Free mock exam

Installation, testing and handover — Smart Home Technology Practice

Free topic-focused mock exam: all 30 questions on Installation, testing and handover, drawn from the wider Smart Home Technology bank. 35-minute timer, 70% to pass, worked explanation on every question. Use this when you've taken the full mock once and want to drill the topics you got wrong.

Questions
30
Time limit
35 min
Pass mark
70% · 21/30
Question bank
30

Free, no sign-up. Retake as many times as you like — the questions are reshuffled, with the answer order changed.

Sample questions

  1. 01A lighting scheme uses DALI drivers, and the DALI pair runs in the same five-core cable as the 230 V supply. A colleague says the pair is SELV data and must be segregated under 528.1. Is he right?
    • ANo, the pair is treated as mains wiring and included in isolation
    • BYes, unless the five-core cable has an earthed screen round the pair
    • CYes, as any bus cable is Band I and must be kept apart from mains
    • DNo, because DALI is PELV, which may share any cable with the mains

    Why: In most drivers the DALI terminals have only basic insulation from the mains, so the pair is not SELV. It is treated as mains wiring: mains-rated cable, often in the same cable as the supply, and included when you isolate. Calling it Band I data is the tempting mistake. PELV is wrong too: in most drivers the pair has only basic insulation from the mains, so it is neither SELV nor PELV. Check the driver maker’s instructions.

  2. 02You are choosing cable for a run that will carry Power over Ethernet to a ceiling access point. Which cable does Section 716 accept?
    • ATwo-core 0.75 mm² flexible cord
    • BSix-core unscreened alarm cable
    • C1.0 mm² flat twin-and-earth cable
    • DCat 6A twisted-pair data cable

    Why: 716.521.101 lists Cat 5, 6, 6A, 7, 7A, 8.1 and 8.2, or other cables defined in BS EN 50173-1. Alarm cable, flexible cord and twin-and-earth are not balanced data cabling, so they are not on the list, even though some of them could carry the current.

  3. 03Inside a house, a Cat 6 run has to go alongside a twin-and-earth cable that is clipped direct, with no conduit, trunking or partition. What safety separation does the On-Site Guide give?
    • AAt least 150 mm, but only if the run is longer than 4 m
    • BNone, because the twin-and-earth already has a sheath
    • CAt least 150 mm, or the BS EN 50174-2 figure if greater
    • DAt least 50 mm, as it does for any internal data cable

    Why: The On-Site Guide allows 50 mm only where the mains is in its own conduit or trunking (bonded if metallic), is mineral-insulated or earthed-armoured, or a protective partition separates the cables. In other cases it is at least 150 mm, or the BS EN 50174-2 EMC figure if that is greater. The 50 mm figure is the tempting one, but none of its conditions applies here.

Common questions

Is the Installation, testing and handover mock exam free?

Yes — 100% free, no sign-up needed. Questions are pulled at random from a substantial bank, with a worked explanation on every question after you submit.

Can I retake the mock exam?

Yes. Every attempt picks a different random selection and reshuffles the options, so each retake gives you genuinely new questions. No limit on retakes.

Does this count towards the real qualification?

No — this is independent practice material. To gain the actual qualification you need to sit the official assessment through an approved provider.

Certificate types
19Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

2,320+ electricians and apprentices · from £6.99 a month

We use cookies to improve the app and measure what works. Cookie Policy