BS 7671 Selection & Erection Questions (AM2 Online Knowledge Test Topic Drill)
Free topic drill: 30 random questions from a pool of 50 on BS 7671 Selection & Erection, drawn from the wider AM2 Online Knowledge Test bank. 60-minute timer, 70% to pass, worked explanation on every question. Use this after you have sat the full AM2 Online Knowledge Test mock exam and want to drill the topics you got wrong.
- Questions
- 30
- Time limit
- 60 min
- Pass mark
- 70% · 21/30
- Question bank
- 50
Free, no sign-up. Retake as many times as you like: different questions each time.
Sample questions
01Which group of factors determines the current-carrying capacity of a cable?
- AThe supply voltage, the supply frequency and the type of earthing system
- BInstallation method, ambient temperature, grouping, thermal insulation
- CThe protective device type, and its breaking capacity at the board
- DConductor colour, the overall cable length and the number of cores fitted
Why: A cable's current-carrying capacity is the Appendix 4 tabulated value for its installation method, corrected for ambient temperature (Ca), grouping with other circuits (Cg) and any thermal insulation (Ci). Conductor size alone tells you nothing until those conditions are known, which is why the same 2.5 mm² cable can carry very different currents.
02What is the minimum copper conductor cross-sectional area permitted for a lighting circuit?
- A1.0mm²
- B2.5mm²
- C0.5mm²
- D1.5mm²
Why: BS 7671 Table 52.3 sets 1.0 mm² copper as the minimum for sheathed and non-sheathed cables in lighting and power circuits. 0.5 mm² is the minimum for signalling and control circuits, and 0.75 mm² applies to flexible cables for general use, so neither is enough for fixed lighting wiring.
03What is the minimum copper conductor cross-sectional area for a ring final circuit wired in thermoplastic twin-and-cpc cable?
- A1.0mm²
- B2.5mm²
- C4.0mm²
- D1.5mm²
Why: Regulation 433.1.204 allows BS 1363 sockets on a ring protected at 30 or 32 A, wired in copper with line and neutral of at least 2.5 mm². The only exception is two-core mineral insulated cable at 1.5 mm². The cable's Iz must be at least 20 A, because the load shares between the two legs. 4.0 mm² is the usual size for a 32 A radial.
Common questions
Is the BS 7671 Selection & Erection mock exam free?
Yes, it is free with no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.
Can I retake the mock exam?
Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.
Does this count as a qualification?
No. This is independent practice material and does not award a qualification, card or certificate. Where a subject has a formal qualification or card, you gain it through an approved provider.