BS 7671:2018+A4:2026 Regulation 701.415.2 permits supplementary bonding to be omitted where two things are established: a prerequisite, and three named conditions (d), (e), and (f).
Prerequisite: The location is in a building that has a protective equipotential bonding system in accordance with Regulation 411.3.1.2. In practice this means main bonding conductors connect the main earthing terminal to the incoming metallic services (gas, water, oil) at or near their point of entry to the building. Without this main bonding in place, supplementary bonding cannot be omitted regardless of the conditions below.
Once the prerequisite is established, ALL three conditions must also be met:
- Condition (d) — Automatic disconnection (Reg 411.3.2): All final circuits of the location comply with the automatic disconnection requirements. Table 41.1 disconnection times apply to socket-outlet circuits up to 63A and to fixed-load-only circuits up to 32A (Regulation 411.3.1.2). Verify by measuring earth fault loop impedance (Zs) and confirming it is within the maximum Zs values for the protective device.
- Condition (e) — Additional RCD protection (Reg 415.1.1): All final circuits of the location have additional protection by a 30mA RCD in accordance with Regulation 415.1.1 (Regulation 701.411.3.3). This includes the lighting circuit, any socket circuit, the shower circuit, electric towel rail circuit, and any underfloor heating circuit. Note that Regulation 701.411.3.3 also requires 30mA RCD protection for LV circuits that merely pass through bathroom zones — not just circuits serving the bathroom.
- Condition (f) — All extraneous-conductive-parts connected (Reg 411.3.1.2): All extraneous-conductive-parts within the location are effectively connected to the protective equipotential bonding. This goes beyond confirming that main bonding exists at the incoming services — it requires each individual piece of accessible metalwork within the bathroom (metal pipes, metal bath, etc.) to be effectively connected into the bonding system.
In a modern domestic installation with a dual-RCD or RCBO consumer unit and main bonding in place, all three conditions are typically met — and supplementary bonding in the bathroom can be omitted. This is now the norm in new-build properties and properties with recently upgraded consumer units.
However, the electrician must verify each condition — not assume. During an EICR, check for the presence and adequacy of main bonding, confirm RCD protection on all bathroom circuits, and verify disconnection times through Zs testing. Only if all three are confirmed can you record that supplementary bonding is not required.