Each circuit must be designed to carry the maximum demand of the connected load. The protective device rating and cable size are selected from the design current (Ib) of the circuit, and Regulation 433.1.1 sets the coordination that follows: Ib ≤ In ≤ Iz.
Typical domestic circuit design currents
| Circuit | Design current | Device | Cable |
|---|
| Ring final circuit (sockets) | Varies — diversity applies | 32 A | 2.5 mm² |
| Radial (sockets) | Up to 20 A | 20 A | 2.5 mm² |
| Lighting | Up to 6 A | 6 A | 1.5 mm² |
| Cooker, 12 kW | ≈ 28 A after diversity (52 A connected) | 32 A | 6 mm² |
| Electric shower, 9.5 kW | ≈ 41 A | 45 A | 10 mm² |
| Immersion heater, 3 kW | ≈ 13 A | 16 A | 2.5 mm² |
| EV charger, 7.4 kW | ≈ 32 A | 32 A | 6 mm² |
Currents are at 230 V. Cable sizes are the usual starting point, not an answer — the current-carrying capacity that matters is the tabulated Iz for the actual reference method, after the rating factors for ambient temperature, grouping and thermal insulation. Verify every circuit with the cable sizing calculator using the real installation method, run length and rating factors.
Diversity applies to circuits too, not just to the main supply
A common misreading is that diversity belongs only at the origin. Regulation 311.1 says otherwise: in determining the maximum demand of an installation or part thereof, diversity may be taken into account — and Part 2 defines diversity in the same terms, as a means of determining maximum demand for an installation or part thereof, taking account of usage patterns. The cooker row above is exactly that. The On-Site Guide method takes the first 10 A of the appliance's rated current in full, adds 30% of the remainder, and adds a further 5 A if a socket-outlet is incorporated in the control unit. A 12 kW cooker draws roughly 52 A connected, which becomes about 28 A of design current — which is why a 32 A device is normal on a 12 kW cooker and a 52 A one is not.
Diversity is a design allowance, not a get-out. Once assessed, the circuit must still satisfy Ib ≤ In ≤ Iz, the voltage drop limit and the Zs limit for its disconnection time. For the dedicated high-demand circuits, see the sizing guides for the cooker circuit, the electric shower and the EV charger.