, and cable direct in masonry with capping. Table 4A2 of Appendix 4 tells you which reference method applies to your installation method, and that determines which column of the current-carrying capacity tables you read. Method C gives higher ratings than the enclosed methods A and B because heat dissipates more easily — but a cable fixed directly under a ceiling, or above a plasterboard ceiling with insulation, is not Method C.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01BS 7671 uses eight reference methods — A, B, C, D1, D2, E, F and G. Reg 521.2 requires the installation method to be in accordance with Table 4A2 of Appendix 4, and Table 4A2 tells you which reference method to use to look up current-carrying capacity.
  2. 02The same cable can have vastly different current-carrying capacities depending on the reference method — for example, 2.5 mm² T+E is rated at 20 A under Method A but 27 A under Method C.
  3. 03The most restrictive section of the cable run determines the reference method for the entire run, even if that restrictive section is only a short distance.
  4. 04Method C (clipped direct) is the most common for domestic T+E cable. Method A is specifically a conduit in a thermally insulated wall — a timber-framed wall with an insulated cavity. Conduit chased into masonry is Method B (Table 4A2, Installation Methods 59 and 60), and cable direct in masonry with capping is Method C (Installation Method 58).
  5. 05Reference Methods 100 to 103 in Table 4A2 cover flat twin-and-earth above a plasterboard ceiling or inside a stud wall with thermal insulation. Ratings come from Table 4D5 of BS 7671; Tables 7.1(iii) and 7.1(iv) of the IET On-Site Guide reproduce the same guidance for installers.
  6. 06Reg 622.85 of BS 7671 requires inspectors to verify that cables are adequate for current-carrying capacity, including the installation reference method and all applicable correction and grouping factors, as part of every EICR inspection.
  7. 07Elec-Mate handles reference method selection as part of its cable sizing calculator, automatically applying the correct column from the Appendix 4 tables across its suite of 70+ calculators.

01 · Technical Guide

What Are Installation Reference Methods?

Already know which method applies and just need the number? Use the free cable derating calculator further down this page — no sign-up needed.

Installation reference methods are standardised descriptions of how a cable is physically installed in a building or site. Table 4A2 of Appendix 4 of BS 7671:2018+A4:2026 lists around 70 numbered installation methods and gives, against each one, the reference method to be used to determine current-carrying capacity. Regulation 521.2 requires the installation method of a wiring system to be in accordance with Table 4A2, and Regulation 523.2 requires the current in the cable not to exceed the value read from Appendix 4 with reference to Table 4A2, subject to any necessary rating factors. The reference method you select determines which column of the Appendix 4 current-carrying capacity tables you read, and therefore the maximum current the cable can safely carry.

The reason reference methods matter is heat dissipation. A cable generates heat when it carries current (I²R losses). How effectively that heat can escape into the surrounding environment depends entirely on the physical installation arrangement. A cable in free air on an open tray can shed heat freely in all directions. The same cable enclosed in conduit inside a masonry wall, surrounded by plaster and possibly thermal insulation, cannot dissipate heat nearly as well — so its safe current-carrying capacity is lower.

BS 7671 uses eight reference methods: A, B, C, D1, D2, E, F and G. (Cable calculation software sometimes shows the IEC subdivisions A1/A2 and B1/B2 for single-core versus multicore cables; the Appendix 4 tables in BS 7671 do not use them — the single-core and multicore cases are separate tables instead.) Each method represents a different installation arrangement, from the most restrictive (enclosed in a thermally insulated wall) to the least restrictive (free air). Selecting the correct reference method is not optional — it is a required step in every cable sizing calculation. Table 4A2 is not a closed list: Regulation 521.2 permits other installation methods provided they meet the requirements of Chapter 52, and Appendix 4 notes that the evaluation of current-carrying capacity may then need to be based on experimental work.

In the app

BS 7671 Reference Method C: Current Capacity

BS 7671 Reference Method C for cables clipped direct to surface. Check Appendix 4:2026 current ratings in seconds. Avoid undersizing on site.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Technical Guide

Method A: Enclosed in a Thermally Insulated Wall

Method A covers cables in conduit inside a thermally insulated wall. Appendix 4 describes the wall precisely: an outer weatherproof skin, thermal insulation, and an inner skin of wood or wood-like material with a thermal conductance of at least 10 W/m²K. The conduit sits close to — but not necessarily touching — the inner skin, and heat from the cables is assumed to escape through the inner skin only. The conduit may be metal or plastic.

  • Installation Method 1: Non-sheathed cables in conduit in a thermally insulated wall. This is the most restrictive of the common reference methods and gives the lowest current-carrying capacities.
  • Installation Method 2: Multicore cable in conduit in a thermally insulated wall. Installation Method 3 covers a multicore cable run direct in the same wall construction. All three are read against Reference Method A.

Common mistake: conduit chased into masonry is not Method A. Appendix 4 defines masonry as brickwork, concrete, plaster and the like, explicitly excluding thermally insulating materials. Conduit in masonry of thermal resistivity not greater than 2 K.m/W is Reference Method B (Table 4A2, Installation Methods 59 and 60). Cable run direct in masonry with added mechanical protection such as capping is Reference Method C (Installation Method 58). Method A belongs to timber-framed and similar insulated wall constructions.

When it applies: Conduit run inside a timber-framed or otherwise thermally insulated wall, and — per Appendix 4 — a cable installed in a ceiling, which it treats as similar to Reference Method A. Appendix 4 also warns that higher ambient temperatures can arise in ceiling-mounted junction boxes serving luminaires, in the region of 40 °C to 50 °C, in which case a rating factor from Table 4B1 must be applied.

Capacity example: A 2.5 mm² T+E cable under Method A has a current-carrying capacity of just 20 A. Compare this with 27 A under Method C. That 7 A difference can determine whether you need to use 4 mm² cable instead of 2.5 mm².

03 · Technical Guide

Method B: Enclosed in Conduit or Trunking, or in Masonry

Method B covers cables enclosed in conduit or trunking on a wooden or masonry wall, and conduit or ducting buried in masonry. Appendix 4 describes the reference case as conduit mounted such that the gap between the conduit and the surface is less than 0.3 times the conduit diameter; the conduit may be metal or plastic. It notes that where the conduit is fixed to a masonry wall, rather than a wooden one, the actual capacity may be higher than tabulated.

  • Surface-mounted PVC or steel conduit on a wooden or masonry wall (Installation Methods 4 and 5)
  • Cables in cable trunking on a wooden or masonry wall, run horizontally or vertically (Installation Methods 6 to 9)
  • Conduit chased into masonry of thermal resistivity not greater than 2 K.m/W (Installation Methods 59 and 60)
  • Cable fixed directly under a wooden or masonry ceiling (Installation Methods 21 to 23) — Appendix 4 requires Method B here, not Method C, because natural air convection is reduced

Method B gives higher current-carrying capacities than Method A because the enclosure is not surrounded by thermal insulation. It is still lower than Method C (clipped direct) because the conduit or trunking restricts airflow around the cable. Note that the tabulated Method B values are for a single circuit: where more than one circuit shares the trunking, the group rating factor from Table 4C1 applies, whether or not there is an internal barrier or partition.

Common use: Commercial and industrial installations where cables are run in surface-mounted conduit or trunking for protection and appearance. Also used in domestic garages, workshops, and utility rooms where surface wiring is acceptable.

04 · Technical Guide

Method C: Clipped Direct to a Surface

Method C is the most common reference method for domestic installations using flat twin-and-earth (T+E) cable. Appendix 4 describes it as single-core or multicore cable fixed on, or spaced less than 0.3 times the cable diameter from, a wooden or masonry wall (Installation Method 20) — no conduit or trunking enclosure. Where the cable is fixed to or embedded in a masonry wall rather than a wooden one, Appendix 4 notes the actual capacity may be higher than tabulated.

  • T+E cable clipped to joists in a loft
  • T+E cable clipped to battens on a wall
  • Cable run direct in masonry with added mechanical protection such as capping (Installation Method 58)
  • SWA cable clipped to a wall with saddle clips
  • Cables on an unperforated tray (Installation Method 30) — with item 2 of Table 4C1 applied
  • Cable on a floor — Appendix 4 states Method C applies for current rating purposes

Method C provides good heat dissipation because the cable is in contact with the mounting surface on one side and exposed to air on the other. The mounting surface (wood, masonry, plaster) absorbs and conducts some heat away from the cable, while the exposed side radiates and convects heat into the air.

Watch the ceiling case. A cable clipped to joists is Method C, but a cable fixed directly under a wooden or masonry ceiling is Reference Method B in Table 4A2, because convection around the cable is reduced. And a T+E cable above a plasterboard ceiling or inside a stud wall containing thermal insulation is not Method C at all — it falls under Reference Methods 100 to 103, covered below.

Capacity example: A 2.5 mm² T+E cable under Method C has a current-carrying capacity of 27 A — a 35% increase over Method A (20 A) for the same cable. This is why the reference method selection has such a significant impact on cable sizing decisions.

Important note: If a cable that is mostly clipped to joists (Method C) passes through a section of conduit in a wall (Method B) or through a thermally insulated wall (Method A) at any point, the more restrictive method applies to the entire run. Design for the worst case.

05 · Technical Guide

Methods D1 and D2: In the Ground

BS 7671 splits the buried case into two reference methods, and mixing them up is a common source of undersized cable. This is the standard territory for armoured cable (SWA) runs supplying outbuildings, garages, garden offices, external lighting, and any other installation that requires an underground route.

  • Method D1 — in a duct: Multicore armoured cable in conduit or cable ducting in the ground (Table 4A2, Installation Method 70). The reference case is a 100 mm diameter plastic, earthenware or metallic duct in direct contact with the soil.
  • Method D2 — direct in the ground: Sheathed, armoured or multicore cable laid direct in the ground, with or without added mechanical protection such as cable covers (Installation Methods 72 and 73).
  • Reference conditions: Both D1 and D2 assume soil of thermal resistivity 2.5 K.m/W at a depth of 0.7 m. Appendix 4 calls these conservative parameters and points to the cable manufacturer or the ERA 69-30 series where the actual ground conditions are known. Use Table 4B3 for soil resistivities other than 2.5 K.m/W, Table 4B4 for laying depths other than 0.7 m, and Table 4B2 for ground temperatures other than 20 °C.
  • Cable protection: SWA cable provides its own mechanical protection via the steel wire armour. The cable is typically laid on a bed of fine sand or sieved fill, covered with more sand, and then protected with cable warning tiles or tape before backfilling. BS 7671 does not itself specify a burial depth — depth is set by the risk of disturbance at that location and by the relevant utility or site guidance, and any departure from 0.7 m is corrected using Table 4B4.

Method D is unique because the thermal environment (soil) is very different from air. The D1 and D2 capacities are given in separate columns of the armoured cable tables in Appendix 4 — Table 4D4A for 70 °C thermoplastic armoured cable and Table 4E4A for 90 °C thermosetting (XLPE) armoured cable. Grouping of buried cables (multiple circuits in the same trench) also has a significant impact: use Table 4C2 for cables buried directly in the ground and Table 4C3 for single cables in ducts buried in the ground — not the Table 4C1 factors used for cables in air.

06 · Technical Guide

Methods E, F, and G: Free Air Installation

Methods E, F and G all cover cables installed in free air — on perforated trays, ladders, brackets, cleats, ties or hangers — where air can circulate freely around the cable. These methods give the highest current-carrying capacities because heat dissipation is maximised. What separates E from F from G is not the support system, as is often assumed: Table 4A2 gives “E or F” for perforated tray, wire mesh tray, brackets, ladder and support wire alike. The split is by cable type and spacing.

Method E: Multicore Cable in Free Air

A multicore cable — two-core, three-core or four-core — in free air, for example on a horizontal or vertical perforated tray. Table 4C4, the grouping factor table for more than one multicore cable, is expressly for “multicore cables in free air — Reference Method E”. Common in commercial and industrial cable management for distribution cables and submains.

Method F: Single-Core Cables Touching, in Free Air

Single-core cables in free air in contact with one another — in trefoil, or laid flat and touching. Table 4C5, the grouping factor table for circuits of single-core cables, is expressly for “one circuit of single-core cables in free air — Reference Method F”. Typical of large power cables in industrial installations, switchrooms and plant rooms on ladder, tray or cleats.

Method G: Single-Core Cables Spaced, in Free Air

Single-core cables in free air spaced apart rather than touching — the Appendix 4 columns are based on a spacing of one cable diameter. Reducing mutual heating between the cables gives the highest capacities of the three free-air methods.

Appendix 4 sets thresholds for whether a support system counts as free air at all. A perforated tray must have a regular pattern of holes occupying at least 30 % of the base area — a tray with no holes, or with less than 30 % open area, is Reference Method C, not E or F. A ladder system qualifies where the metalwork under the cables occupies less than 10 % of the plan area. And free-air capacities may only be used where the clearance between the cable and any adjacent surface is at least 0.3 times the cable diameter for multicore cables, or 1.0 times the cable diameter for single-core cables.

These methods are rarely used in domestic work but are essential for commercial and industrial installations. The higher current-carrying capacities they provide can mean smaller (and cheaper) cables for the same circuit, which makes a significant cost difference on large installations with many long cable runs.

In the app

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

07 · Technical Guide

Methods 100 to 103: Flat Twin-and-Earth in Thermal Insulation

Alongside the lettered reference methods, Table 4A2 of BS 7671 carries a separate section headed “Installation methods for flat twin and earth cables in thermal insulation”, giving four numbered methods — 100, 101, 102 and 103. These are the methods that apply to almost every domestic rewire. They are not an On-Site Guide invention: they are in BS 7671 itself, and the ratings for all four come from Table 4D5.

  • Method 100: Flat twin-and-earth clipped direct to a wooden joist, or touching the plasterboard ceiling surface, above a plasterboard ceiling with thermal insulation not exceeding 100 mm in thickness (minimum U value 0.1 W/m²K).
  • Method 101: The same arrangement, but with the thermal insulation exceeding 100 mm in thickness. The extra insulation depth is the only difference between 100 and 101 — and it is the difference that most often gets missed on a loft that has since been topped up.
  • Method 102: Flat twin-and-earth in a stud wall containing thermal insulation, with the cable touching the inner wall surface (or touching the plasterboard ceiling surface), the inner skin having a minimum U value of 10 W/m²K.
  • Method 103: The same stud wall, but with the cable not touching the inner wall surface. Guides that stop at 102 miss this one — it is a distinct column in Table 4D5.

Table 4A2 adds the overriding instruction: wherever practicable, a cable is to be fixed in a position such that it will not be covered with thermal insulation, and points to Regulation 523.9 and BRE guidance on avoiding overheating. The IET On-Site Guide reproduces the same material in Tables 7.1(iii) and 7.1(iv), noting that Methods 100, 101 and 102 all require the cable to be in contact with the plasterboard or the joists. Where a cable is instead surrounded by thermal insulation for more than 0.5 m and no more precise information is available, the On-Site Guide requires the capacity to be taken as 0.5 times the Method C value.

Practical note: These scenarios are very common in domestic rewires and first-fix work. Any T+E cable that runs through a stud wall or above a plasterboard ceiling in a void containing thermal insulation must be assessed against Methods 100 to 103 rather than simply defaulting to Method C.

08 · Technical Guide

How to Choose the Right Reference Method

Selecting the correct reference method is a three-step process:

  1. Survey the entire cable route. Walk the route from the distribution board to the final point. Note every section: through the wall in conduit, clipped to joists, through a floor void, passing through insulation, on a tray, etc.
  2. Identify the reference method for each section. Find the numbered installation method that matches the physical arrangement in Table 4A2 of Appendix 4, then read across to the reference method column (for domestic final circuits, column 4 of Table 7.1(ii) of the IET On-Site Guide lists the installation methods the tabulated circuit lengths assume). Match the arrangement, not the name you would give it on site.
  3. Use the most restrictive method for the whole run. If the cable passes through multiple installation arrangements, the section with the lowest current-carrying capacity determines the reference method for the entire cable. Design for the worst case.

In practice, for most domestic work the choice is between Method C (clipped direct), Method B (conduit or trunking, including conduit chased into masonry, and cable fixed directly under a ceiling) and Methods 100 to 103 (T+E above a plasterboard ceiling or in an insulated stud wall). Method A only comes in where the wall is a thermally insulated construction. For commercial work with tray and trunking, you may be choosing between Method B (trunking) and Method E or F (perforated tray, ladder or cleats, depending on whether the cable is multicore or single-core). Always document your reference method choice — it forms part of the design records required by BS 7671.

In the app

70+ calculators built for UK electricians

Cable sizing, voltage drop, max demand, Zs, PFC, adiabatic equation, conduit fill, trunking fill, power factor, diversity factor…

09 · Technical Guide

Impact on Current-Carrying Capacity

The difference in current-carrying capacity between reference methods is substantial. Here is a comparison for common cable sizes using Table 4D5 (multicore PVC copper T+E):

Cable SizeMethod A (A)Method B (A)Method C (A)
1.5 mm²14.517.520
2.5 mm²202427
4 mm²273237
6 mm²344047
10 mm²465464
16 mm²617385

As you can see, the difference between Method A and Method C is approximately 25 to 40% for the same cable. This can easily mean the difference between a 2.5 mm² and a 4 mm² cable, or a 6 mm² and a 10 mm² cable. The cost and physical size difference is significant — especially for long runs or when conduit sizing is a constraint.

These tabulated values are before correction factors for grouping, ambient temperature, and thermal insulation are applied. After applying those factors, the effective capacity is lower still. The Elec-Mate cable sizing calculator handles all of this in one step.

10 · Technical Guide

Work Out the Derated Capacity for Your Reference Method

Free to use, and no sign-up or account needed.

The table above gives the tabulated current for each reference method. That figure is the starting point, not the answer. Take the value from the column for your reference method — 27 A for 2.5 mm² T+E on Method C, 20 A on Method A — enter it as the base current rating, then set the conditions the cable actually sees: ambient temperature, how many circuits are grouped together, whether it is surrounded by thermal insulation, and for a buried run the soil thermal resistivity and cable spacing.

The calculator applies the rating factors from Tables 4B1 (Ca), 4C1 and 4C2 (Cg), Appendix 4 Section 2.6 (Ci) and Table 4B3 (Cs), plus Cf for a BS 3036 semi-enclosed fuse and Cc for a buried installation, and returns Iz. Give it a design current and device rating as well and it checks Ib ≤ In ≤ Iz for you.

Cable Derating Calculator

Calculate cable current carrying capacity with BS 7671 derating factors

Circuit Design (Optional)

A
A

From BS 7671 current capacity tables

K·m/W

Standard is 2.5 K·m/W

Empty: Design Current (Ib), Base Current Rating.

Iz = It × Ca × Cg × Ci × Cs × Cf × Cc — the tabulated current from Appendix 4, reduced by every rating factor that applies. Size the cable so Iz is not less than the rating of the protective device (In).

11 · Technical Guide

Common Installation Scenarios

Here are the reference methods for the most common cable installation scenarios you will encounter:

Domestic Ring Final Circuit

T+E clipped to joists under the floor and dropping down through conduit chased into a masonry wall to socket outlets. The section clipped to joists is Method C; the conduit in masonry is Method B (Installation Methods 59 and 60), not Method A. Use Method B for the whole run. If the drop is instead in an insulated stud wall, it becomes Method 102 or 103.

Shower Circuit

Dedicated circuit from the consumer unit to the shower. Cable typically clipped to joists (Method C) then dropping through the bathroom wall in conduit chased into masonry (Method B). Use the most restrictive section — here, Method B. Where the run crosses a loft with insulation over it, Method 100 or 101 will usually govern instead. Given the high design current, the reference method has a significant impact on the cable size required.

SWA to Outbuilding

Armoured cable from the main distribution board, through the wall, buried in the ground across the garden, and into the outbuilding. The section inside each building clipped to the wall is Method C; the buried section is Method D2 if laid direct in the ground, or Method D1 if drawn into a duct. Size on the buried section — and check whether the ground conditions match the tabulated 2.5 K.m/W at 0.7 m before using the figures unadjusted.

Commercial Distribution

Submain cables on perforated cable tray from the main switchboard to a sub-distribution board. Method E for a multicore submain on the tray, or Method F for single-core cables touching (G if they are spaced). Check the tray is genuinely perforated — at least 30 % open base area — or it reverts to Method C. If the cable enters trunking at any point, that section becomes Method B. Use the most restrictive method, or size each section individually if the design allows.

Frequently Asked Questions About Reference Methods

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Cable Sizing with Automatic Reference Methods

Join 1,000+ UK electricians using Elec-Mate's 70+ calculators. Select the installation method, enter the conditions — cable sizing is done in seconds with the correct Appendix 4 table applied automatically. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy