The cable size depends on the shower rating, the installation method, and the applicable correction factors. The cable must carry the full load current continuously — diversity does not apply to electric shower circuits because the full load operates whenever the shower is in use.
Quick Reference: Shower Cable Sizes
7.5kW (32.6A): 10mm² on 40A MCB — 32.6A is above a 32A device, so Ib ≤ In fails on a 32A MCB at 230V
8.5kW (37A): 10mm² on 40A MCB
9.5kW (41.3A): 10mm² on 45A MCB
10.5kW (45.7A): 50A device (45.7A is above a 45A MCB) — 10mm² or 16mm² depending on the reference method and correction factors
10.8kW (47A): 16mm² on 50A MCB. A 12kW unit (52.2A) needs a 63A device
These sizes assume standard installation conditions with no adverse correction factors. If the cable is grouped with other cables, passes through thermal insulation, or is installed in a high ambient temperature, apply the correction factors from Appendix 4 of BS 7671. After applying correction factors, the cable's adjusted current-carrying capacity must still exceed the MCB rating.
Check voltage drop for the actual cable length and design current. Shower circuits often have longer cable runs because the distribution board may be on the ground floor and the shower on the first floor or in a loft conversion. A 20-metre run of 10mm² at 41.3A gives a voltage drop of approximately 6.1V — within the 11.5V limit, but check your specific run length.
In the app
Electric Shower Installation: Cable Size & Wiring (BS 7671)
Electric shower wiring guide: cable and MCB size by kW rating, RCD and bathroom zone requirements, and isolator placement to BS 7671.