Testing supplies the numbers that confirm or eliminate each candidate cause. Which tests you reach for depends on the symptom.
| Symptom | Tests to run |
|---|
| No power / circuit dead | Voltage at the consumer unit and at the affected accessory. Continuity of line and neutral conductors. Insulation resistance, to establish whether insulation failure is what operated the protective device. |
| RCD tripping | Milliamp clamp meter on the live circuit to measure standing earth leakage. Insulation resistance after safe isolation and load disconnection. RCD test to Regulation 643.8 to establish whether the device itself is at fault. |
| MCB tripping under load | Load current with a clamp meter to confirm or rule out genuine overload. Earth fault loop impedance to confirm the device will disconnect in time on a real fault. Insulation resistance to rule out breakdown between conductors. |
| Overheating or burning smell | Load current with a clamp meter. Thermal imaging to locate hot spots. Continuity and resistance at suspect connections to identify high-resistance joints. |
Insulation resistance — test voltages and minimum values
Regulation 643.3.2 requires insulation resistance to be measured at the test voltages in Table 64, with all final circuits connected but current-using equipment disconnected. The result is satisfactory if it is not less than the corresponding minimum value.
| Circuit nominal voltage | Test voltage (DC) | Minimum insulation resistance |
|---|
| SELV and PELV | 250 V | 0.5 MΩ |
| Up to and including 500 V, except the above systems | 500 V | 1.0 MΩ |
| Above 500 V | 1000 V | 1.0 MΩ |
A reading below the minimum points to insulation breakdown — but account for connected loads before you conclude that. Surge protective devices, electronic equipment and simple damp will all drag a reading down on otherwise sound wiring. Where connected equipment would influence the result or be damaged, Regulation 643.3.3 requires the Table 64 test to be applied before that equipment is connected, followed by a 250 V DC test between live conductors and the protective conductor once it is connected, with a minimum value of 1 MΩ. The insulation resistance testing guide sets out the full procedure.
Core diagnostic instruments
Voltage indicator (GS38)
Two-pole approved indicator for proving dead and confirming live voltage. Prove it on a known source or proving unit before and after use.
Low-resistance ohmmeter
Continuity of protective conductors and ring final circuits (R1+R2, R2). Null the leads before measuring.
Insulation resistance tester
Detects breakdown between live conductors, and between live conductors and Earth, at the Table 64 test voltage above.
Loop impedance tester
Measures Ze and Zs to confirm the protective device will disconnect within the maximum time that Regulation 411.3.2.2 applies to the circuit.
RCD tester
Verifies disconnection on an AC test at the rated residual operating current (IΔn), separating a faulty device from genuine earth leakage on the circuit.
Clamp meter (mA AC)
Load current for overload checks, and standing earth leakage on a live circuit to chase down nuisance tripping.
For RCDs used for additional protection, Regulation 643.8 requires verification with equipment to BS EN 61557-6. Its note states that, regardless of RCD type, effectiveness is deemed verified where the device disconnects within the stated time on an alternating current test at IΔn — a maximum of 300 ms for a general non-delay type. Table 3A, which previously gave the half-times and five-times criteria, was deleted at A4:2026.