No Power to Sockets? Systematic Troubleshooting Guide
Dead sockets can be caused by a simple tripped MCB, a broken ring circuit, a loose connection, or a blown spur fuse. This guide covers every common cause, explains what homeowners can check safely, and provides a structured diagnostic approach for electricians.
The most common cause is a tripped MCB or RCD at the consumer unit, so check there first. If only some sockets on one circuit are dead, suspect a broken ring final circuit or a loose connection. A single dead socket or appliance often means a blown fuse in a fused spur. If everything is off and neighbours are affected too, it is a supply fault — call 105.
You can safely reset a tripped breaker and replace a blown BS 1362 fuse in a fused connection unit. Any fault needing work behind a socket faceplate or inside the consumer unit should be left to a qualified electrician.
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1The most common cause of dead sockets is a tripped MCB or RCD at the consumer unit — always check the consumer unit first before investigating further.
2A broken ring circuit (cable damage, disconnected joint, or failed connection at a socket) can leave multiple sockets dead while others on the same circuit continue to work.
3Loose connections at socket terminals, junction boxes, or the distribution board are a frequent cause of intermittent or permanent power loss to individual sockets.
4Fused spurs protect equipment on a spur from the ring circuit — a blown fuse in a fused connection unit (FCU) will kill power to everything downstream of that spur, leaving the ring unaffected.
5Elec-Mate's AI fault diagnosis tool walks you through a structured dead-socket diagnosis, helping you identify whether the cause is a tripped protective device, a broken ring, a loose connection, or a spur fault.
01 · Troubleshooting
Common Causes of Dead Sockets at a Glance
Dead sockets almost always trace back to one of five causes. Use this table to match your symptoms to the most likely fault, see whether it is a safe homeowner check or a job for a qualified electrician, and jump to the detailed section below.
Cause
Typical symptom
Who fixes it
More detail
Tripped MCB / RCD / RCBO
All sockets dead, or a whole half of the board off. A switch sits in the down or middle position at the consumer unit.
Safe to do yourself: resetting a tripped MCB or RCD, and replacing a blown BS 1362 fuse in a fused connection unit. Always an electrician: anything behind a socket faceplate or inside the consumer unit. That work is on the fixed installation, can be dangerous, and may be notifiable under Part P of the Building Regulations.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Troubleshooting
Initial Checks Before Calling an Electrician
Before calling an electrician for dead sockets, there are a few simple checks that any homeowner or tenant can perform safely. These checks do not involve opening any socket faceplates or touching any live parts — they only require looking at the consumer unit and testing a few appliances.
Check the consumer unit. Open the cover and look for any tripped switches. If an MCB or RCD is in the down or middle position, that circuit has tripped. Try resetting it (push it firmly to the up position). If it holds, the problem may be resolved. If it trips immediately, leave it off and call an electrician.
Check whether other sockets in the property work. Test sockets in different rooms. If all sockets are dead, the RCD protecting the socket circuits may have tripped. If only sockets in one area are dead, the fault may be on one specific circuit.
Check the appliance, not the socket. Try plugging a known-working appliance (a lamp, a phone charger) into the suspect socket. If the appliance works, the problem was with the original appliance, not the socket.
Check for blown FCU fuses. If the dead socket is supplied via a fused connection unit (common for kitchen worktop sockets, extractor fans, and outdoor sockets), check whether the FCU fuse has blown. The FCU is the small rectangular unit with a fuse carrier on the front.
Check whether neighbours are affected. If all power is off (not just sockets), check whether your neighbours have power. If they do not, the problem is with the supply — contact your electricity supplier, not an electrician.
If these checks do not resolve the issue, the fault is likely in the fixed wiring and you should call a qualified electrician. Do not attempt to open socket faceplates or work inside the consumer unit — these tasks require a competent person working to safe isolation procedures.
03 · Troubleshooting
Tripped MCB or RCD
The most common cause of dead sockets is a tripped protective device at the consumer unit. This can be an MCB (miniature circuit breaker), an RCD (residual current device), or an RCBO (combined MCB and RCD). The device trips to protect the circuit from a fault — the socket itself is fine, it simply has no supply because the protective device has disconnected it.
MCB Trip — Overcurrent or Short Circuit
An MCB trips when the current on the circuit exceeds the MCB rating (typically 32 A for a socket circuit). This can be caused by an overloaded circuit (too many high-power appliances on one circuit), a short circuit in an appliance or the wiring, or a fault in the cable. If the MCB trips immediately on reset, do not keep resetting it — there is a fault that must be investigated. Disconnect all appliances from the circuit and try resetting. If it holds with nothing plugged in, reconnect appliances one at a time to find the faulty one.
RCD Trip — Earth Leakage
An RCD trips when it detects earth leakage current exceeding its sensitivity (typically 30 mA). On a split-load consumer unit, one RCD may protect half the circuits — so a single RCD trip can kill power to multiple socket circuits and lighting circuits simultaneously. Common causes include a faulty appliance leaking to earth, moisture in an outdoor socket or connection, or cumulative earth leakage from multiple appliances. Reset the RCD after disconnecting suspect appliances.
RCBO Trip — Circuit-Specific Protection
On a modern RCBO board, each circuit has its own combined overcurrent and earth leakage protection. If an RCBO trips, only that one circuit loses power. This makes diagnosis easier — you know exactly which circuit has the fault. The RCBO may have tripped due to overcurrent, earth leakage, or both. The diagnostic approach is the same: disconnect appliances, reset, and reconnect one at a time.
Why one RCD trip can kill both sockets and lights — BS 7671:2018+A4:2026 Reg 411.3.4
A common source of homeowner confusion on split-load boards is that a single RCD trip kills both socket circuits and lighting circuits simultaneously. This is explained by Regulation 411.3.4 of BS 7671:2018+A4:2026, which requires that, in domestic premises, AC final circuits supplying luminaires shall be provided with additional protection by an RCD with a rated residual operating current not exceeding 30 mA. Because domestic lighting circuits now require the same 30 mA RCD protection as socket circuits, both circuit types sit behind the same RCD on a split-load board — so an earth leakage fault on any one circuit, whether a socket or a light fitting, can trip the RCD protecting both.
04 · Troubleshooting
Broken Ring Circuit
In UK domestic installations, socket outlets are typically wired as ring final circuits. The cable runs from the MCB at the consumer unit, visits each socket in turn, and returns to the same MCB terminal — forming a complete ring. If this ring is broken at any point, the consequences depend on where the break occurs and how many sockets are between the break and the return path.
Complete break: If the cable is completely severed (a nail through both conductors, a joint pulled apart), all sockets beyond the break — when measured from both directions around the ring — will lose power. The sockets before the break on each leg of the ring will continue to work.
Single conductor break: If only the line conductor is broken (but the neutral and CPC are intact), the affected sockets will be dead. If only the neutral is broken, the sockets may appear dead or may behave erratically (depending on the load conditions on the circuit).
CPC break only: If only the earth conductor (CPC) is broken, the sockets will still work (power is present) but the earth path is compromised. This is dangerous because the protective device cannot disconnect quickly enough in the event of an earth fault. An earth loop impedance test will reveal the high Zs.
To identify a broken ring, perform the ring final circuit continuity test at the distribution board — the live-conductor continuity measurement required for ring final circuits by Regulation 643.2.1 of BS 7671:2018+A4:2026. Disconnect both ends of the ring (line, neutral, and CPC at both legs). Measure R1 (end-to-end line conductor resistance), Rn (end-to-end neutral conductor resistance), and R2 (end-to-end CPC resistance). If any of these reads open circuit, the ring is broken on that conductor. Cross-connect the conductors and measure the resistance between the line and CPC at each socket around the ring to locate the break point.
Pass/fail criterion — GN3 Reg 2.20
When the CPC is the same cross-sectional area and material as the line conductor (standard 2.5/1.5 mm² twin-and-earth), the line-to-CPC resistance measured at each socket-outlet around the ring will be substantially the same — approximately one quarter of the total line-plus-CPC loop resistance. Readings that are substantially equal confirm acceptable ring continuity. A significant outlier (a reading materially higher than the others) at a particular socket indicates a high-resistance joint or partial break at or between that socket, and shall be investigated — it is not sufficient to confirm only that no socket reads open circuit.
Ring circuit calculator for fault diagnosis
Enter your R1, Rn, and R2 values into Elec-Mate's ring circuit calculator. The app validates the ring integrity, flags any anomalies…
Loose connections are a common cause of both intermittent and permanent power loss to individual sockets. On a ring circuit, each socket has at least four terminal connections (line in, line out, neutral in, neutral out — plus two earth connections). Any one of these can loosen over time, and the consequences depend on which connection fails.
Line conductor loose at socket: If the line connection to the incoming cable is loose, that socket and all sockets downstream (on that leg of the ring) may lose power. If it is the outgoing cable that is loose, only downstream sockets are affected.
Neutral conductor loose: A loose neutral at a socket can cause intermittent operation — the socket may work with light loads but fail under heavy loads when the higher current causes the loose connection to open.
Junction box connections: Junction boxes under floors and in loft spaces can develop loose connections due to vibration, thermal cycling, and poor initial workmanship. A failed junction box connection has the same effect as a cable break at that point.
Distribution board terminals: A loose connection at the MCB terminal will affect the entire circuit — all sockets on that circuit will be dead. Check both the line connection at the MCB and the neutral connection at the neutral bar.
Warning signs of a loose connection include intermittent power, sparking when plugging in appliances, a warm socket faceplate, discolouration around the socket pins, and a burning smell. Any of these signs should be investigated immediately — loose connections that arc are a significant fire risk. If you find evidence of arcing, the socket must be replaced and the finding recorded on the EICR as a C1 or C2 observation.
Arcing at a loose socket terminal is precisely the hazard that arc fault detection devices (AFDDs) are designed to detect. Regulation 421.1.7 of BS 7671:2018+A4:2026 now requires AFDDs conforming to BS EN 62606 for single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes. For all other premises — including ordinary domestic installations — AFDDs are recommended for those socket circuits. Where used, the AFDD must be placed at the origin of the circuit it protects, and it does not remove the need for the other protective measures in the standard.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
A spur is a branch circuit taken from a ring circuit (or radial circuit) to supply one or more additional socket outlets or a specific piece of equipment. Spurs can be unfused (one socket connected directly to a socket on the ring) or fused (connected through a fused connection unit with a cartridge fuse). Faults on spurs can cause dead sockets while the main ring continues to work normally.
Blown Fuse in FCU
The most common spur fault. The cartridge fuse in the FCU (fused connection unit) has blown, cutting power to everything downstream. Common causes include an overloaded appliance, a short circuit in the equipment connected to the spur, or simply a fuse that has reached end of life. Remove the fuse carrier, test or replace the fuse, and restore power. If the new fuse blows immediately, there is a fault on the spur that must be investigated.
Disconnected Spur at the Ring
The spur cable connects to the ring at a socket or junction box. If this connection has failed (loose terminal, pulled-out conductor), the spur socket loses power while the ring continues to work. This is particularly common when spurs are connected at sockets — the socket has three sets of cables (two ring legs plus the spur), and the terminals can become overloaded.
Cable Damage on the Spur
The spur cable itself may be damaged — a nail through the cable under the floorboard, rodent damage, or a crushed cable. This creates the same effect as a broken ring but on the spur only. The spur socket is dead, the ring works. An insulation resistance test on the spur cable will typically reveal the fault.
To determine whether a dead socket is on a spur or on the ring, check the number of cables at the socket. A ring socket typically has two cables (one from each direction around the ring). A spur socket typically has one cable (from the ring connection point). A socket where the spur originates may have three cables (two ring legs plus the spur).
07 · Troubleshooting
Systematic Diagnosis Approach for Electricians
When called to diagnose dead sockets, follow this structured approach to identify the cause efficiently and avoid wasting time:
Tools you will need
Low-reading ohmmeter — a standard continuity buzzer is not sufficient for ring circuit continuity work; you need an instrument capable of resolving milliohm differences to detect high-resistance joints.
Proving unit — used to confirm your voltage indicator is functioning correctly before and after proving dead (prove — test — prove sequence).
Two-pole voltage indicator (GS38 compliant) — for proving the circuit dead before opening any socket faceplate.
Common mistake: Do not test continuity without fully isolating adjacent live circuits. Energised parallel paths — for example, a bonding conductor or a second circuit sharing a common neutral — will give false low readings on the ohmmeter, making a broken conductor appear intact. Isolate the circuit under test completely before measuring.
Check the consumer unit. Is the MCB for the socket circuit in the on position? Is the RCD protecting that circuit in the on position? If either has tripped, investigate why before simply resetting.
Determine the scope. How many sockets are dead? Which rooms? Use a socket tester or voltage indicator to test multiple sockets. Map the dead sockets against the circuit chart (if one exists) to understand which circuit is affected.
Check for tripped FCUs. Walk around and check all fused connection units on the affected circuit. An FCU with a blown fuse will have no neon indicator (if fitted). Check the fuse with a continuity tester.
Perform safe isolation. Isolate the circuit at the consumer unit. Lock off and prove dead at the point of work.
Test the ring circuit continuity. At the distribution board, disconnect both ends of the ring. Test R1, Rn, and R2 end-to-end. An open circuit on any conductor confirms a broken ring.
Cross-connect and test at each socket. If the ring is broken, perform the cross-connected (figure-of-eight) test, measuring at each socket around the ring. The readings will be anomalous at the socket where the break occurs — this locates the fault.
Inspect connections. At the socket nearest to the identified fault location, open the faceplate and inspect the terminal connections. Look for loose conductors, evidence of arcing, heat damage, and pulled-out wires.
Test insulation resistance. Perform an insulation resistance test on the affected section to check for cable damage.
AI-guided fault diagnosis
Describe the dead socket symptoms to Elec-Mate's AI fault diagnosis tool — how many sockets are affected, which rooms…
When investigating dead sockets, safety must come first. Even a socket that appears dead may have a live conductor present — a loose neutral can leave the line conductor energised with no apparent load. Always follow the safe isolation procedure before opening any socket faceplate or making any physical contact with conductors.
Use a voltage indicator, not a neon screwdriver. A two-pole voltage indicator (GS38 compliant) is the only reliable way to test for the presence of voltage. Neon screwdrivers can give false readings and are not suitable for proving dead.
Prove — test — prove. Before testing the dead socket, prove your voltage indicator on a known live source. Then test the dead socket. Then prove the indicator again on the known live source. This confirms the indicator was working correctly during the test.
Lock off at the consumer unit. Switch off the MCB, apply a lock-off device, and attach a warning tag. This prevents anyone from re-energising the circuit while you are working on it.
Beware of back-fed circuits. On a ring circuit, isolating the MCB disconnects the supply from the consumer unit, but if the ring has a connection to another circuit (a borrowed neutral, for example), there may still be voltage present. Always prove dead at the point of work, not just at the consumer unit.
After completing the diagnosis and repair, re-test the affected sockets with a socket tester to confirm correct wiring (polarity, earth present). Record test results on the schedule of test results and issue the appropriate certificate for the remedial work. Elec-Mate's EICR certificate app lets you capture all test results by voice, classify any observations with AI-suggested defect codes, and generate a professional PDF certificate from site.
Complete certificates on site — send before you leave
Elec-Mate's digital EICR and Minor Works certificates capture test results by voice, suggest defect codes with AI, and export as professional PDFs.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Diagnose Socket Faults with Elec-Mate
AI fault diagnosis, ring circuit calculator, digital EICR certificates, and voice test entry. Join 1,000+ UK electricians using Elec-Mate. 7-day free trial, cancel anytime.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy