EICR GUIDE

EICR Limitations: What the Report Does and Does Not Cover

Every EICR has a Section D — extent and limitations of inspection and testing. This guide sets out what goes in each of its four boxes, the difference between agreed and operational limitations, the exclusions already printed on the model form, and how to word an entry that will stand up.

Free for 7 days · No charge until day 8 · Cancel anytime · Used by 1,000+ UK electricians

12 min readUpdated 2026-08-07Andrew Moore, Founder of Elec-Mate

Written and reviewed by Andrew Moore, founder of Elec-Mate, against BS 7671:2018+A4:2026, IET Guidance Note 3 and the IET On-Site Guide.

ShareXinW
Follow

The short answer

What are limitations on an EICR?

Limitations are the parts of the installation the inspector did not or could not inspect and test, recorded in Section D of the Electrical Installation Condition Report — "Extent and limitations of inspection and testing". Regulation 653.2 requires the report to include both details of those parts that have been inspected and tested and any limitations of the inspection and testing. There are two kinds: agreed limitations, which are scope exclusions confirmed with the person ordering the report before the inspection, and operational limitations, such as an inability to gain access to parts of the installation or an item of equipment on the day. Both must be recorded with the reason.

1,000+

UK electricians

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5

Key takeaways

  1. 01Limitations go in Section D of the Electrical Installation Condition Report — "Extent and limitations of inspection and testing". Regulation 653.2 requires the report to state both (a) details of those parts of the installation that have been inspected and tested and (b) any limitations of the inspection and testing.
  2. 02There are two kinds. Agreed limitations are scope exclusions confirmed with the person ordering the report (and other interested parties) before the inspection. Operational limitations are the things that stopped you on the day — no access to part of the installation or to an item of equipment.
  3. 03The model form already carries its own default exclusions: unless specifically agreed beforehand, cables concealed in conduit and trunking, under floors, in roof spaces, generally within the building fabric or underground have not been inspected, and no checks are made for safety alerts, corrective actions or product recalls.
  4. 04Regulation 651.2 sets the method: periodic inspection is carried out without dismantling, or with partial dismantling as required, supplemented by appropriate tests from Chapter 64. Lifting floors and opening up concealed areas is extra work that has to be agreed.
  5. 05Intake equipment is not excluded — it is inspected visually only. Service cable, service head, earthing arrangement, meter tails and metering equipment get a visual check, and an outcome against that section (other than access to live parts) does not determine the overall satisfactory/unsatisfactory result.
  6. 06Sampling is a GN3 obligation, not a negotiation. GN3 Chapter 8 Reg 8.2 requires the sampling plan to be justified by risk assessment and documented in the Schedule of Inspections and Schedule of Test Results.
  7. 07A4:2026 changed how a limitation-driven FI lands. The summary of changes for Appendix 6 states that the code FI no longer needs to be marked as unsatisfactory — an observation coded C3 or FI does not affect the overall assessment, which turns on C1 and C2.

01 · EICR Guide

Section D at a Glance: The Four Boxes You Have to Fill

Limitations are not free text bolted onto the end of an EICR. They live in a named part of the model form: Section D — Extent and limitations of inspection and testing, which the form itself cross-references to Regulation 651. Section D has four entries, and each one wants something different.

Section D entryWhat belongs in it
Details of those parts of the installation that have been inspected and testedThe extent. Which distribution boards, which circuits, which parts of the premises, and whether the whole installation or only part of it is covered.
Agreed limitations including the reasonsScope the client chose to exclude, settled before the inspection began — plus why.
Agreed withWho signed off those exclusions. Not optional, and not you.
Operational limitations including the reasonsWhat stopped you on the day: no access to a part of the installation or to an item of equipment — plus why.

The requirement behind the form is Regulation 653.2. It states that the Report shall include (a) details of those parts of the installation that have been inspected and tested and (b) any limitations of the inspection and testing. Regulation 653.1 requires the report to be based on the model given in BS 7671:2018+A4:2026 Appendix 6, taking account of the notes for the person producing the report. Section D is not housekeeping — it is what the declaration in Section G is qualified by, because the inspector declares the report to be an accurate assessment of the installation taking into account the stated extent and limitations in Section D.

What A4:2026 changed here

  • Regulation 653.1 now requires the notes for the person producing the report, provided in Appendix 6, to be taken into account on the Condition Report.
  • Regulation 653.2 now requires the report to include guidance for the recipient(s) based on the model in Appendix 6, and a note has been added that photographic and/or thermographic images can be appended to the report — useful evidence where a limitation stopped you getting closer.
  • The Appendix 6 notes for the person producing the condition report have been redrafted and items rearranged, and the code FI no longer needs to be marked as unsatisfactory.

Free download

Get the BS 7671 A4:2026 Cheat Sheet — free

Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.

  • Every regulation change summarised
  • New model forms (EIC + MEIWC)
  • Free PDF — no subscription

We'll email it once. No spam — unsubscribe any time.

02 · EICR Guide

Agreed vs Operational Limitations

The two boxes are not interchangeable, and putting an entry in the wrong one weakens it. The difference is when it was settled and who agreed it.

Agreed limitationOperational limitation
SettledBefore the inspection is carried outEncountered during the inspection
Confirmed withThe person ordering the report and other interested parties — a licensing authority, insurance company, mortgage provider and the likeNobody in advance. The inspector records it and the reason for it
Typical entry"Inspection limited to the landlord's communal installation; tenant demises excluded at client's instruction.""Garage sub-board not tested — garage locked, key not available at the time of inspection."
Common mistakeLeft blank, or filled in after the eventWritten without the reason, which is what makes it useful

The extent of the installation covered by the report is also to be agreed before the inspection and testing is undertaken — not decided afterwards to match what you managed to reach.

03 · EICR Guide

The Limitations Already Printed on the Form

Before you write anything, the model Condition Report already excludes certain things. The agreed-limitations box carries pre-printed wording that applies unless specifically agreed between the client and inspector prior to the inspection:

Printed default exclusions

  • Cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or underground, have not been inspected.
  • No checks for safety alerts, corrective actions or product recalls for electrical equipment forming part of the installation have been made.
  • An inspection should be made of other electrical equipment housed within an accessible roof space.

This is why repeating "concealed wiring not inspected" in your own words adds nothing — it is already there. What earns its place in Section D is anything beyond the printed defaults, or anything that narrows them further.

The Schedule of Inspections points back at Section D

Two items on the Condition Report Schedule of Inspections explicitly refer the reader to Section D, because they cannot be answered without knowing what you could see:

  • Concealed cables installed in prescribed zones (see Section D, Extent and limitations) — Regulation 522.6.202.
  • Cables concealed under floors, above ceilings or in walls/partitions, adequately protected against damage (see Section D, Extent and limitations) — Regulation 522.6.204.

If Section D says the concealed cabling was not inspected, those two items cannot honestly be marked as verified. The two documents have to agree with each other.

04 · EICR Guide

Extent of the Inspection: What Is Covered

A standard EICR covers the fixed electrical installation from the origin to the final circuits and accessories. Regulation 651.2 sets the method: periodic inspection is carried out without dismantling, or with partial dismantling as required, supplemented by appropriate tests and measurements from Chapter 64.

  • Consumer unit / distribution board. Condition, labelling, protective devices (MCBs, RCDs, RCBOs), main switch, connections.
  • Earthing and bonding. Main earth terminal, earthing conductor, main protective bonding conductors, supplementary bonding where applicable.
  • Final circuits. Wiring to socket-outlets, lighting circuits, cooker circuits, shower circuits, and any other final circuits.
  • Accessories. Socket-outlets, switches, light fittings, connection units, and other fixed electrical equipment.
  • Permanently connected equipment. Cookers, immersion heaters, electric showers, towel rails and other fixed appliances.
  • Consumer's means of isolation and consumer's meter tails. Listed as installation items on the Schedule of Inspections, separately from the distributor's intake equipment.

Two checkpoints that catch people out

Regulation 411.3.4 — introduced with BS 7671:2018 itself, not by a later amendment — requires that within domestic (household) premises, additional protection by an RCD with a rated residual operating current not exceeding 30 mA shall be provided for AC final circuits supplying luminaires. Regulation 421.1.7 covers arc fault detection devices, and the Schedule of Inspections carries a matching item: confirmation of indication that AFDD(s) are operational (421.1.7; 532.6; 651.2(e)).

An older installation is not automatically unsatisfactory

The notes for the person producing the report are explicit: an installation which was designed to an earlier version of BS 7671 or the IEE Wiring Regulations, and which does not fully comply with the current version, is not necessarily unsafe for continued use or in need of upgrading. What is to be recorded is damage, deterioration, defects, dangerous conditions and non-compliances which might give rise to danger. So a pre-A4 lighting circuit without 30 mA RCD protection is an observation to be classified on its risk — not an automatic fail.

The extent entry should specify which circuits were tested, how many distribution boards were inspected, and whether the inspection covered the whole installation or a defined part of it.

05 · EICR Guide

Sampling: Why Not Every Circuit Is Tested

On larger installations — particularly commercial premises with many circuits — testing every circuit and accessory is not always practical. The inspector then uses a sampling approach, tests a representative proportion, and records what was sampled.

Guidance Note 3 Chapter 8 Reg 8.2 describes sampling as the procedure where, for groups of similar circuits, not all are tested if an appropriate sampling plan is justified. The conditions attached to it are the part people skip: sampling shall be documented, justified by risk assessment, and the details included in the Schedule of Inspections and Schedule of Test Results. It is not a percentage you negotiate over the phone.

Sampling that will stand up

  • Do the risk assessment first and document the justification in the Schedule of Inspections and Schedule of Test Results (GN3 Ch 8 Reg 8.2).
  • Agree the approach with the client before starting, and record it in Section D as an agreed limitation.
  • Choose a representative sample — different circuit types, ages and locations, not the four easiest ways to reach.
  • If a sampled circuit shows a defect, increase the sample for that circuit type to establish whether the issue is widespread.
  • Record which circuits were tested and which were not. GN3 also asks for the extent and location of sampling of cable terminations to be stated in Section D.

"10% sample of lighting circuits tested — circuits 4, 7 and 11 of 30" is informative. "Sampling applied" is not a limitation, it is a shrug.

06 · EICR Guide

Concealed Wiring: The Biggest Limitation

The most significant limitation on any EICR is concealed wiring. In most properties, the majority of the cabling is hidden — buried in walls, run under floorboards, routed through ceiling voids, or enclosed in trunking. During a standard EICR the inspector cannot see it, and the model form says so before you do.

Instead, the inspector infers condition from test results. Insulation resistance testing at 500 V DC (Table 64, minimum 1.0 MΩ for circuits up to and including 500 V) can reveal degraded insulation. Continuity testing can find broken or high-resistance conductors. Earth fault loop impedance testing can expose problems with the protective conductor. None of these detects physical damage to cable sheathing, a non-compliant cable route, or mechanical damage that has not yet changed the electrical properties.

What a concealed-wiring limitation actually means

  • The wiring behind walls, under floors and above ceilings has not been visually inspected.
  • Results for concealed circuits come from measurements taken at accessible points — sockets, switches, distribution boards.
  • Physical damage, incorrect installation methods or non-compliant cable routes may exist and cannot be identified without opening up.
  • Where test results suggest a concealed fault the inspector cannot classify, that is exactly the case for an FI — further investigation is advised.

Insulation resistance where equipment cannot be disconnected

Regulation Group 643.3 was redrafted at A2:2022 and the requirement is a two-stage test, not a reduced one. Under Regulation 643.3.3, where connected equipment is likely to influence the measurement or result of the test, or be damaged, the test shall be applied prior to the connection of such equipment, in accordance with Table 64. Following connection of the equipment, a test at 250 V DC shall be applied between live conductors and the protective conductor connected to the earthing arrangement, and the insulation resistance shall be at least 1 MΩ.

So the 250 V test does not replace the Table 64 test, and its acceptance threshold is not lower than the 1.0 MΩ that Table 64 sets for low voltage circuits. Where you could only perform the second stage — because the equipment was already connected and could not be taken out — that is a limitation and belongs in Section D, for example: "IR at 250 V DC with equipment connected; sensitive electronics on lighting circuit 3 could not be disconnected."

For most properties, accepting the concealed-wiring limitation is reasonable. Where the wiring is very old, where there is a history of electrical problems, or where a previous report reported overheating, the client may want to commission invasive inspection of specific areas.

In the app

Record test results hands-free on site

AI board scanner, voice test entry, and automatic BS 7671 validation — finish the certificate before you leave the property. From £6.99/mo.

07 · EICR Guide

What the EICR Does Not Cover

Knowing what falls outside the scope matters as much as knowing what is inside it — and one of these is more nuanced than the usual shorthand suggests.

ItemEICR positionWhat is needed instead
Portable and moveable appliancesOut of scope. Anything that plugs into a socket is not part of the fixed installationSeparate in-service inspection and testing
Gas installationsOut of scope entirelyA Gas Safe registered engineer and a separate gas safety record
Distributor's intake equipment — service cable, service head, earthing arrangement, meter tails, metering equipmentVisual inspection only. An outcome against this section, other than access to live parts, does not determine the overall outcome of the reportReport inadequacies to the person ordering the work and/or dutyholder; they are strongly advised to inform the appropriate authority
Telephone, data and TV cablingOut of scope. These are extra-low voltage (Band I) circuits, not the low voltage (Band II) installation BS 7671 is inspecting hereOnly the mains-powered part — a powered amplifier or PoE source, for example — is in scope
Fire detection and alarm systemsPresence may be noted; the EICR is not a system assessmentInspection to BS 5839-1 by a competent person
Emergency lightingPresence may be noted; not an emergency lighting testInspection and testing to BS 5266
Structural and building fabric issuesWater ingress, damp and insulation are noted where they affect the installationA building surveyor for a full assessment

If you are a landlord or property manager, commission the right inspection for each system. An EICR alone does not cover everything, and the intake-equipment line is the one most often misread in both directions — it is inspected, but it is not tested and it does not drive the overall result.

08 · EICR Guide

Recording Limitations Correctly on the EICR

Recording limitations is a professional skill. Generic statements do not serve the purpose. Every entry should name the thing, name the place, and give the reason.

Poor entries

  • "Limited inspection."
  • "Some areas not accessed."
  • "Non-invasive inspection only."
  • "As per standard limitations."
  • "Concealed wiring not inspected" — already pre-printed on the form.

Entries that do the job

  • "Loft space not accessed — hatch obstructed by fitted wardrobe in bedroom 2."
  • "Ground floor under-floor wiring not visually inspected — solid floor, no access."
  • "Garage sub-board not tested — garage locked, key not available at time of inspection."
  • "Distribution board 2 inspected externally only — cover secured by tamper-proof fixings, no key on site."

The second column tells the reader exactly what was excluded and why. That matters for accountability: if a fault later develops in an area recorded as a limitation, Section D shows it was outside the inspection, and the Section G declaration is expressly qualified by it.

In the app

Get the limitations section right first time

Elec-Mate prompts you to record the extent and limitations as you work through the EICR. Pre-populated options for common limitations…

09 · EICR Guide

Common Limitation Examples by Property Type

The limitations you meet vary by property type. Common ones:

Domestic properties

  • Furniture not moved — sockets behind heavy wardrobes, beds or kitchen units not accessed.
  • Loft wiring not visually inspected — insufficient boarding, or insulation covering cables.
  • Under-floor wiring not inspected — solid floors, or fully carpeted timber floors.
  • Outbuildings not included — separate supply, not part of this installation.

Commercial properties

  • Sampling applied — 20% of lighting circuits, 100% of socket circuits tested.
  • Ceiling void wiring not visually inspected — suspended ceiling tiles not removed.
  • Server room circuits not tested — could not be isolated during business hours.
  • Three-phase distribution not tested — main isolator could not be operated during trading hours.

Houses in multiple occupation

  • Tenant rooms 3 and 5 not accessed — tenants not available at time of inspection.
  • Communal under-stair cupboard locked — key not provided.
  • External lighting circuit to rear not tested — area inaccessible due to overgrown vegetation.

AFDDs — what Regulation 421.1.7 actually says

Arc fault detection devices conforming to BS EN 62606 shall be provided for single-phase AC final circuits supplying socket-outlets with a rated current not exceeding 32 A in four categories of premises: high rise residential buildings (HRRBs), houses in multiple occupation (HMOs), purpose-built student accommodation, and care homes. A note assumes HRRBs to be residential buildings over 18 m in height or in excess of six storeys, whichever is met first. For all other premises the use of AFDDs is recommended, not required. Where used, AFDDs shall be placed at the origin of the circuit to be protected. The requirement in those four premises dates from A2:2022; A4:2026 changed sub-item (a) to read "high rise residential buildings", so a report or template still saying "higher risk residential buildings" is using superseded wording.

On an EICR of an existing installation in one of the four categories, absence of AFDDs is a non-compliance with the current version of BS 7671 to be classified on the danger it presents — read alongside the note that an installation designed to an earlier version is not necessarily unsafe for continued use.

10 · EICR Guide

For Electricians: Getting Limitations Right

Recording extent and limitations properly is one of the clearest markers of a competent inspector. It shows you thought about scope and were straight about what you could and could not assess.

  • Agree the extent before you start. The extent of the installation covered by the report is to be agreed prior to the inspection and testing being undertaken. Whole installation or defined part? Known access restrictions? Will someone be there to move furniture and provide keys?
  • Record limitations as you go. Do not try to reconstruct them at the van. Log each one at the moment you hit it, with the reason.
  • Put each entry in the right box. Agreed limitations were confirmed beforehand and need a name in "Agreed with". Operational limitations were encountered on the day.
  • Keep Section D and the Schedule of Inspections consistent. The concealed-cable items on the schedule refer back to Section D — they cannot say "verified" if Section D says you never saw them.
  • Use FI where the limitation blocks a classification. FI is for a potential issue where you cannot determine a code until further investigation has taken place — which is precisely what a limitation produces.
  • Talk the client through it. Explain what each limitation means in practice at handover, and what further investigation would involve.

In the app

Record extent and limitations as you inspect

Elec-Mate walks you through the extent and limitations section as part of the EICR workflow. Common limitation templates plus free text…

Frequently Asked Questions About EICR Limitations

What electricians say

Verified reviews from the UK App Store.

One App for Everything!

Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.

Apple App Store · GBR

Fantastic app for electricians

I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.

Apple App Store · GBR

Absolutely amazing

I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.

Apple App Store · GBR

Trusted by electricians across the UK

Real feedback from real sparks

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer

Sole Trader · DP Electrical

“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”

Nathan Perry

Electrician · NP Electrical Services

“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”

Jake Pizey

3rd Year Apprentice · Apprentice

7-day free trial

Complete Professional EICRs on Your Phone

AI board scanning, voice test entry, structured extent and limitations recording, and instant PDF delivery. Join 1,000+ electricians doing EICRs the smart way. 7-day free trial.

Start your free trial

From £6.99/mo after the trial — no charge until day 8.

“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”

Daniel Palmer, DP Electrical · 5 out of 5
  • 7 days free, then from £6.99/mo
  • Cancel in one tap — no calls, no hassle
  • iOS, Android and web
  • Built to BS 7671:2018+A4:2026

Or download the app

Download on the App StoreGet it on Google Play
Certificate types
16Certificate types
Calculators
70+Calculators
Training courses
46+Training courses
AI specialists
8AI specialists

1,000+ electricians · From £6.99/mo after trial

We use cookies to improve the app and measure what works. Cookie Policy