The most significant limitation on any EICR is concealed wiring. In most properties, the majority of the cabling is hidden — buried in walls, run under floorboards, routed through ceiling voids, or enclosed in trunking. During a standard EICR the inspector cannot see it, and the model form says so before you do.
Instead, the inspector infers condition from test results. Insulation resistance testing at 500 V DC (Table 64, minimum 1.0 MΩ for circuits up to and including 500 V) can reveal degraded insulation. Continuity testing can find broken or high-resistance conductors. Earth fault loop impedance testing can expose problems with the protective conductor. None of these detects physical damage to cable sheathing, a non-compliant cable route, or mechanical damage that has not yet changed the electrical properties.
What a concealed-wiring limitation actually means
- The wiring behind walls, under floors and above ceilings has not been visually inspected.
- Results for concealed circuits come from measurements taken at accessible points — sockets, switches, distribution boards.
- Physical damage, incorrect installation methods or non-compliant cable routes may exist and cannot be identified without opening up.
- Where test results suggest a concealed fault the inspector cannot classify, that is exactly the case for an FI — further investigation is advised.
Insulation resistance where equipment cannot be disconnected
Regulation Group 643.3 was redrafted at A2:2022 and the requirement is a two-stage test, not a reduced one. Under Regulation 643.3.3, where connected equipment is likely to influence the measurement or result of the test, or be damaged, the test shall be applied prior to the connection of such equipment, in accordance with Table 64. Following connection of the equipment, a test at 250 V DC shall be applied between live conductors and the protective conductor connected to the earthing arrangement, and the insulation resistance shall be at least 1 MΩ.
So the 250 V test does not replace the Table 64 test, and its acceptance threshold is not lower than the 1.0 MΩ that Table 64 sets for low voltage circuits. Where you could only perform the second stage — because the equipment was already connected and could not be taken out — that is a limitation and belongs in Section D, for example: "IR at 250 V DC with equipment connected; sensitive electronics on lighting circuit 3 could not be disconnected."
For most properties, accepting the concealed-wiring limitation is reasonable. Where the wiring is very old, where there is a history of electrical problems, or where a previous report reported overheating, the client may want to commission invasive inspection of specific areas.