BS 7671 TESTING

Prospective Fault Current PFC Guide for BS 7671

The complete guide to prospective fault current (PFC/Ipf). What it is, why it matters, how to measure it on site, typical values for domestic and commercial installations, breaking capacity of MCBs and fuses, and the BS 7671 regulatory requirements under Regulation 434.5.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-07-02Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What is prospective fault current (PFC)?

Prospective fault current (PFC, or Ipf) is the maximum current that would flow if a fault of negligible impedance occurred — taken as the greater of the prospective short-circuit current (line-to-neutral) and the prospective earth fault current. It is measured at the origin and recorded on the certificate. Under BS 7671 Reg 434.5.1, every protective device must have a rated breaking capacity not less than the PFC at its point of installation.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Prospective fault current (PFC or Ipf) is the maximum current that would flow under a short-circuit or earth fault condition — every protective device must be capable of safely interrupting this current.
  • 2PFC must be measured, calculated, or determined at the origin of every installation and at every relevant point — defined in GN3 as every point where a protective device is required to operate under fault conditions. The highest value (typically the line-to-neutral short circuit) is the one that matters.
  • 3Typical domestic PFC values range from 1kA to 6kA. Standard domestic MCBs to BS EN 60898 have a minimum breaking capacity of 6kA — but installations close to transformers can exceed this.
  • 4PFC is directly related to Ze: the lower the Ze (earth fault loop impedance at the origin), the higher the prospective fault current. TN-C-S supplies with low Ze can have high PFC values.
  • 5Elec-Mate's PFC calculator and adiabatic calculator verify that protective devices and cables can handle the fault current. Schedule of tests validates PFC values against device ratings automatically.
  • 6Where site measurement is not possible before energisation — for example on a new installation — PFC may be determined by enquiry to the DNO/distributor, who can provide Ze and Ipsc figures for the supply point (OSG Reg 1.2.7).
  • 7Appendix 14 of BS 7671 contains worked examples for calculating Ips at relevant points in the installation. The Elec-Mate PFC calculator applies the same methodology.
01 · BS 7671 Testing

What Is Prospective Fault Current?

Prospective fault current (PFC), also written as Ipf or PSCC (prospective short-circuit current), is the maximum current that would flow at a given point in an electrical installation if a fault of negligible impedance occurred at that point. It represents the worst-case scenario — the absolute maximum current the supply can deliver into a dead short circuit or a solid earth fault.

There are two types of prospective fault current to consider. The first is the prospective short-circuit current — the current that would flow if the line and neutral conductors were connected directly together (a dead short). This is typically the higher value. The second is the prospective earth fault current — the current that would flow if the line conductor made direct contact with the earth conductor or an earthed metallic part. This is related to the earth fault loop impedance (Ze).

PFC is determined by the supply impedance — the impedance of the path from the supply transformer to the point of measurement. The lower the impedance, the higher the prospective fault current. A property close to the transformer with a large supply cable has low impedance and therefore high PFC. A property at the end of a long supply run has high impedance and therefore lower PFC.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · BS 7671 Testing

Why PFC Matters

PFC matters for one critical reason: every protective device in the installation must be capable of safely interrupting the maximum fault current that could flow at the point where it is installed. This is a fundamental safety requirement set out in BS 7671 Regulation 434.5.1.

When a short circuit or earth fault occurs, an enormous current flows — potentially thousands of amperes. The protective device (MCB, RCBO, fuse) must interrupt this current safely, containing the arc within the device enclosure and disconnecting the circuit without fire, explosion, or danger to persons. If the fault current exceeds the device's rated breaking capacity, the device may fail catastrophically.

What happens when PFC exceeds breaking capacity

If the prospective fault current exceeds the breaking capacity of a protective device, the consequences can include: device contacts welding together (failing to disconnect), the device exploding and ejecting fragments of plastic and metal, sustained arcing that ignites the consumer unit or surrounding materials, and cascading failure of adjacent devices. This is not a theoretical risk — it is the reason PFC must be measured and verified on every installation.

PFC also matters for cable protection. The adiabatic equation (k²S² ≥ I²t) verifies that the cable conductor can withstand the heating effect of the fault current for the duration of the disconnection time. If the PFC is very high and the disconnection time is not short enough, the cable can be damaged by the fault current — the conductor can overheat, melting the insulation and creating a fire risk.

PFC calculator and adiabatic verification

Elec-Mate's PFC calculator determines the fault current from supply impedance. The adiabatic calculator then verifies the cable can withstand it.

Try it free for 7 days
Download on the App StoreGet it on Google Play
03 · BS 7671 Testing

How to Measure PFC

PFC is measured using a multifunction tester (MFT) or a dedicated loop impedance tester. Most modern MFTs have a PFC function that measures the supply impedance and calculates the maximum fault current automatically. Where site measurement is not yet possible — for example on a new installation before energisation — PFC may be determined by enquiry to the DNO/distributor, who can supply Ze and prospective short-circuit current (Ipsc) figures for the supply point. The OSG states that measurement shall be made ‘if not determined by enquiry of the distributor’, so the two routes are equally valid under BS 7671.

Defining ‘every relevant point’ — GN3 Reg 2.29

Reg 643.7.3.201 requires PFC to be determined at the origin and at every other relevant point. GN3 Reg 2.29 defines this precisely: “every relevant point shall mean every point where a protective device is required to operate under fault conditions, and includes the origin of the installation.” For a large commercial switchboard feeding multiple MCCBs, each MCCB location is a relevant point — not only the incoming incomer. Appendix 14 of BS 7671 provides worked examples of Ips determination at such points.

At the Origin

PFC is measured at the origin of the installation — typically at the consumer unit or main distribution board. Connect the test instrument to the line, neutral, and earth terminals at the main switch (incoming side). The instrument measures both the line-to-neutral impedance and the line-to-earth impedance (Ze), then calculates the PFC from each. The higher of the two values is the prospective fault current that must be recorded on the certificate. Most instruments display the PFC value directly in kA (kiloamperes).

At Sub-Distribution Boards

PFC should also be measured at each sub-distribution board in the installation. The PFC at a sub-board is always lower than at the origin because the impedance of the submain cable between the main board and the sub-board adds to the total fault loop impedance, reducing the fault current. Connect the instrument to the incoming terminals of the sub-board and measure in the same way. The PFC at each board must not exceed the breaking capacity of the protective devices installed at that board.

Recording on Certificates

The measured PFC is recorded in the "Prospective fault current Ipf" field on the EIC or EICR. Record the highest value (typically the line-to-neutral PFC). On the EICR, the PFC at the origin is recorded in the Supply Characteristics section. If the PFC exceeds the breaking capacity of any installed device, this must be recorded as an observation with the appropriate classification code.

04 · BS 7671 Testing

Typical PFC Values

PFC values vary widely depending on the supply characteristics, the distance from the transformer, and the type of installation. Here are typical ranges for UK installations.

Typical PFC ranges by installation type

Domestic (end of long run)

0.5 — 2 kA

Domestic (typical urban)

2 — 4 kA

Domestic (near transformer)

4 — 8 kA

Commercial (small)

6 — 16 kA

Commercial/industrial (large)

16 — 50+ kA

Properties immediately adjacent to a ground-mounted transformer (pad-mount or mini-pillar) on a TN-C-S supply can have PFC values that exceed the 6kA breaking capacity of standard domestic MCBs. This is not unusual — it is simply a consequence of the very low supply impedance at close range. In these cases, higher-rated devices must be installed.

05 · BS 7671 Testing

Breaking Capacity of Protective Devices

Breaking capacity (also called rated short-circuit capacity) is the maximum fault current that a protective device has been tested and certified to safely interrupt. The device must be able to contain the arc, extinguish it, and open the circuit without fire, explosion, or danger. Different device types and standards specify different breaking capacities.

Common device breaking capacities

MCB (BS EN 60898)

6kA minimum (standard domestic), 10kA, 15kA available

MCB (BS EN 60947-2)

10kA, 16kA, 25kA, 36kA, 50kA (industrial)

RCBO (BS EN 61009)

6kA minimum (domestic), 10kA available

HRC fuse (BS 88)

80kA typical — very high breaking capacity

BS 3036 rewirable fuse

1kA to 4kA — very low breaking capacity

MCCB (moulded case)

16kA to 150kA depending on frame size

A critical point: BS 3036 rewirable fuses have very low breaking capacities, typically 1kA to 4kA. On many modern supplies with PFC values of 3kA or more, the BS 3036 fuse may not have adequate breaking capacity. This is one of the reasons why BS 3036 fuse boards are often identified as requiring upgrade during periodic inspection.

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
06 · BS 7671 Testing

PFC and Ze — The Relationship

Prospective fault current and Ze (external earth fault loop impedance) are directly related through Ohm's law. The prospective earth fault current is:

Ipf(earth) = Uo ÷ Ze

Uo = nominal phase voltage (230V) | Ze = external earth fault loop impedance

The lower the Ze, the higher the earth fault current. For a TN-C-S supply with a typical Ze of 0.20 ohms: Ipf = 230 / 0.20 = 1,150A (1.15kA) for the earth fault path. The prospective short-circuit current (line-to-neutral) is typically higher still because the neutral impedance is lower than the earth fault loop impedance.

Ze and corresponding earth fault PFC

Ze = 0.10Ω

2.3 kA

Ze = 0.20Ω

1.15 kA

Ze = 0.35Ω

657 A

Ze = 0.80Ω

288 A

Remember that the earth fault PFC is usually lower than the short-circuit PFC (line-to-neutral). The overall PFC recorded on the certificate should be the higher of the two values — typically the line-to-neutral short circuit current. The Ze is recorded separately in the supply characteristics section of the earthing arrangements data.

APCS Calculator | BS 7671:2018+A4:2026

APCS calculator for prospective fault current testing. Verify Ze values and breaking capacities against BS 7671:2018+A4:2026 in seconds. Free tool.

Try it free for 7 days
Download on the App StoreGet it on Google Play
07 · BS 7671 Testing

When PFC Is Too High

PFC being "too high" means that the prospective fault current exceeds the rated breaking capacity of the installed protective devices. This is a serious safety defect that requires immediate action.

Replace devices with higher-rated ones

The most straightforward solution is to replace the protective devices with ones that have a breaking capacity exceeding the measured PFC. For example, replacing standard 6kA MCBs with 10kA MCBs. This may require a consumer unit upgrade if the existing consumer unit cannot accept higher-rated devices.

Install a current-limiting device upstream

An HRC fuse (BS 88) installed upstream of the consumer unit can limit the fault current that reaches the downstream MCBs. BS 88 fuses have very high breaking capacities (typically 80kA) and can current-limit, reducing the peak fault current. This "back-up protection" arrangement allows standard 6kA MCBs to be used downstream of a suitable HRC fuse, provided the let-through energy of the fuse does not exceed the MCB's capacity.

Observation codes on EICR

If PFC exceeds device breaking capacity, this should typically be classified as C2 (potentially dangerous) on the EICR. In extreme cases where the margin is significant, C1 (danger present) may be appropriate. The observation should specify the measured PFC, the device breaking capacity, and the recommended remedial action.

08 · BS 7671 Testing

Regulatory Requirements for PFC

BS 7671 has several regulations that address prospective fault current. The key regulations are:

Regulation 434.5.1

The rated short-circuit capacity of each protective device shall be not less than the prospective fault current at the point at which the device is installed. This is the fundamental requirement — every device must be able to safely interrupt the maximum fault current it could face.

Regs 536.1 (last paragraph) & 536.5 — Back-up Protection

Where a protective device has a rated breaking capacity lower than the maximum prospective fault current at its point of installation, Reg 533.2.2 requires compliance with the last paragraph of Reg 536.1 and Reg 536.5. The operative acceptance criterion is that the I²t let-through energy of the upstream device must not exceed the withstand capability of the downstream device (and the cables it protects). This is the regulatory basis for back-up protection arrangements — for example an HRC BS 88 fuse upstream of standard 6kA MCBs.

Reg 643.7.3.201 — Testing-Stage Determination of PFC

Regulation 643.7.3.201 (Part 6, Chapter 64) requires that the prospective short-circuit current and prospective earth fault current are measured, calculated, or determined at the origin of the installation and at every other relevant point as part of initial verification. This is the testing-stage duty. The design-stage obligation to assess supply characteristics — including PFC — is covered by Part 3, Chapter 31, which requires the assessment to be made before design begins and informs protective device selection, consumer unit specification, and cable sizing.

Chapter 43 — Protection Against Overcurrent

Chapter 43 sets out the general principles of protection against overcurrent, including short-circuit current. The protective device must disconnect the circuit before the short-circuit current causes damage to the cable insulation or connections. The adiabatic equation (k²S² ≥ I²t) is the tool used to verify this requirement.

EICR records PFC and validates against device ratings

Elec-Mate's digital EICR records the PFC at the origin and checks it against the breaking capacity of every installed protective device.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

PFC verification, built into every certificate

Join 1,000+ UK electricians using Elec-Mate for on-site testing and certification. PFC calculator, adiabatic verification, and automatic validation on every EICR. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy