REGULATIONS GUIDE

Supplementary Bonding: When Is It Required and When Can It Be Omitted?

Supplementary bonding in bathrooms is one of the most misunderstood topics in BS 7671. This guide explains Regulation 415.2, the three conditions for omission, 4 mm conductor requirements, and how to test bonding correctly.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-05-18Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Supplementary bonding connects exposed-conductive-parts and extraneous-conductive-parts within a specific location (such as a bathroom) to ensure they are at the same potential — reducing the risk of electric shock from simultaneous contact.
  • 2Regulation 415.2 of BS 7671 sets out the requirement for supplementary equipotential bonding, which applies primarily to locations of increased shock risk such as bathrooms (Section 701).
  • 3Supplementary bonding can be omitted in bathrooms if all circuits in the room have 30 mA RCD protection AND the main bonding is in place AND all extraneous-conductive-parts are connected to the protective equipotential bonding via the main bonding system.
  • 4Where required, the supplementary bonding conductor must be at least 4 mm copper (or 2.5 mm if mechanically protected) for connections between extraneous-conductive-parts, and sized according to Regulation 544.2 for connections involving exposed-conductive-parts.
  • 5Elec-Mate includes an AI regulations assistant that can confirm supplementary bonding requirements for any bathroom or special location scenario in seconds.
01 · Regulations Guide

What Is Supplementary Bonding?

Supplementary bonding (also called supplementary equipotential bonding) is the practice of connecting exposed-conductive-parts and extraneous-conductive-parts within a specific location to each other, creating a local equipotential zone. The purpose is to reduce the potential difference (voltage) between metallic parts that a person might simultaneously touch, particularly in locations where the risk of electric shock is increased.

The most common location where supplementary bonding is discussed is the bathroom. In a bathroom, a person is often wet or standing on a wet floor — both of which significantly reduce body resistance and increase the severity of an electric shock. If a person simultaneously touches two metallic parts that are at different electrical potentials (for example, a metal tap connected to a water pipe and a metal towel rail connected to an earthed circuit), the potential difference between them could cause a dangerous current to flow through the body.

Supplementary bonding eliminates this risk by ensuring that all metallic parts within the room are at the same potential. If everything is at the same voltage, there can be no current flow between them — regardless of what voltage that might be relative to true earth.

This is different from main protective bonding, which connects services at the point of entry into the building. Supplementary bonding is additional, local bonding within a specific room. Under certain conditions in BS 7671, supplementary bonding in bathrooms can be omitted — but understanding when and why is essential.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Regulations Guide

Regulation 415.2: The Core Requirement

Regulation 415.2 of BS 7671:2018 is the general regulation for supplementary equipotential bonding. It states that where the conditions for automatic disconnection of supply cannot be met (specifically, where disconnection times under Regulation 411.3.2.2 or 411.3.2.4 cannot be achieved), supplementary equipotential bonding must be provided.

In the context of bathrooms, the specific regulation is 701.415.2, which provides a modified set of rules for bathroom locations. The interaction between these regulations determines whether supplementary bonding is required in any given bathroom.

  • Regulation 415.2 (General): Supplementary bonding must be provided where the conditions for automatic disconnection of supply cannot be met. The supplementary bonding conductor must connect all simultaneously accessible exposed-conductive-parts and extraneous-conductive-parts. The resistance between the bonded parts must not exceed 50V divided by the operating current of the protective device (Ia).
  • Regulation 701.415.2 (Bathrooms): Supplementary bonding is required in bathrooms connecting all extraneous-conductive-parts and exposed-conductive-parts of equipment in Zones 0, 1, 2, and 3 (the zones defined in Section 701). However, this bonding may be omitted if specific conditions are met (see the omission criteria below).
  • Regulation 544.2 (Conductor sizing): Supplementary bonding conductors between two extraneous-conductive-parts must have a cross-section of at least 2.5 mm copper if mechanically protected, or 4 mm if not. Between an exposed-conductive-part and an extraneous-conductive-part, the conductor must be at least half the size of the CPC of the circuit, with a minimum of 2.5 mm.

The 50V/Ia formula from Regulation 415.2 provides a way to verify the effectiveness of supplementary bonding by testing. If the resistance between two simultaneously accessible bonded parts is low enough that the touch voltage cannot exceed 50V, the bonding is effective. In practice, this means the resistance measured between bonded parts should be very low — typically less than 0.05 ohms.

03 · Regulations Guide

When Is Supplementary Bonding Required?

Supplementary bonding is required in the following situations:

  • Bathrooms where the omission conditions are not met. If any circuit serving the bathroom does not have 30 mA RCD protection — for example, if the bathroom lighting is on a lighting circuit without an RCD — supplementary bonding is required. This is the most common reason for requiring supplementary bonding in domestic installations.
  • Bathrooms where main bonding is absent or defective. If the water or gas service is not bonded to the main earthing terminal (or the bonding is corroded, disconnected, or undersized), the main bonding condition is not met and supplementary bonding is required.
  • Locations where disconnection times cannot be achieved. If the earth fault loop impedance on a circuit is too high to achieve the required disconnection time under Regulation 411.3.2, supplementary bonding can be used as an alternative protective measure. However, this is a last resort — the preferred approach is to reduce the impedance or add RCD protection.
  • Special installations. Swimming pools (Section 702), saunas (Section 703), and other special locations may require supplementary bonding regardless of RCD protection. Check the specific section requirements.

In practice, most modern domestic installations with RCBO consumer units or split-load boards with RCD protection on all circuits will meet the omission conditions for bathrooms. However, older installations with rewireable fuseboards or MCB-only boards without RCD protection will almost always require supplementary bonding in the bathroom.

04 · Regulations Guide

When Can Supplementary Bonding Be Omitted?

Under Regulation 701.415.2, supplementary bonding in a bathroom can be omitted if all three of the following conditions are met:

  • Condition 1: All circuits have 30 mA RCD protection. Every circuit that serves the bathroom — lighting, socket outlets, electric shower, heated towel rail, extractor fan — must be protected by a 30 mA RCD. This means each circuit must have its own RCBO, or be on a group RCD that provides 30 mA protection.
  • Condition 2: All extraneous-conductive-parts are connected to the protective equipotential bonding. Every metallic service in the bathroom (water pipes, gas pipes if present, heating pipes) must be connected to the main bonding system. This means the main bonding conductors must be in place, correctly sized, and properly connected at both ends.
  • Condition 3: Main bonding complies with Regulation 411.3.1.2. The main bonding conductors must be correctly sized (typically 10 mm copper for domestic installations), properly installed, and in good condition. Corroded, loose, or undersized main bonding does not meet this condition.

If any one of these conditions is not met, supplementary bonding must be provided. During a periodic inspection (EICR), you must assess all three conditions before deciding whether supplementary bonding is required or can be validly omitted. If supplementary bonding has been omitted but the conditions for omission are not all met, record this as a C2 observation.

A common mistake is assuming that RCD protection alone is sufficient to omit supplementary bonding. All three conditions must be met — not just the RCD condition. Check the main bonding carefully before deciding that supplementary bonding can be left out.

Check bonding requirements with AI

Describe the bathroom installation to Elec-Mate's AI regulations assistant — RCD protection, pipe materials…

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · Regulations Guide

Bathroom Bonding: The Practical Scenario

Bathrooms are where supplementary bonding questions arise most frequently. Here is the practical decision process for a typical domestic bathroom:

Modern Installation (RCBO Board)

The consumer unit has RCBOs on every circuit, including the bathroom lighting and any sockets. The water and gas services are bonded with 10 mm copper to the MET. The bonding is in good condition and correctly connected. In this scenario, all three omission conditions are met — supplementary bonding is not required. Record on the EICR that supplementary bonding is not required due to compliance with Regulation 701.415.2 omission conditions.

Older Installation (Split-Load Board)

The consumer unit is a dual-RCD split-load board. The socket circuits are on one RCD and the lighting circuits are on the other. Both RCDs are 30 mA. The water is bonded with 10 mm copper, the gas is bonded with 10 mm copper, both connections are secure. All three omission conditions are met — supplementary bonding is not required. However, check that the bathroom lighting is definitely on the RCD-protected side of the split-load board — if it is on the non-RCD side (the main switch side), condition 1 is not met and supplementary bonding is required.

Legacy Installation (No RCD Protection)

The consumer unit has MCBs only — no RCDs. The bathroom lighting and electric shower are on MCB-protected circuits without RCD protection. Condition 1 is not met. Supplementary bonding is required in the bathroom. Bond all metallic pipes (hot, cold, heating), any metal bath or shower tray, and the earth terminals of all electrical equipment (towel rail, extractor fan, light fittings) using 4 mm green/yellow cable. Alternatively, recommend upgrading the consumer unit to provide RCD protection on all circuits, which would then allow the supplementary bonding to be omitted.

During periodic inspections, check the bathroom bonding as part of the standard inspection schedule. Record whether supplementary bonding is present, absent, or not required (with the reason). If bonding is required but absent, record as C2 (Potentially Dangerous).

Try Elec-Mate free for 7 days

16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.

Start free trial
Download on the App StoreGet it on Google Play
06 · Regulations Guide

4 mm Conductors: The Standard for Supplementary Bonding

The conductor size for supplementary bonding is set out in Regulation 544.2 of BS 7671. The rules are:

  • Between two extraneous-conductive-parts: 4 mm copper minimum if not mechanically protected, 2.5 mm copper if mechanically protected (run in conduit, trunking, or buried in plaster behind a wall). In practice, most supplementary bonding in bathrooms is surface-clipped and therefore requires 4 mm.
  • Between an exposed-conductive-part and an extraneous-conductive-part: at least half the cross-section of the CPC serving the circuit, with a minimum of 2.5 mm copper. For a circuit with a 1.5 mm CPC (such as a 1.0 mm lighting circuit with an integral CPC), the supplementary bonding conductor must be at least 2.5 mm. For a circuit with a 2.5 mm CPC, the minimum would be 2.5 mm (half of 2.5 is 1.25, but the minimum is 2.5).

The simplest approach is to use 4 mm green/yellow single-core cable for all supplementary bonding connections. This meets the requirement for both extraneous-to-extraneous and exposed-to-extraneous connections, regardless of mechanical protection. It avoids any need to calculate conductor sizes or assess mechanical protection — just use 4 mm and it complies.

The 4 mm cable is readily available, inexpensive, and easy to terminate. Use BS 951 bonding clamps on pipes and standard screw terminals on electrical equipment earth terminals. Where the cable is surface-run, clip it neatly using green/yellow saddle clips.

07 · Regulations Guide

How to Install Supplementary Bonding

Installing supplementary bonding in a bathroom is a straightforward task. Here is the step-by-step process:

  1. Identify all parts to be bonded. Walk the bathroom and identify every extraneous-conductive-part (metallic water pipes, heating pipes, gas pipes if present) and exposed-conductive-part (earth terminals of light fittings, towel rails, extractor fans, shaver sockets). Note the positions and plan the routing.
  2. Plan the conductor route. Plan the shortest practical route for the 4 mm bonding conductor. You can use a daisy-chain configuration (connecting from one part to the next in sequence) or a star configuration (running separate conductors from a central bonding point to each part). The daisy-chain method uses less cable but creates a single-path dependency.
  3. Install bonding clamps on pipes. Clean the pipe surface with emery cloth to ensure a good metal-to-metal contact. Fit a BS 951 bonding clamp at each connection point. Tighten the clamp securely. Attach the permanent safety label: "Safety Electrical Connection — Do Not Remove."
  4. Connect to electrical equipment earth terminals. Where equipment has an earth terminal (towel rail, fan, light fitting), connect the supplementary bonding conductor to that terminal. Do not disturb the existing CPC connection.
  5. Route and clip the conductor. Run the 4 mm green/yellow cable between all bonding points. Clip neatly using saddle clips at regular intervals. Where the cable passes through a wall, use a grommet. Keep the cable accessible for future inspection.
  6. Test the installation. Use a low-resistance ohmmeter to verify continuity between all bonded parts. The resistance between any two bonded parts should be very low — typically less than 0.05 ohms. Record the test results.

The entire installation for a typical bathroom takes 30 to 60 minutes and uses a few metres of 4 mm cable plus a handful of bonding clamps. It is a small job but a critical one — supplementary bonding can be the difference between a safe bathroom and a lethal one.

08 · Regulations Guide

Testing Supplementary Bonding

Testing supplementary bonding is part of the standard inspection and testing sequence, both for initial verification of new work and for periodic inspection (EICR).

  • Continuity test. Using a low-resistance ohmmeter, measure the resistance between each pair of bonded parts. Place one probe on a bonded pipe and the other on another bonded part (a different pipe, a light fitting earth terminal, etc.). The reading should be very low — typically less than 0.05 ohms. A high reading indicates a loose clamp, corroded connection, or broken conductor.
  • Visual inspection. Check all bonding clamps for security and corrosion. Verify that safety labels are present and legible. Check that the bonding conductor is correctly sized (4 mm minimum for unprotected runs), properly routed, and not damaged. Confirm that the conductor is green/yellow throughout its length.
  • Verification formula. The resistance between bonded parts should satisfy: R less than or equal to 50V / Ia, where Ia is the operating current of the protective device for the circuit. For a 30 mA RCD, this gives R less than or equal to 50 / 0.03 = 1,667 ohms — which is easily met. For an MCB-only circuit, the required resistance is much lower (for a 32A MCB, R less than or equal to 50 / 160 = 0.31 ohms, where 160A is the magnetic trip current of a Type B 32A MCB).

Record the supplementary bonding test results on the EICR or EIC. Note which parts are bonded, the measured resistance, and the conductor size. If supplementary bonding is absent where required, record it as C2. If the bonding is present but deteriorated (corroded clamps, loose connections), record the specific defect with the appropriate classification.

Record bonding test results on your phone

Elec-Mate lets you record inspection and test results for supplementary bonding, main bonding, and all other tests directly on your phone.

Try it free for 7 days
Download on the App StoreGet it on Google Play

Frequently Asked Questions About Supplementary Bonding

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Get Bonding Requirements Right Every Time

Elec-Mate's AI regulations assistant confirms supplementary bonding requirements for any installation scenario. Plus calculators, EICR certificates, and training courses. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy