REGULATION DEEP-DIVE

Regulation 314: Division of Installation Into Circuits

Every installation must be divided into circuits to avoid danger and minimise inconvenience. This guide covers the regulatory requirements, ring vs radial decisions, circuit separation, maximum demand, and practical circuit schedules for domestic and commercial installations.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

17 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What does Regulation 314 of BS 7671 require?

Regulation 314 requires every installation to be divided into circuits. Regulation 314.1 lists six objectives (a–f): avoid danger and inconvenience, allow safe testing and maintenance, limit the effect of a single circuit failing, reduce unwanted RCD tripping, mitigate electromagnetic disturbance, and prevent indirect energising. Regulations 314.2 to 314.4 then require separate circuits for parts needing separate control, set the number of circuits and points, and keep each final circuit electrically separate.

Section 314 sits in Part 3 (Assessment of General Characteristics) of BS 7671:2018+A4:2026 and is the foundation of circuit design.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Regulation 314.1 requires that every installation shall be divided into circuits, as necessary, to avoid danger and minimise inconvenience in the event of a fault. This is not a suggestion — it is a mandatory design requirement listing six specific objectives, items (a) to (f).
  • 2Regulation 314.2 requires that separate circuits are provided for parts of the installation that need to be separately controlled, in such a way that those circuits are not affected by the failure of other circuits, with due account taken of the consequences of the operation of any single protective device.
  • 3Regulation 314.3 sets the number of final circuits and the number of points per final circuit, such that compliance with Chapter 43 (overcurrent), Chapter 46 and Section 537 (isolation and switching) and Chapter 52 (current-carrying capacity) is facilitated.
  • 4Ring final circuits are standard for 13A socket outlets in domestic installations (BS 7671 Appendix 15, Regulation 433.1.204). Radial circuits are preferred for dedicated loads (cooker, shower, immersion heater) and where the cable run is too long for a ring. Both are equally valid — the choice depends on the application.
  • 5Regulation 314.1(c) requires the design to take account of hazards that may arise from the failure of a single circuit, such as a lighting circuit — the basis for keeping lighting on a separate protective device from the socket-outlet circuits, so that a trip on a socket circuit does not leave the occupants in darkness.
01 · Regulation Deep-Dive

Division of Installation Into Circuits

Section 314 of BS 7671:2018+A4:2026 sets out the requirements for dividing an electrical installation into circuits. This is the foundation of circuit design — it determines how many circuits the installation needs, what type of circuits to use, and how to arrange them to provide safe and reliable operation.

Circuit division is not just about calculating cable sizes and protective device ratings. It is about designing an installation that limits the consequences of a fault, allows safe maintenance, provides operational flexibility, and minimises nuisance tripping. A well-designed circuit arrangement means a fault on one circuit does not plunge the house into darkness, does not disable the fire alarm, and does not defrost the freezer.

This guide covers the regulatory requirements, the practical decisions (ring vs radial, how many circuits, what goes on each), and design approaches for both domestic and commercial installations.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Regulation Deep-Dive

Regulation 314.1 — Every Installation Shall Be Divided

Regulation 314.1 is clear: every installation shall be divided into circuits, as necessary, to achieve six objectives. The regulation lists them as items (a) to (f), and a compliant design must satisfy each one that is relevant to the installation:

  • (a)Avoid danger and minimise inconvenience in the event of a fault. A single circuit feeding the whole installation is not acceptable — a fault must not be allowed to disable everything at once.
  • (b)Facilitate safe inspection, testing and maintenance (see also Chapter 46 and Section 537). Dividing the installation lets individual circuits be isolated for safe working without shutting down the whole property.
  • (c)Take account of hazards arising from the failure of a single circuit such as a lighting circuit. This is the regulatory basis for keeping lighting separate from sockets and for dedicating critical circuits (fire alarm, emergency lighting).
  • (d)Reduce the possibility of unwanted tripping of RCDs due to excessive protective conductor (PE) currents not due to a fault. This drives the choice between split-load RCD boards and individual RCBO boards.
  • (e)Mitigate the effects of electromagnetic disturbances (see also Chapter 44). Circuits supplying sensitive equipment (data and communications) are kept apart from circuits supplying disturbance sources (motors, welders).
  • (f)Prevent the indirect energising of a circuit intended to be isolated — supported by Regulation 314.4, which requires each final circuit to be wired electrically separately from every other final circuit.
03 · Regulation Deep-Dive

Regulations 314.2, 314.3 and 314.4 — Separation and Numbers

The remaining regulations in Section 314 turn the broad objectives of 314.1 into concrete design rules. It is worth getting the numbering right, because each one means something different:

  • 314.2Separate circuits shall be provided for parts of the installation that need to be separately controlled, in such a way that those circuits are not affected by the failure of other circuits, and due account shall be taken of the consequences of the operation of any single protective device.
  • 314.3The number of final circuits required, and the number of points supplied by any final circuit, shall be such as to facilitate compliance with Chapter 43 (overcurrent protection), Chapter 46 and Section 537 (isolation and switching) and Chapter 52 (current-carrying capacities of conductors).
  • 314.4Where an installation comprises more than one final circuit, each final circuit shall be connected to a separate way in a distribution board, and the wiring of each final circuit shall be electrically separate from that of every other final circuit, to prevent the indirect energising of a circuit intended to be isolated.

In practice, Regulation 314.2 is the one that drives the everyday separation decisions below — the situations where giving a load its own circuit is not optional:

  • Lighting vs power — lighting and socket-outlet circuits must be on separate protective devices. A fault on a socket circuit must not extinguish the lighting. This is the most fundamental circuit separation in any installation.
  • Safety services — fire alarm systems, emergency lighting, and smoke detection must be on dedicated circuits, separate from all other loads. These circuits must not be affected by faults elsewhere in the installation.
  • High-current dedicated loads — equipment with high current demand (cooker, electric shower, immersion heater, EV charger) must have dedicated circuits. Sharing a circuit between a high-demand load and other equipment causes voltage fluctuations and nuisance tripping.

The regulation does not prescribe exactly how to divide circuits — it sets the objectives (avoid danger, minimise inconvenience) and leaves the specific design to the competent electrician. This is where professional judgement and design skill are essential.

04 · Regulation Deep-Dive

Maximum Demand Per Circuit

Each circuit must be designed to carry the maximum demand of the connected load. The protective device rating and cable size are selected based on the design current (Ib) of the circuit — the maximum current expected in normal operation.

Typical Circuit Design Currents (Domestic)

CircuitDesign CurrentMCB RatingCable Size
Ring final circuit (sockets)Varies (diversity)32A2.5mm sq
20A radial (sockets)Up to 20A20A2.5mm sq
Lighting circuitUp to 6A6A1.5mm sq
Cooker (12kW)Approx 30A (with diversity)32A6.0mm sq
Electric shower (9.5kW)Approx 41A45A10.0mm sq
Immersion heater (3kW)Approx 13A16A2.5mm sq
EV charger (7.4kW)Approx 32A32A6.0mm sq

Cable sizes assume standard installation method (clipped direct or enclosed in conduit). Always verify using the cable sizing calculator with the actual installation method, cable run length, and derating factors.

Diversity is applied to the total installation demand (at the main switch and supply level), not to individual circuit design. Each circuit must be designed to carry its full maximum demand — diversity is used when calculating the total demand on the main supply to determine the supply cable size and main fuse rating. For dedicated high-demand circuits, see our detailed sizing guides for the cooker circuit, the electric shower and the EV charger.

05 · Regulation Deep-Dive

Ring vs Radial Circuits: When to Use Each

The choice between ring and radial circuits is one of the most common design decisions for UK electricians. Both are equally compliant with BS 7671 — the choice depends on the application, cable routing, and floor area.

Ring Final Circuit

Cable runs in a ring from the consumer unit, around the socket outlets, and back to the consumer unit. Both ends of the line, neutral, and earth are connected to the same terminals.

Protection: 30A or 32A overcurrent device (Appendix 15)

Cable: 2.5mm sq (copper, twin and earth)

Floor area: historically limited to 100 sq m (Appendix 15)

Advantages: Lower Zs at mid-point (halved impedance), lower voltage drop, can supply multiple 13A sockets over a large area

Use when: Multiple general-purpose socket outlets serving a room or area up to 100 sq m

Radial Circuit

Cable runs from the consumer unit to the load(s) in a single direction. No return path to the consumer unit — the cable terminates at the last point on the circuit.

Protection: Varies (e.g. 20A socket radial, or matched to the load)

Cable: Sized for the design current and length

Floor area: a 20A/2.5mm sq socket radial historically limited to 50 sq m (Appendix 15, Figure 15B)

Advantages: Simpler cable routing, ideal for dedicated loads, no ring continuity issues

Use when: Dedicated load (cooker, shower, EV charger), small area, or where ring routing is impractical

Common mistake: Spurs on ring circuits are often misunderstood. Per Appendix 15, an unfused spur run in 2.5mm sq cable should feed one single or one twin socket-outlet only, and may be connected to the ring at a socket-outlet, at a junction box, or at the origin of the circuit in the distribution board. If you need to supply several additional sockets, either extend the ring itself or use a fused connection unit (max 13A fuse) to create a fused spur — the number of sockets a fused spur can feed then depends on the load, having taken diversity into account.

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Regulation Deep-Dive

Circuit Separation Requirements

Beyond ring vs radial, the design must consider which loads go on which circuits. Proper circuit separation ensures safety, reliability, and ease of maintenance.

  • Lighting circuits — must be separate from socket-outlet circuits. Provide at least two lighting circuits in any dwelling (upstairs and downstairs, or front and back). This ensures that a fault on one lighting circuit does not leave the entire property in darkness. Each lighting circuit is typically protected by a 6A MCB with 1.5mm sq cable.
  • Socket-outlet circuits — provide at least two ring or radial circuits for general socket outlets. Distribute them so that a trip on one circuit does not remove all socket power (for example, one circuit for upstairs, one for downstairs; or one for the kitchen/utility and one for living areas).
  • Dedicated circuits — the following loads should always have dedicated circuits: cooker, electric shower, immersion heater, electric vehicle charger, heat pump, fire alarm system, security system, and any other load exceeding 2kW or requiring specific control.
  • Outdoor circuits — outdoor socket outlets, garden lighting, and outbuilding supplies should be on separate circuits from indoor circuits. This limits the impact of outdoor faults (which are more common due to weather exposure) on the indoor installation.
07 · Regulation Deep-Dive

Practical Design Approach: Domestic Installations

Here is a practical circuit design for a typical 3-bedroom semi-detached house. This is a starting point — adjust based on the specific property, customer requirements, and installed equipment.

Typical Domestic Circuit Schedule

CircuitTypeProtectionCable
Downstairs socketsRing32A RCBO Type A2.5mm sq
Upstairs socketsRing32A RCBO Type A2.5mm sq
Kitchen socketsRing32A RCBO Type A2.5mm sq
Downstairs lightingRadial6A RCBO Type A1.5mm sq
Upstairs lightingRadial6A RCBO Type A1.5mm sq
CookerRadial32A RCBO Type A6.0mm sq
Electric showerRadial45A RCBO Type A10.0mm sq
Immersion heaterRadial16A RCBO Type A2.5mm sq
Smoke/fire alarmRadial6A MCB Type B1.5mm sq
Outdoor socketRadial20A RCBO Type A2.5mm sq

Add dedicated circuits for EV charger (32A/6.0mm sq), heat pump, or other high-demand equipment as required. Consumer unit should accommodate spare ways for future additions.

Design circuit schedules with AI assistance

Elec-Mate's AI circuit designer generates circuit schedules based on property type, room layout, and equipment.

Try it free for 7 days
Download on the App StoreGet it on Google Play
08 · Regulation Deep-Dive

Practical Design Approach: Commercial Installations

Commercial installations follow the same principles as domestic but with additional considerations for three-phase supplies, larger load diversity, and more complex circuit arrangements.

  • Phase balancing — in three-phase installations, circuits must be distributed across the three phases to balance the load. Unbalanced loads cause excessive neutral current and voltage imbalance. Allocate single-phase circuits approximately equally across L1, L2, and L3.
  • Sub-distribution — large commercial installations use sub-distribution boards to reduce cable lengths and improve discrimination. The main distribution board supplies sub-boards via sub-main cables, and the sub-boards supply final circuits. Each sub-board serves a defined area or function.
  • Essential and non-essential loads — commercial installations often separate essential loads (servers, fire alarms, emergency lighting, security) from non-essential loads (general lighting, socket outlets, HVAC). Essential loads may be supplied from a UPS or generator, requiring separate distribution.
  • Mechanical plant circuits — HVAC equipment, lifts, and other mechanical plant require dedicated circuits with specific protective devices. These circuits often use Type C or D MCBs due to the inductive loads and high starting currents.

The design process for a commercial installation typically starts with a load schedule (listing every item of equipment and its power demand), followed by a diversity assessment (applying allowances for diversity — BS 7671 defines diversity but the worked allowance tables sit in the IET On-Site Guide and Guidance Note 1), then circuit allocation (deciding which loads go on which circuits), and finally cable sizing and protective device selection for each circuit. Current-carrying capacity and voltage drop figures for that final step come from BS 7671 Appendix 4. The cable sizing calculator handles the cable sizing and protective device verification for each individual circuit.

Frequently Asked Questions About Circuit Division and Design

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Design Circuit Schedules and Size Cables on Your Phone

Join 1,000+ UK electricians using Elec-Mate for AI-assisted circuit design, cable sizing, and on-site EIC certificates with professional schedules. 7-day free trial, cancel anytime.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy