BS 7671 Compliant

Three Phase Voltage Drop Calculator BS 7671 Compliant

VD = mV/A/m (three-phase) × Ib × L ÷ 1000, using the BS 7671 Appendix 4 tables. The √3 is already inside the tabulated value. Handles balanced and unbalanced loads, SWA and multicore cables, with instant pass/fail against the 20 V and 12 V limits on a 400 V supply.

Three-PhaseAll Cable TypesBS 7671:2018+A4:2026

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

10 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate
ShareXinW
Follow

Work out your three-phase volt drop

Free · no sign-up · BS 7671:2018+A4:2026

Voltage Drop Calculator

Calculate voltage drop using BS 7671 Appendix 4 tabulated values

Cable Selection
A

Ib - design current

m

One-way route length

%

Origin → this board (submains). Leave blank if this circuit starts at the origin.

Empty: Design Current, Cable Length, Cable Size.

Set the supply to 400 V (three phase) and the result is checked against the Table 4Ab limits — 12 V for lighting, 20 V for other uses. The tool applies the two-core mV/A/m value, which over-states the drop by roughly 15%, so a pass here is a genuine pass. For a final design, take the three-phase figure from the three-phase mV/A/m table below.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01The formula is VD = mV/A/m x Ib x L / 1000 — the same structure as single-phase, but you must read the three-phase column of the BS 7671 Appendix 4 tables, not the single-phase column.
  2. 02On a 400 V three-phase supply taken from the public distribution network the limit is 5% = 20 V for power and 3% = 12 V for lighting. The figures are in Appendix 4, Section 6.4 (Table 4Ab); Regulation 525.202 is what makes meeting them deem the requirement satisfied.
  3. 03The root 3 factor is already inside the tabulated three-phase mV/A/m values — Appendix 4, Section 6 states that for three-phase circuits the tabulated values relate to the line voltage and balanced conditions are assumed. Never multiply by 1.732 again.
  4. 04For a balanced load one calculation covers the circuit. For an unbalanced load, work phase by phase using the single-phase mV/A/m values, and assess the neutral separately where third harmonic content is significant.
  5. 05Elec-Mate's three-phase voltage drop calculator has the Appendix 4 tables built in, handles balanced and unbalanced loads, and gives an instant pass/fail against the correct limit.

The Three-Phase Voltage Drop Formula

Jump to the free three-phase volt drop calculator

VD = (mV/A/m3ph × Ib × L) / 1000

VD = line-to-line voltage drop in volts

mV/A/m3ph = three-phase millivolts per ampere per metre, from the BS 7671 Appendix 4 tables

Ib = design current per phase in amperes

L = run length in metres

Two things separate this from the single-phase calculation. You must read the three-phase column of the table rather than the single-phase column, and the answer is compared against a percentage of 400 V rather than 230 V.

Appendix 4, Section 6 is explicit about what the tabulated number already contains: for three-phase circuits the tabulated mV/A/m values relate to the line voltage, and balanced conditions have been assumed. The root 3 is inside the figure. Multiply the length by the design current, divide by 1000, and you have the line-to-line drop in volts.

Cables above 16 mm²: resistance and reactance

For conductors of 16 mm² or less, Appendix 4, Section 6 says the inductance can be ignored and only a single mV/A/m value is tabulated. Above 16 mm² the table gives an impedance value (mV/A/m)z together with a resistive component (mV/A/m)r and a reactive component (mV/A/m)x. Using the impedance value on its own is safe but pessimistic.

Where the load power factor is worth taking into account, Section 6.2 gives the design value as cos φ × (mV/A/m)r + sin φ × (mV/A/m)x. This is the same relationship as the first-principles form √3 × I × L × (R cos φ + X sin φ), with the √3 and the per-metre resistance folded into the tabulated values. It matters most on three-phase motor circuits, where the power factor can be well below unity.

Frequency range (BS 7671 Appendix 4, Section 6)

The tabulated voltage drop values apply, for a.c. operation, to frequencies in the range 49 to 61 Hz. Appendix 4 warns that the voltage drop for cables operating at higher frequencies may be substantially greater. On the output side of a variable-frequency drive, the tabulated values are not the right tool.

In the app

Three-Phase Volt Drop Calculator (BS 7671)

Enter cable size, current and length to check volt drop against the 3% and 5% limits.

BS 7671 Three-Phase Voltage Drop Limits

BS 7671:2018+A4:2026 Regulation 525.202 states that the voltage drop between the origin of the installation (usually the supply terminals) and a socket-outlet or the terminals of fixed current-using equipment shall not exceed the values in Appendix 4, Section 6.4. Those values are Table 4Ab, and they are expressed as a percentage of the nominal voltage of the installation.

SupplyLightingOther usesOn a 400 V three-phase supply
(a) Low voltage installations supplied directly from a public low voltage distribution system3%5%12 V lighting, 20 V other uses
(b) Low voltage installation supplied from a private LV supply6%8%24 V lighting, 32 V other uses

Source: BS 7671:2018+A4:2026, Appendix 4, Section 6.4, Table 4Ab. Volt figures are the percentages applied to a 400 V nominal line voltage.

The 6% and 8% figures do not release the final circuit

Table 4Ab attaches a footnote to row (b): the voltage drop within each final circuit should not exceed the values given in row (a). A generator-fed or transformer-fed installation therefore gets more headroom across the distribution path as a whole, but each individual final circuit is still held to 3% and 5%.

Three allowances worth knowing

Long wiring systems. Table 4Ab permits the percentages above to be increased by 0.005% per metre of wiring system beyond 100 m, provided the increase is not greater than 0.5%. The cap is reached at 200 m, where the 5% power limit becomes 5.5%. Beyond that length the allowance does not grow any further.

Motor starting. Regulation 525.203 accepts a greater voltage drop during motor starting periods and for other equipment with high inrush currents — but only where it is verified that the voltage variations stay within the limits in the relevant product standard, or the manufacturer’s recommendations where no product standard exists.

Harmonics. Appendix 4, Section 6.4 states that the calculated voltage drop should include any effects due to harmonic currents. On a board full of switched-mode supplies that is not a formality.

The limit applies across the whole path, so where sub-mains sit between the origin and the load their voltage drops are added together and the total is what must comply.

In the app

Instant pass/fail against the Table 4Ab limits

Elec-Mate applies the right limit for the circuit type and supply arrangement automatically.

The Root 3 Factor Explained

The square root of 3, about 1.732, runs through three-phase calculations. It comes from the geometry of three sinusoids displaced by 120 degrees: in a star-connected system the line voltage is root 3 times the phase voltage, which is where 230 V × 1.732 = 400 V comes from.

The question that brings most people to this page is whether they need to apply it themselves. They do not. Appendix 4, Section 6 states that for three-phase circuits the tabulated mV/A/m values relate to the line voltage and balanced conditions are assumed, so the factor is baked into the number in the table.

Common mistake

Do not multiply the result by root 3 as well. If you do, your answer comes out 73% high and you will oversize the cable for no reason.

Why the three-phase column is lower

It helps to see where the difference comes from. A single-phase circuit drops voltage in two conductors, the line and the return, so the drop is 2 × I × R × L. A balanced three-phase circuit carries no neutral current, and the line-to-line drop works out at √3 × I × R × L.

The ratio between them is therefore √3 / 2, or about 0.866. A tabulated three-phase value is roughly 87% of the single-phase value for the same cable — not a third of it, and not the single-phase value divided by root 3. Above 16 mm², where reactance is tabulated separately, the relationship is no longer a simple ratio.

What Is Three-Phase Voltage Drop?

Voltage drop in a three-phase circuit is the loss of potential along the conductors as current flows from the supply to the load. Every cable has resistance, and at larger sizes reactance too. When current passes through that impedance, part of the supply voltage is consumed by the cable rather than delivered to the equipment.

Three line conductors each carry current displaced by 120 degrees, and the reference voltage is the line-to-line value of 400 V rather than the 230 V phase-to-neutral value. That is why the same 5% limit gives 20 V on a three-phase power circuit but only 11.5 V on a single-phase one.

Getting it right matters most on the jobs where the runs are long: cable sizing for sub-mains feeding distribution boards, motor circuits, three-phase EV chargers and large power supplies on commercial and industrial installations.

In the app

The calculators live where your certs and quotes are

Run the calc, fill the certificate, and price the job in the same app — 70+ calculators, 16 certificate types, quoting with AI cost estimation. From £6.99/mo.

Balanced vs Unbalanced Three-Phase Loads

A balanced load draws equal current on all three phases at the same power factor — three-phase motors, three-phase heaters with equal elements, 22 kW EV chargers. Because the tabulated three-phase values assume exactly this, one calculation covers the circuit.

An unbalanced load draws different currents on each phase. That is the normal state of a three-phase board feeding single-phase final circuits; perfect balance is close to impossible in practice.

Balanced load

  • Equal current on L1, L2, L3
  • Zero neutral current
  • Use the three-phase mV/A/m column
  • Compare against a percentage of 400 V

Unbalanced load

  • Different current on each phase
  • Neutral carries the out-of-balance current
  • Use the single-phase mV/A/m column, phase by phase
  • Compare against a percentage of 230 V

For a sub-main feeding a three-phase board, design for the worst-case phase. Where the circuit loading is known, check the highest individual phase current against the single-phase values. Where the loading is genuinely expected to be near balanced, the three-phase calculation is the right one.

Third harmonic and neutral current (Appendix 4, Sections 5.5 and 5.6)

Where a three-phase circuit supplies a high proportion of switched-mode power supplies or LED drivers, the third harmonic currents from each phase add in the neutral instead of cancelling. Appendix 4, Section 5.6 notes that the rating factors in Section 5.5 take account of the heating effect of the third harmonic in the neutral as well as in each line conductor. The neutral can end up carrying more current than any line conductor, which affects conductor sizing and the drop along the neutral, and the balanced / unbalanced framing above does not capture it. Where third harmonic content is high enough that the neutral becomes the basis of sizing, Regulation 431.2.3 also requires overcurrent detection for the neutral conductor.

Worked Examples: Three-Phase Voltage Drop

Each example uses the three-phase a.c. column and checks the result against the Table 4Ab limit for a public low voltage supply. Confirm the mV/A/m figure against the printed table for your own cable before relying on it.

Example 1 — three-phase sub-main, XLPE SWA

A 4-core 25 mm² copper XLPE SWA cable runs 55 metres from the main switchboard to a sub-distribution board. The balanced design current is 75 A per phase. The three-phase value taken from Table 4E4B is 1.50 mV/A/m. At 25 mm² this is an impedance value, so the answer is on the pessimistic side.

VD = 1.50 × 75 × 55 / 1000 = 6.19 V (1.55% of 400 V)

Pass — well inside the 20 V limit, leaving 13.81 V of budget for the final circuits downstream.

Example 2 — long run to a motor

A three-phase motor draws 42 A at full load, supplied by a 10 mm² 4-core copper PVC SWA cable over 80 metres. Table 4D4B gives a three-phase value of 3.8 mV/A/m.

VD = 3.8 × 42 × 80 / 1000 = 12.77 V (3.19% of 400 V)

Pass against the 20 V steady-state limit. If this motor sits downstream of a sub-main, add that drop too. The starting dip is a separate check under Regulation 525.203.

Example 3 — three-phase warehouse lighting

A three-phase lighting circuit serves a warehouse at a balanced 14 A per phase over 65 metres, wired in 4 mm² 4-core copper PVC. Table 4D2B gives a three-phase value of 9.5 mV/A/m.

VD = 9.5 × 14 × 65 / 1000 = 8.65 V (2.16% of 400 V)

Pass against the 12 V lighting limit. At 90 metres the same circuit gives 11.97 V, or 2.99% — still inside 3%, but with nothing left over.

Example 4 — sub-main plus final circuit

A three-phase sub-main of 35 mm² SWA runs 40 m at 100 A with a three-phase value of 1.05 mV/A/m. A final circuit from that board — 6 mm² singles in trunking, 25 m, 28 A, three-phase value 6.4 mV/A/m — serves a three-phase heater.

Sub-main: 1.05 × 100 × 40 / 1000 = 4.20 V

Final circuit: 6.4 × 28 × 25 / 1000 = 4.48 V

Total = 8.68 V (2.17% of 400 V)

Pass — and the total is what Regulation 525.202 asks for, since it measures from the origin of the installation.

Common Three-Phase mV/A/m Values

Indicative three-phase values for copper conductors, for orientation only. Voltage drop figures live in the B-suffix Appendix 4 tables, and the right table depends on insulation and construction: 4D2B multicore non-armoured 70 °C thermoplastic, 4D4B multicore armoured 70 °C thermoplastic, 4E4B multicore armoured 90 °C thermosetting.

SizemV/A/m (three-phase)CableTable
4 mm²9.54-core PVC, non-armoured4D2B
6 mm²6.44-core PVC, non-armoured4D2B
10 mm²3.84-core PVC, non-armoured4D2B
16 mm²2.44-core PVC SWA4D4B
25 mm²1.504-core XLPE SWA4E4B
35 mm²1.054-core XLPE SWA4E4B
50 mm²0.784-core XLPE SWA4E4B
70 mm²0.554-core XLPE SWA4E4B
95 mm²0.414-core XLPE SWA4E4B

Read the figure for your own job from the printed BS 7671:2018+A4:2026 table. The value changes with insulation type, conductor material and construction, and from 25 mm² upwards the table gives an impedance value alongside separate resistive and reactive components rather than a single number.

Single-core armoured cable caveat

Appendix 4, Section 6 states that for single-core armoured cables the tabulated voltage drop values apply where the armour is bonded to earth at both ends. Bond at one end only and the tabulated values no longer hold. Multicore SWA, 3-core and 4-core, is not affected by this.

Correction factors guide: derating and grouping

How to Calculate Three-Phase Voltage Drop — Step by Step

Six steps to a compliant three-phase voltage drop figure using the BS 7671 Appendix 4 tables.

1

Identify the circuit parameters

Determine the design current (Ib) per phase in amperes, the run length (L) in metres from the distribution board to the furthest point, whether the load is balanced or unbalanced, and the circuit type (lighting or power).

2

Select the cable type and confirm it is three-phase

Identify the cable construction (armoured, singles in conduit, multicore), conductor material (copper or aluminium), insulation type (70 degrees C thermoplastic or 90 degrees C thermosetting), and the number of cores — 3-core or 4-core for three-phase.

3

Look up the three-phase mV/A/m value

Open the correct Appendix 4 voltage drop table. The B-suffix tables from 4D1B to 4J4B carry the voltage drop figures. Find the row for your cross-sectional area and read the three-phase a.c. column, not the single-phase column. Above 16 mm2 the table gives an impedance value plus separate resistive and reactive components.

4

Apply the voltage drop formula

Calculate VD = mV/A/m (three-phase) x Ib x L / 1000. The result is the line-to-line voltage drop in volts, because the tabulated three-phase values relate to the line voltage. For a balanced load, Ib is the current per phase.

5

Check against the Table 4Ab limit

On a public low voltage supply, compare against 20 V (5% of 400 V) for power or 12 V (3% of 400 V) for lighting. If a sub-main feeds the board, add its drop to the final circuit drop — Regulation 525.202 covers the whole path from the origin.

6

Refine the figure only if it is marginal

Appendix 4, Sections 6.1 and 6.2 allow correction for operating temperature and load power factor. The temperature factor Ct applies only where the protective device is not a BS 3036 fuse and the ambient temperature is at least 30 degrees C, and above 16 mm2 it is applied to the resistive component alone.

Why Use Elec-Mate's Three-Phase Voltage Drop Calculator?

Purpose-built for UK electricians working on three-phase commercial and industrial installations. Faster and more accurate than manual table look-ups.

Three-Phase mV/A/m Lookup

The BS 7671 Appendix 4 voltage drop tables are built in. Select your cable type and the correct three-phase value is applied automatically.

Balanced & Unbalanced Modes

Switch between balanced three-phase calculations and per-phase unbalanced calculations. Enter a single current or individual phase currents.

All UK Cable Types

Supports SWA, singles in trunking and conduit, XLPE, multicore, and MI cables. Copper and aluminium conductors. Three-core and four-core configurations.

Pass/Fail Indication

Instant colour-coded pass/fail against the correct limit — 20 V (5%) for power or 12 V (3%) for lighting on a 400 V three-phase public supply.

Maximum Cable Length

Works out the longest permissible run for your chosen cable size and load before the voltage drop limit is exceeded.

BS 7671:2018+A4:2026

Calculations follow the current edition of the wiring regulations, including Amendment 4. Values taken from the published Appendix 4 tables.

Frequently Asked Questions About Three-Phase Voltage Drop

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Calculate Three-Phase Voltage Drop in Seconds

Join 1,000+ UK electricians using Elec-Mate for on-site calculations. All BS 7671 tables built in. 7-day free trial, cancel anytime.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy