BS 7671:2018+A4:2026 Regulation 525.202 states that the voltage drop between the origin of the installation (usually the supply terminals) and a socket-outlet or the terminals of fixed current-using equipment shall not exceed the values in Appendix 4, Section 6.4. Those values are Table 4Ab, and they are expressed as a percentage of the nominal voltage of the installation.
| Supply | Lighting | Other uses | On a 400 V three-phase supply |
|---|
| (a) Low voltage installations supplied directly from a public low voltage distribution system | 3% | 5% | 12 V lighting, 20 V other uses |
| (b) Low voltage installation supplied from a private LV supply | 6% | 8% | 24 V lighting, 32 V other uses |
Source: BS 7671:2018+A4:2026, Appendix 4, Section 6.4, Table 4Ab. Volt figures are the percentages applied to a 400 V nominal line voltage.
The 6% and 8% figures do not release the final circuit
Table 4Ab attaches a footnote to row (b): the voltage drop within each final circuit should not exceed the values given in row (a). A generator-fed or transformer-fed installation therefore gets more headroom across the distribution path as a whole, but each individual final circuit is still held to 3% and 5%.
Three allowances worth knowing
Long wiring systems. Table 4Ab permits the percentages above to be increased by 0.005% per metre of wiring system beyond 100 m, provided the increase is not greater than 0.5%. The cap is reached at 200 m, where the 5% power limit becomes 5.5%. Beyond that length the allowance does not grow any further.
Motor starting. Regulation 525.203 accepts a greater voltage drop during motor starting periods and for other equipment with high inrush currents — but only where it is verified that the voltage variations stay within the limits in the relevant product standard, or the manufacturer’s recommendations where no product standard exists.
Harmonics. Appendix 4, Section 6.4 states that the calculated voltage drop should include any effects due to harmonic currents. On a board full of switched-mode supplies that is not a formality.
The limit applies across the whole path, so where sub-mains sit between the origin and the load their voltage drops are added together and the total is what must comply.
In the app
Instant pass/fail against the Table 4Ab limits
Elec-Mate applies the right limit for the circuit type and supply arrangement automatically.