Industrial distribution and earthing — Industrial Electrical Practice

Free topic-focused mock exam: all 30 questions on Industrial distribution and earthing, drawn from the wider Industrial Electrical bank. 35-minute timer, 70% to pass, worked explanation on every question. Use this when you've taken the full mock once and want to drill the topics you got wrong.

Questions
30
Time limit
35 min
Pass mark
70% · 21/30
Question bank
30

Free, no sign-up. Retake as many times as you like — the questions are reshuffled, with the answer order changed.

Sample questions

  1. 01A replacement contactor coil marked 230 V has been wired between L1 and L2 of a 230/400 V three-phase supply. What voltage will the coil see?
    • A400 V, which is 230 V multiplied by √3
    • B230 V, because each line is 230 V to earth
    • C690 V, three times the line-to-neutral value
    • D460 V, twice the 230 V line-to-neutral value

    Why: Between any two lines of a UK 230/400 V supply the voltage is 400 V, which is the 230 V line-to-neutral voltage multiplied by √3 (about 1.73). A 230 V coil across two lines will not last. Doubling 230 V is tempting, but it ignores the fact that the line voltages peak one after another rather than together. 230 V is what you read from one line to neutral, not between two lines.

  2. 02You are choosing enclosures, cables and glands for a food factory where the plant is hosed down every day. Which regulation of the Electricity at Work Regulations deals directly with equipment exposed to wet, dirt, dust and corrosion?
    • ARegulation 6
    • BRegulation 16
    • CRegulation 5
    • DRegulation 14

    Why: EAWR regulation 6 requires equipment that may foreseeably be exposed to things such as mechanical damage, weather, wet, dirt, dust or corrosion to be built or protected to prevent danger from that exposure, so far as is reasonably practicable. Regulation 5 is tempting because it is also about equipment, but it deals with equipment being pushed beyond what it is built to handle. Regulation 14 covers live work and regulation 16 covers competence.

  3. 03A maintenance manager says the 24 V DC control circuits on a packing line are outside the Electricity at Work Regulations because the voltage is so low. Is that right?
    • AYes, EAWR only applies to circuits within BS 7671
    • BNo, but only as the line is fed from a 400 V board
    • CNo, EAWR applies at work whatever the voltage
    • DYes, EAWR only applies above 50 V AC or 120 V DC

    Why: The Electricity at Work Regulations apply to all electrical systems at work and have no voltage limit; they apply wherever danger may arise. BS 7671 has its own scope, but EAWR is not tied to it. The 400 V board answer reaches the right verdict for the wrong reason: the control circuits are covered in their own right, whatever feeds them.

Common questions

Is the Industrial distribution and earthing mock exam free?

Yes — 100% free, no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.

Can I retake the mock exam?

Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.

Does this count towards the real qualification?

No — this is independent practice material. To gain the actual qualification you need to sit the official assessment through an approved provider.

Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

2,320+ electricians and apprentices · from £6.99 a month

We use cookies to improve the app and measure what works. Cookie Policy