BS 7671 Inspection & Testing Questions (AM2 Online Knowledge Test Topic Drill)
Free topic drill: 30 random questions from a pool of 116 on BS 7671 Inspection & Testing, drawn from the wider AM2 Online Knowledge Test bank. 60-minute timer, 70% to pass, worked explanation on every question. Use this after you have sat the full AM2 Online Knowledge Test mock exam and want to drill the topics you got wrong.
- Questions
- 30
- Time limit
- 60 min
- Pass mark
- 70% · 21/30
- Question bank
- 116
Free, no sign-up. Retake as many times as you like: different questions each time.
Sample questions
01What is the correct sequence for initial verification tests?
- AContinuity of protective conductors, insulation resistance, polarity, Zs, RCD
- BInsulation resistance, continuity of protective conductors, RCD, polarity, then Zs
- CRCD operation, Zs, polarity, continuity of protective conductors, insulation resistance
- DZs, RCD operation, polarity, insulation resistance, continuity of protective conductors
Why: Regulation 643.1 requires the dead tests in order before energising: continuity of protective conductors and ring conductors, then insulation resistance, then polarity. Live tests follow, Zs and then RCD operation. Insulation testing before continuity is the usual slip, but a 500 V test to earth only means something once the cpc is proven continuous.
02Which instrument is used to test the continuity of protective conductors?
- ARCD tester
- BEarth fault loop impedance tester
- CInsulation resistance tester
- DLow resistance ohmmeter
Why: Continuity of protective conductors is measured with a low-resistance ohmmeter or the continuity range of an insulation and continuity tester. GN3 recommends a source of 4 V to 24 V, DC or AC, giving at least 200 mA. An insulation resistance tester applies 500 V and reads in megohms, so it cannot resolve the fractions of an ohm a cpc gives.
03What test voltage is used for insulation resistance testing on 230 V circuits?
- A1000V DC
- B500V DC
- C230V AC
- D250V DC
Why: Table 64 sets 500 V DC for circuits up to and including 500 V, other than SELV and PELV, so a 230 V circuit is tested at 500 V DC. 250 V DC is the SELV and PELV row, or the reduced test after vulnerable equipment is connected (Regulation 643.3.3). The test is always DC, never the 230 V AC supply.
Common questions
Is the BS 7671 Inspection & Testing mock exam free?
Yes, it is free with no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.
Can I retake the mock exam?
Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.
Does this count as a qualification?
No. This is independent practice material and does not award a qualification, card or certificate. Where a subject has a formal qualification or card, you gain it through an approved provider.