SAFETY GUIDE

GS 38 Proving Dead: Test Equipment Requirements

HSE Guidance Note GS 38 sets the standard for electrical test equipment. Proving units, voltage indicators, fused probes, the 4 mm probe tip rule, and the prove-test-prove procedure. This guide covers everything electricians need to know about safe testing.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

9 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is GS38 and what does proving dead mean?

GS38 is the HSE guidance note on electrical test equipment for use by electricians. It sets out how voltage indicators, test probes and leads must be designed and used safely — finger barriers, minimal exposed metal at the probe tips, fused leads and clear ratings. Proving dead means confirming a circuit is isolated using an approved voltage indicator, after first verifying that indicator works on a known live source or proving unit.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1GS 38 is an HSE Guidance Note titled "Electrical test equipment for use on low voltage electrical systems." It specifies the requirements for electrical test equipment used when proving circuits dead. It is the accepted industry standard for safe testing.
  • 2A two-pole voltage indicator (not a multimeter) is strongly recommended by GS 38 for proving dead, as it has fewer failure modes and does not rely on batteries or correct range selection.
  • 3Test leads must be fused with a maximum 500 mA HBC fuse as close as possible to the probe tip, and probe tips must be spring-loaded with no more than 4 mm of exposed metal.
  • 4The prove-test-prove procedure is mandatory: prove the voltage indicator works on a known live source, test the circuit being worked on, then prove the indicator still works afterwards.
  • 5Elec-Mate AI tools and training courses cover safe isolation procedures, GS 38 compliance, and test equipment requirements to keep your team competent and compliant.
01 · Safety Guide

What Is GS 38?

GS 38 is a Guidance Note published by the Health and Safety Executive (HSE) titled "Electrical test equipment for use on low voltage electrical systems." It specifies the requirements for test probes, test leads, voltage indicators, and proving units used when proving circuits dead before work begins.

The guidance was introduced because electricians were being injured and killed by electric shock while testing circuits they believed to be dead. In many cases, the test equipment being used was inadequate — unfused leads with long exposed probe tips, multimeters set to the wrong range, or voltage indicators with flat batteries that gave a false "dead" reading. GS 38 addresses these specific failure modes by setting minimum standards for test equipment design and use.

Although GS 38 is guidance rather than regulation, it represents the accepted industry standard. The Electricity at Work Regulations 1989 require work on electrical systems to be carried out in a manner that prevents danger — and using test equipment that meets GS 38 standards is the recognised way of satisfying this duty when proving circuits dead. All competent person schemes (NICEIC, NAPIT, ELECSA), all training providers, and the HSE itself treat GS 38 compliance as the baseline requirement.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Safety Guide

Proving Unit Requirements

A proving unit is a battery-powered device that generates a known voltage output to verify that your voltage indicator is functioning correctly. It is an essential piece of test equipment — without it, you cannot carry out the prove-test-prove procedure that is central to safe isolation.

  • Known voltage output — the proving unit must generate a reliable, known voltage within the detection range of your voltage indicator. Most produce around 50V AC or 230V AC equivalent.
  • Compatibility — the proving unit must be compatible with your specific voltage indicator. Some indicators have matching proving units from the same manufacturer.
  • Battery condition — check the battery before each use. A proving unit with a flat battery will not produce the required test voltage. Carry spare batteries.
  • Portability — the proving unit must be portable enough to carry to the point of work. You need it at the point of isolation, not back in the van.
03 · Safety Guide

Voltage Indicator Requirements

GS 38 strongly recommends a dedicated two-pole voltage indicator for proving circuits dead. A two-pole indicator is preferred over a multimeter because it has fewer failure modes:

  • No battery dependency for basic function — most two-pole voltage indicators use the voltage being measured to power the indication (LEDs or neon lamps). A flat battery may disable additional features but the basic voltage detection still works.
  • No range selector — multimeters require the user to select the correct range and function. Selecting the wrong function can give a misleading reading. A two-pole indicator is always in voltage detection mode.
  • No internal fuse dependency — multimeters have internal fuses that can blow without the user noticing, potentially giving a false dead reading. Two-pole indicators do not have this failure mode.
  • Clear indication — voltage indicators provide an unambiguous live/dead indication (usually LEDs and an audible tone). No need to interpret a numerical reading.

Popular GS 38 compliant voltage indicators include the Fluke T-series, Megger TPT, and Martindale VI-13800. Ensure your indicator meets the category rating requirements for your work (CAT III minimum for distribution-level testing, CAT IV at the supply origin).

04 · Safety Guide

Fused Probes and Test Leads

The test leads and probes are just as important as the voltage indicator itself. GS 38 specifies detailed requirements for test lead construction:

  • Fused leads — each test lead must contain a fuse rated at no more than 500 mA (HBC). The fuse must be located as close as possible to the probe tip. This limits the energy available in the event of an accidental short circuit.
  • Finger guards — test probes must have barriers that prevent the user's fingers from sliding forward and contacting live parts. The guard must provide genuine physical protection.
  • Insulation — test leads must be fully insulated along their entire length. No exposed metal other than the probe tip. No cracks, cuts, abrasion, or deterioration.
  • Lead length — keep test leads as short as practical. Most GS 38 compliant leads are approximately 1.2 metres in length.

Always carry spare fuses for your test leads. If a fuse blows during testing, investigate why before simply replacing it — it may indicate a live circuit.

AI-generated RAMS include GS 38 procedures

Every risk assessment and method statement generated by Elec-Mate's AI Health and Safety agent includes the correct safe isolation procedure referencing…

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · Safety Guide

IP Rating and Probe Tips

The probe tips are the most critical safety feature of your test leads. GS 38 specifies:

  • Maximum 4 mm exposed metal — the conductive tip must not extend more than 4 mm beyond the insulating shroud. This limits probe penetration into a terminal, reducing the risk of bridging between adjacent live conductors.
  • Spring-loaded shrouds — the probe tips should have spring-loaded insulating shrouds that cover the exposed metal when not being pressed against a conductor.
  • Robust construction — probe tips must withstand normal use without bending, breaking, or becoming loose. Damaged probe tips must be replaced immediately.

Many older test leads do not meet these requirements. Long, sharp, fully exposed probe tips are still commonly seen on site, but they are non-compliant and dangerous. Replace any leads that do not meet the 4 mm maximum and spring-loaded shroud requirements.

Generate RAMS in minutes

Site-specific risk assessments and method statements, written to CDM 2015 expectations and ready to send. From £6.99/mo.

Try the safety tools free
Download on the App StoreGet it on Google Play
06 · Safety Guide

The Prove-Test-Prove Procedure

The prove-test-prove procedure is the cornerstone of safe working on electrical circuits. It has three steps:

1

PROVE — Test on Known Live Source

Use your proving unit to verify that the voltage indicator is working correctly. The indicator should clearly detect the voltage. If it does not respond, the indicator is faulty — do not use it.

1b

SECURE — Lock Off the Isolation Point

Before approaching the load, secure the isolation device against inadvertent re-energisation. Fit a personal padlock to the isolating device and apply a warning label or tag at the point of isolation. Where you are not in full control of all isolation points, every point shall be locked off (OSG 12.5). BS 7671 Regulation 462.1 requires that isolation provisions allow the installation to be worked on safely — securing against re-connection is integral to satisfying this requirement.

2

TEST — Test the Circuit

Test at the load side of the isolation device — not the supply side. This is a critical spatial requirement: testing the supply side of the isolator will always read live and give a false sense of security. Test between all combinations at the load side and at the point of work: line to neutral, line to earth, and neutral to earth. If the indicator shows no voltage on any combination, the circuit appears dead. If voltage is detected, the circuit is still live — do not proceed.

3

PROVE — Retest on Known Live Source

Use the proving unit again to confirm the voltage indicator is still working correctly. If the indicator responds normally, the test result is valid and the circuit can be confirmed as dead. If it fails, the test result cannot be trusted — replace the indicator and repeat the entire procedure.

Multiple-Supply Installations

Isolating the incoming mains supply may not render all conductors dead. Modern installations increasingly include solar PV inverters, battery storage systems, EV chargers, or standby generators that can back-feed conductors even with the main switch open. GN3 Regulation 2.9 requires a multiple-supplies warning notice at distribution boards where alternative voltage sources are present. BS 7671 Regulation 462.1 requires that isolation provisions are provided for each source of supply. Always check for an alternative-supply notice before commencing work, and prove dead at the actual point of work — not just at the board.

Semiconductor Devices Cannot Be Used to Isolate

BS 7671 Regulation 537.2.2 prohibits using semiconductor devices as the means of isolation. Variable speed drives (VSDs), soft starters, solid state relays, AFDD electronics, and smart switching modules are all semiconductor-based — none of them constitute a safe means of isolation, even when in an off state. A mechanical isolator (fused isolator, switch-disconnector, or MCB with visible contacts) must always be used as the isolation point before proving dead.

07 · Safety Guide

Common GS 38 Non-Compliance Issues

  • Long exposed probe tips — using test leads with probe tips longer than 4 mm. This is the most common non-compliance issue and significantly increases the risk of accidental short circuits.
  • No fuses in test leads — using unfused test leads or leads where the fuses have been removed. This removes the energy-limiting protection that prevents severe arc flash.
  • Using a multimeter without proving unit — relying on a multimeter reading without first proving the instrument works. A multimeter on the wrong range can display zero volts on a live circuit.
  • Skipping the second prove — testing the circuit but not re-proving the voltage indicator afterwards. The second prove catches a voltage indicator fault that occurred during testing.
  • Damaged or worn test leads — continuing to use test leads with cracked insulation, worn probe tips, or non-functioning spring shrouds.
08 · Safety Guide

Test Equipment Maintenance and Calibration

Maintaining your test equipment in good condition is essential for safety and compliance.

  • Visual inspection before every use — check the voltage indicator body, test leads for insulation damage, probe tips for wear, fuses for presence, and spring-loaded shrouds for functioning.
  • Calibration — voltage indicators and multifunction testers should be calibrated at the manufacturer-recommended intervals, typically every 12 months. Use a UKAS accredited laboratory. Keep the calibration certificate on file.
  • Spare fuses and batteries — always carry spare fuses for test leads (500 mA HBC) and spare batteries for the proving unit.
  • Storage — store test equipment in a protective case away from damp, dust, extreme temperatures, and mechanical damage.

Elec-Mate inspection and testing training courses cover GS 38 compliance, test equipment requirements, and the prove-test-prove procedure in detail. The RAMS generator includes GS 38 references in every risk assessment and method statement it produces.

Track calibration dates and training certificates

Elec-Mate's site safety tools help you manage test equipment calibration dates, PPE inspection records, and training certificates.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About GS 38 and Proving Dead

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Stay Safe with Proper Test Procedures

Join 1,000+ UK electricians using Elec-Mate for AI-powered RAMS generation, safety training courses, and professional certification tools. GS 38 procedures are built into every assessment. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy