A TT (terre terre) earthing arrangement has no metallic earth connection between the installation and the supply transformer. Instead, the installation has its own earth electrode (typically a driven rod, plate, or tape buried in the ground), and the earth fault current returns to the supply transformer via the general mass of earth. The transformer has its own separate earth electrode.
TT Ze Characteristics
- Distributor-quoted typical maximum value: 21 ohms
- Typical measured range: 10 to 200+ ohms (highly variable)
- Common in: Rural properties, farms, outbuildings, properties where the DNO does not provide an earth
- Earth terminal location: Connected to the installation's own earth electrode (rod, plate, or tape)
The very high Ze of a TT system means that the fault current during an earth fault is far too low to trip an MCB within the required disconnection time. For example, with a Ze of 50 ohms, the fault current at 230V is only 4.6A — not enough to trip even a 6A Type B MCB within 0.4 seconds. This is why TT systems absolutely require RCD protection on all circuits. The RCD trips on the residual current (30mA) rather than the fault current magnitude, bypassing the Zs limitation.
For TT systems, BS 7671 Regulation 411.5.3 requires that the product of the earth electrode resistance (RA) and the RCD operating current (I delta n) does not exceed 50V. For a 30mA RCD: RA must not exceed 50 / 0.030 = 1667 ohms. This is easily achieved with any reasonable earth electrode. However, the lower the electrode resistance, the better — aim for below 200 ohms as a practical target.
In the app
Maximum Ze Values UK: TN-S, TN-C-S & TT (BS 7671)
Typical maximum Ze: TN-S 0.80 ohms, TN-C-S (PME) 0.35 ohms, TT 21 ohms. How to measure external earth fault loop impedance and when to query the DNO.