TESTING GUIDE

Ze Values UK: External Earth Loop Impedance by Earthing Type

Ze is the starting point for every Zs reading in the installation. Distributor-quoted typical maximum values: TN-S 0.80 ohms, TN-C-S (PME) 0.35 ohms, TT 21 ohms. These figures apply to supplies up to 100 A — actual Ze must always be measured. This guide explains what Ze is, how to measure it safely, what affects it, and what to do when the reading exceeds the expected maximum.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-06-10Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

What are the maximum Ze values in BS 7671?

The distributor-quoted typical maximum external earth fault loop impedance (Ze) values used by BS 7671 tables are 0.80 ohms for TN-S, 0.35 ohms for TN-C-S (PME), and 21 ohms for TT systems. These figures apply to supplies up to 100 A and are not a guaranteed cap — actual Ze must be measured at the origin of each installation.

TN-C-S is lowest because the supply earth uses a low-impedance PEN conductor; TN-S is higher as it relies on the cable sheath. Query the DNO if a measured Ze exceeds the distributor-quoted typical maximum for the earthing arrangement.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer — DP Electrical

Key Takeaways

  • 1Ze (external earth fault loop impedance) is the impedance of the fault loop path outside the installation — from the supply transformer, through the line conductor, and back via the earth return path.
  • 2Expected maximum Ze values by earthing arrangement: TN-S = 0.80 ohms, TN-C-S (PME) = 0.35 ohms, TT = 21 ohms. These are distributor-quoted typical maximum values used by BS 7671 tables — they apply to supplies up to 100 A and are not a statutory cap. Actual Ze must be measured and verified at every installation.
  • 3Ze directly affects every Zs reading on the installation — a high Ze pushes up Zs on every circuit, potentially causing widespread compliance failures.
  • 4If measured Ze significantly exceeds the distributor-quoted typical maximum for the earthing arrangement, the DNO (Distribution Network Operator) should be queried because the supply earth may be defective.
  • 5Elec-Mate records Ze at the origin on the EICR, validates it against expected values for the declared earthing arrangement, and uses it to cross-check every Zs reading in the schedule of test results.
  • 6BS 7671:2018+A4:2026 introduced Regulation 421.1.7 recommending arc fault detection devices (AFDDs) and simplified the Appendix 6 schedule of inspections, adding an example initial-verification checklist. Use the current A4:2026 model forms when completing EICRs and EICs.
01 · Testing Guide

What Is Ze (External Earth Fault Loop Impedance)?

Ze stands for external earth fault loop impedance. It is the impedance of the earth fault loop path that is external to the electrical installation — the part you, as the electrician, cannot modify. It represents the impedance of the supply system from the transformer to the origin of the installation and back.

Ze comprises three main components: the impedance of the supply transformer winding, the impedance of the line conductor from the transformer to the installation, and the impedance of the earth return path from the installation back to the transformer. The earth return path is what varies most between earthing arrangements — and this is why Ze differs significantly between TN-S, TN-C-S, and TT systems.

The importance of Ze is straightforward: it sets the baseline for every Zs measurement in the installation. Since Zs = Ze + (R1+R2) — worked through in full in our earth fault loop impedance calculation guide — a high Ze means less headroom for the circuit's own impedance (R1+R2) within the maximum permitted Zs. If Ze is unusually high, it can push every circuit in the installation towards or beyond the maximum, causing widespread compliance failures.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · Testing Guide

TN-S Systems — Expected Ze: 0.80 Ohms Maximum

A TN-S (terre neutre separate) earthing arrangement provides a separate earth conductor from the supply transformer to the installation. In practice, this earth return path is the metallic sheath or armour of the supply cable — typically lead sheath on older cables or steel wire armour on newer ones.

TN-S Ze Characteristics

  • Distributor-quoted typical maximum value: 0.80 ohms
  • Typical measured range: 0.20 to 0.80 ohms
  • Common in: Older properties (pre-1970s), properties with underground lead-sheathed supply cables
  • Earth terminal location: Separate earth terminal at the supply cutout, connected to the cable sheath

TN-S systems tend to have higher Ze values than TN-C-S because the cable sheath has a smaller effective cross-sectional area and higher resistance than a dedicated PEN conductor. Older installations with ageing lead-sheathed cables can have Ze values approaching or exceeding 0.80 ohms, especially if there are corroded joints in the cable sheath. If Ze exceeds 0.80 ohms on a TN-S supply, the cable sheath may have deteriorated and the DNO should be queried.

With a Ze of 0.60 to 0.80 ohms, the available R1+R2 headroom for a B32 circuit (maximum corrected Zs of 1.10 ohms) is only 0.30 to 0.50 ohms. This limits the permissible cable length and may require larger conductor sizes than would be needed on a lower-Ze supply. Always check Ze first when testing an older TN-S installation — if it is high, expect some circuits to fail Zs testing.

03 · Testing Guide

TN-C-S (PME) Systems — Expected Ze: 0.35 Ohms Maximum

A TN-C-S (terre neutre combined-separate) system, commonly called PME (Protective Multiple Earthing), is the most common earthing arrangement for modern domestic installations in the UK. The earth return path is via the combined neutral and earth (PEN) conductor in the supply cable. The PEN conductor is earthed at multiple points along the DNO network and at the supply transformer.

TN-C-S (PME) Ze Characteristics

  • Distributor-quoted typical maximum value: 0.35 ohms
  • Typical measured range: 0.10 to 0.35 ohms
  • Common in: Modern domestic installations (post-1970s), most new builds and housing estates
  • Earth terminal location: Earth terminal at the supply cutout, provided by the DNO as part of the PME arrangement

The low Ze of a PME supply provides excellent headroom for Zs compliance. With a typical Ze of 0.20 ohms, a B32 circuit has 0.90 ohms of R1+R2 headroom (corrected maximum Zs of 1.10 ohms minus Ze of 0.20). This allows comfortably long cable runs even with smaller conductor sizes.

However, PME systems have a specific limitation: if the PEN conductor is lost (for example, due to a DNO cable fault), the installation's earth potential can rise to a dangerous level. This is why BS 7671 imposes restrictions on bonding, extraneous conductive parts, and the use of PME earthing in certain locations (bathrooms in caravan parks, marinas, construction sites). These restrictions are separate from the Ze value itself but are important considerations when assessing a PME installation.

04 · Testing Guide

TT Systems — Expected Ze: 21 Ohms Maximum

A TT (terre terre) earthing arrangement has no metallic earth connection between the installation and the supply transformer. Instead, the installation has its own earth electrode (typically a driven rod, plate, or tape buried in the ground), and the earth fault current returns to the supply transformer via the general mass of earth. The transformer has its own separate earth electrode.

TT Ze Characteristics

  • Distributor-quoted typical maximum value: 21 ohms
  • Typical measured range: 10 to 200+ ohms (highly variable)
  • Common in: Rural properties, farms, outbuildings, properties where the DNO does not provide an earth
  • Earth terminal location: Connected to the installation's own earth electrode (rod, plate, or tape)

The very high Ze of a TT system means that the fault current during an earth fault is far too low to trip an MCB within the required disconnection time. For example, with a Ze of 50 ohms, the fault current at 230V is only 4.6A — not enough to trip even a 6A Type B MCB within 0.4 seconds. This is why TT systems absolutely require RCD protection on all circuits. The RCD trips on the residual current (30mA) rather than the fault current magnitude, bypassing the Zs limitation.

For TT systems, BS 7671 Regulation 411.5.3 requires that the product of the earth electrode resistance (RA) and the RCD operating current (I delta n) does not exceed 50V. For a 30mA RCD: RA must not exceed 50 / 0.030 = 1667 ohms. This is easily achieved with any reasonable earth electrode. However, the lower the electrode resistance, the better — aim for below 200 ohms as a practical target.

Maximum Ze Values UK: TN-S, TN-C-S & TT (BS 7671)

Typical maximum Ze: TN-S 0.80 ohms, TN-C-S (PME) 0.35 ohms, TT 21 ohms. How to measure external earth fault loop impedance and when to query the DNO.

Try it free for 7 days
Download on the App StoreGet it on Google Play
05 · Testing Guide

How to Measure Ze at the Origin

Ze is measured at the origin of the installation — typically at the consumer unit or main distribution board. The procedure is a live test and requires care.

  1. Ensure the installation is safe to work on. Complete a visual inspection and all dead tests before performing live tests. Confirm the supply voltage is within normal limits (216V to 253V).
  2. Turn the main switch off and secure it with a safety locking device. GN3 Reg 2.29 requires isolation before the earthing conductor is disturbed — this step must not be skipped. Inform any occupants that the supply will be briefly interrupted.
  3. Disconnect the main earthing conductor from the main earthing terminal (MET). This isolates the installation earth from the supply earth, ensuring you measure only the external loop. While disconnected, the entire installation has no earth connection — this must be done as quickly as possible.
  4. Set your multifunction tester to loop impedance (Ze) mode. Connect the test leads between the incoming line terminal and the disconnected end of the earthing conductor at the MET.
  5. Press the test button and record the reading. The instrument displays the external earth fault loop impedance in ohms.
  6. Reconnect the main earthing conductor to the MET immediately. Verify the connection is tight and secure, then restore the main switch.
  7. Compare the reading against the distributor-quoted typical maximum for the earthing arrangement: 0.35 ohms for TN-C-S, 0.80 ohms for TN-S, 21 ohms for TT.

Safety Warning

While the main earthing conductor is disconnected, every exposed metallic part in the installation is unearthed. If a fault develops during this period, there is no earth path and no automatic disconnection. Minimise the disconnection time. Ensure no one uses the installation during the measurement. Some electricians prefer to leave all circuit MCBs off during Ze measurement to reduce the risk.

Voice entry for Ze and all test results

Speak your Ze reading — 'Ze, 0.24 ohms' — and Elec-Mate records it on the EICR. Continue speaking Zs, R1+R2, insulation resistance…

Try it free for 7 days
Download on the App StoreGet it on Google Play

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

Try the certificate tools free
Download on the App StoreGet it on Google Play
06 · Testing Guide

What Affects Ze

Ze is determined by factors that are entirely outside the electrician's control — they are characteristics of the supply network. Understanding what affects Ze helps explain why readings vary between installations and why some properties consistently have higher values.

  • Distance from the supply transformer. The further the property is from the nearest substation, the longer the supply cable, and the higher the line conductor resistance — increasing Ze. Rural properties at the end of long supply runs typically have higher Ze values.
  • Supply cable cross-sectional area. Larger cables have lower resistance per metre. Properties served by older, smaller-gauge supply cables will have higher Ze values than those with modern, larger-gauge cables.
  • Condition of the cable sheath (TN-S). Corroded or damaged joints in the cable sheath increase the earth return path impedance. Old lead-sheathed cables with deteriorating joints are a common cause of high Ze on TN-S supplies.
  • Quality of PEN conductor connections (TN-C-S). Loose or corroded connections at joints in the PEN conductor can increase Ze. However, because the PEN conductor is also the neutral return path, a poor connection would likely also cause voltage fluctuation complaints, prompting the DNO to investigate.
  • Soil conditions (TT). For TT systems, Ze is dominated by the earth electrode resistance, which depends on soil type, moisture content, temperature, and electrode depth. Sandy or rocky soil gives high resistance; clay or loam gives lower resistance. Ze on TT systems can vary by an order of magnitude depending on these factors.

Because Ze is outside the electrician's control, it must be measured and accepted as a given. The installation design must work within the Ze constraints — selecting appropriate MCB types, cable sizes, and circuit lengths to achieve compliant Zs values on every circuit.

07 · Testing Guide

When Ze Is Higher Than Expected

If your measured Ze exceeds the distributor-quoted typical maximum value for the earthing arrangement, it is a significant finding that requires action. A Ze above that figure means the supply earth may be compromised, and every circuit in the installation is affected.

  • Verify the measurement. Retest to confirm the reading. Check that the test leads are in good condition and the connections are clean and tight. Null the test leads before measuring.
  • Check the earthing arrangement. Confirm the earthing type. It is possible that the installation has been incorrectly recorded as TN-C-S when it is actually TN-S, or vice versa. Inspect the supply cutout and earthing terminal to verify.
  • Check the earthing conductor connections. A loose or corroded connection between the earthing terminal and the MET will add resistance to the Ze measurement. Inspect and remake connections if necessary.
  • Record the finding on the EICR. If Ze remains above the expected maximum after verification, record it as an observation. The code depends on the severity: C2 (Potentially Dangerous) if the high Ze causes Zs to exceed maximum values on circuits without RCD protection, or C3 (Improvement Recommended) with a note to query the DNO.

A high Ze on a TN-S installation is particularly concerning because it may indicate that the cable sheath is deteriorating. In the worst case, the earth path could become completely open, leaving the installation with no effective earth connection. This is a C1 (Danger Present) defect if discovered.

08 · Testing Guide

When to Query the DNO

The Distribution Network Operator (DNO) owns and maintains the supply cable, including the earth terminal. If you measure a Ze that exceeds the expected maximum for the earthing arrangement, or if you observe visible damage or deterioration to the supply earthing, you should query the DNO.

When to Contact the DNO

  • Ze exceeds the distributor-quoted typical maximum value — for the declared earthing arrangement (above 0.35 ohms for TN-C-S, above 0.80 ohms for TN-S).
  • Visible damage to the supply earth terminal — corroded earthing clamp, damaged cable sheath at the cutout, or signs of overheating.
  • No earth terminal at the cutout — the property may need the DNO to provide a PME earth connection, or the installation may need a TT arrangement with an earth electrode.
  • Suspected loss of PEN conductor — on a PME supply, symptoms include voltage fluctuations between line and neutral, high voltage on the earthing conductor, and unexplained tripping. This is an emergency — the DNO should be contacted immediately.

The UK DNOs have different names depending on the region: UK Power Networks (UKPN) in London and the South East, Western Power Distribution (now part of National Grid) in the South West and Midlands, Northern Powergrid in the North East, SP Energy Networks in Central and Southern Scotland, and Scottish and Southern Electricity Networks (SSEN) in the North of Scotland and South of England. Contact details are on the electricity meter or on the DNO's website.

Record the DNO query on the EICR under "Observations" with a note of the measured Ze value and the action taken.

Record Ze, PFC, and all supply characteristics digitally

Elec-Mate captures the full supply characteristics section of the EICR — earthing arrangement, Ze, PFC, supply voltage…

Try it free for 7 days
Download on the App StoreGet it on Google Play
09 · Testing Guide

Obtaining Ze from the DNO for New Installations

For new installations requiring a new electrical supply, the procedure for establishing Ze is different from measuring it at an existing installation. OSG Reg 1.3 requires that, before starting work, the installer shall establish with the local electricity distributor the typical maximum Ze of the earth fault path outside the consumer's installation. This is a distinct workflow from on-site Ze measurement — the value comes from the DNO, not from a tester.

New Supply: Ze Workflow

  • Contact the DNO at design stage — request the typical maximum Ze for the proposed point of supply before finalising protective device selection and cable sizing.
  • Use the DNO-quoted figure for design calculations — verify that the chosen protective devices will achieve the required disconnection times with the worst-case (maximum) Ze.
  • Measure Ze once the supply is connected — the measured value should be at or below the distributor-quoted maximum; if it is higher, raise the discrepancy with the DNO before energising the installation.
  • Record both values on the EIC — the DNO-quoted design figure and the measured Ze at commissioning. A significant difference between the two may indicate a supply defect.

This two-stage approach — obtain from DNO for design, measure at commissioning — ensures that circuits are designed to work within the worst-case supply impedance and that the as-built installation is verified against it. For periodic inspection of an existing installation, only the measured Ze is relevant; the DNO-quoted figure is a design tool, not a pass/fail threshold for condition reporting.

Frequently Asked Questions About Ze Values

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-Day Free Trial — Cancel Anytime, No Hassle

Validate Ze and Every Test Result Automatically

Elec-Mate validates Ze against expected values, cross-checks Zs with Ze + R1+R2, and flags any discrepancies. Voice test entry records readings hands-free. 70+ calculators built in. Join 1,000+ UK electricians. 7-day free trial.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical

From £6.99/mo after trial — less than a coffee a week

or download the app
Download on the App StoreGet it on Google Play
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy