Amendment 3 (A3:2024) to BS 7671 introduced Regulation 530.3.201, requiring designers and installers to take account of whether a unidirectional or bidirectional protective device is appropriate — and to follow any orientation marking on the device. This guide explains what it means, which installations are affected, and how to comply.
Regulation 530.3.201, introduced by BS 7671:2018+A3:2024, requires that the selection and erection of equipment for protection takes account of the appropriate use of either a unidirectional or a bidirectional protective device. It matters for solar PV, battery storage and V2G EV chargers, where current can flow back towards the supply. A NOTE adds that some devices are marked (in/out, line/load, arrows) to indicate direction.
1,000+
UK electricians
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer — DP Electrical
Key Takeaways
1Regulation 530.3.201 was introduced by BS 7671:2018+A3:2024 (Amendment 3, issued 31 July 2024). It requires that those selecting and erecting protective equipment take account of the appropriate use of either a unidirectional or bidirectional protective device — and follow any orientation marking (in/out, line/load, arrows) on the device.
2Bidirectional power flow occurs in installations with solar PV, battery storage, vehicle-to-grid (V2G) EV chargers, or other embedded generation where current can flow both from the supply to the installation and from the installation back to the supply.
3Standard MCBs and RCDs are designed and tested for unidirectional current flow only. Using a unidirectional device where bidirectional flow occurs may result in the device failing to operate correctly under fault conditions or failing to break the circuit safely.
4RCCBs, RCBOs, circuit-breakers, and AFDDs may carry orientation markings (such as "in"/"out", "line"/"load", or arrows) required by the relevant product standard listed in Appendix I of BS 7671. Installers must follow this marking when connecting the device.
5BS 7671:2018+A4:2026 (Amendment 4) introduced further changes including a redrafted Reg 421.1.7 — now requiring AFDDs (to BS EN 62606) on single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, HMOs, purpose-built student accommodation and care homes (and recommending them in all other premises) — plus a new Reg 411.6.5 and a new Regulation group 419 for where automatic disconnection is not feasible.
6Elec-Mate solar PV and battery storage certificates include fields for confirming bidirectional device selection in compliance with Regulation 530.3.201. The app references BS 7671:2018+A4:2026 on relevant certificates.
01 · Amendment 4
What Is Regulation 530.3.201?
Regulation 530.3.201 is a new regulation introduced by Amendment 3 (A3:2024) to BS 7671:2018. It addresses a specific safety concern: the selection and erection of protective devices in installations where electrical current can flow in both directions through those devices.
The regulation requires that those selecting and erecting protective equipment take account of the appropriate use of either a unidirectional or a bidirectional protective device. The designer or installer shall determine which directional characteristic is appropriate for the application. Where a device is marked to indicate its orientation (for example "in"/"out", "line"/"load", or arrows), the installer shall connect it in accordance with that marking.
This regulation was added because the UK is seeing rapid growth in domestic and commercial installations that include embedded generation (solar PV), battery energy storage systems (BESS), and vehicle-to-grid (V2G) EV chargers. All of these technologies can cause current to flow "backwards" through devices that were historically designed only for unidirectional current flow.
Prior to Amendment 3 (A3:2024), there was no explicit regulation in BS 7671 requiring designers and installers to consider the directional characteristics of protective devices. Electricians relied on manufacturer guidance and good practice, but there was no regulatory framework mandating it. Regulation 530.3.201 fills this gap.
“Selection and erection of equipment for protection shall take account of appropriate use of either a unidirectional protective device or a bidirectional protective device.”
NOTE: Product standards as listed in Appendix I, for some protective devices including RCCBs, RCBOs, circuit-breakers and AFDDs, require these devices to be marked to indicate if they are unidirectional — e.g. “in” and “out”, “line” and “load”, or arrows.
Device Orientation Marking — Site Check
The NOTE to Regulation 530.3.201 states that product standards (listed in Appendix I of BS 7671) for some protective devices — including RCCBs, RCBOs, circuit-breakers, and AFDDs — require those devices to be marked to indicate if they are unidirectional (e.g. “in”/“out”, “line”/“load”, or arrows). Where such marking is present, connect the device in line with it. Before signing off a solar PV, battery storage, or V2G installation, check every protective device in the bidirectional current path for orientation markings and confirm they are installed accordingly.
Free download
Get the BS 7671 A4:2026 Cheat Sheet — free
Every key change in the 2026 amendment on one page. AFDDs, TN-C-S protection, new schedule columns, model forms. Pinned on your van dash.
Every regulation change summarised
New model forms (EIC + MEIWC)
Free PDF — no subscription
02 · Amendment 4
BS 7671 Amendment History: A3:2024 and A4:2026
BS 7671:2018+A3:2024 was issued on 31 July 2024 by the IET. It is a supplementary amendment to the base standard (BS 7671:2018, commonly known as the 18th Edition) and to Amendment 2 (A2:2022). A3:2024 is a small, focused document available as a free PDF from the IET website — it is not a new book. Its primary addition is Regulation 530.3.201 (bidirectional and unidirectional protective devices), together with two supporting definitions.
BS 7671:2018+A4:2026 (Amendment 4) followed in 2026. Amendment 4 is the current amendment and, among other changes, redrafted Reg 421.1.7 on arc fault detection devices (AFDDs), inserted a new Reg 411.6.5, and added a new Regulation group 419 for situations where automatic disconnection in accordance with Regulation 411.3.2 is not feasible. The full current citation for the standard is BS 7671:2018+A4:2026.
BS 7671 Amendment Timeline
2018BS 7671:2018 — 18th Edition published (the "brown book")
2020Amendment 1 (A1:2020) — corrections and clarifications
2022Amendment 2 (A2:2022) — SPD requirements, EV charging updates
Jul 2024Amendment 3 (A3:2024) — Regulation 530.3.201 (bidirectional/unidirectional devices) + two new definitions
2026Amendment 4 (A4:2026) — redrafted Reg 421.1.7 (AFDDs now required for socket-outlet circuits ≤32 A in higher-risk premises), new Reg 411.6.5, new group 419 — current standard
The current full citation for the standard is BS 7671:2018+A4:2026. When referencing the standard on certificates and documentation, use this full citation to confirm compliance with the latest amendment. The 18th Edition guide covers the base standard in detail.
What Else Did A4:2026 Introduce?
Amendment 4 (A4:2026) extends beyond the bidirectional device rules introduced by A3:2024. Key additions in A4:2026 include:
Reg 421.1.7 (AFDDs) — redrafted. AFDDs conforming to BS EN 62606 are now required on single-phase AC final circuits supplying socket-outlets rated up to 32 A in high rise residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes. For all other premises, AFDDs are recommended on such circuits. Where used, the AFDD is placed at the origin of the circuit it protects.
Reg 411.6.5 — inserted as part of a reorganisation of the IT system requirements in Section 411.6 (Chapter 41, Protection Against Electric Shock).
New Regulation group 419 — inserted for installations where automatic disconnection in accordance with Regulation 411.3.2 is not feasible, such as electronic equipment with limited short-circuit current.
Understanding the difference between bidirectional and unidirectional switching devices is essential for compliance with Regulation 530.3.201. BS 7671 Part 2 (Definitions) defines both terms by reference to how the manufacturer intends the supply to be connected:
BS 7671 Part 2 — Definitions
Unidirectional protective device. A protective device where it is intended by the manufacturer that a source of supply is only connected to one defined set of connection terminals.
Bidirectional protective device. A protective device where it is intended by the manufacturer that a source of supply is connected to either or both sets of connection terminals.
Unidirectional Devices
Designed to interrupt current flowing in one direction only — from supply to load. The internal arc-quenching mechanism is optimised for this direction of current flow.
Standard MCBs, most RCBOs, and many isolators are unidirectional. They will function as a switch in either direction, but the arc-interruption capability may not be guaranteed for reverse current flow. Under a high-energy fault in the reverse direction, the device may fail to extinguish the arc safely.
Bidirectional Devices
Designed and tested to interrupt current flowing in either direction — from supply to load and from load to supply. The arc-quenching mechanism works equally well regardless of current direction.
Bidirectional devices are specifically tested to IEC standards for both directions of current flow and are marked as suitable for bidirectional operation. They may carry a specific symbol or marking on the rating plate.
Check Device Datasheets
Not all devices clearly state whether they are bidirectional or unidirectional on their front plate. Check the manufacturer's technical datasheet or installation instructions for the specific device. If in doubt, contact the manufacturer. Major manufacturers (Hager, Schneider, Siemens, ABB) now clearly state bidirectional suitability in their product documentation.
04 · Amendment 4
Impact on Solar PV Installations
Solar PV installations are the most common application of Regulation 530.3.201 in domestic work. A solar PV system with a grid-tied inverter generates AC power that can flow in two directions: to the property's loads (self-consumption) and to the grid (export).
The key devices that experience bidirectional current in a typical domestic grid-tied solar PV installation are set out below:
Device
Why current can flow both ways
AC isolator at the inverter
Generated current flows from the inverter towards the consumer unit through this isolator, so it sits in the generation-direction path.
MCB / RCBO for the PV circuit
The protective device for the inverter's AC output circuit carries generated current from the inverter to the consumer unit busbars.
Consumer unit main switch
Where surplus generation is exported, the main switch sees both import and export current, so it must suit bidirectional operation.
When specifying protective devices for a solar PV installation, confirm with the device manufacturer that each device in the bidirectional current path is rated for bidirectional operation. Document this on the installation certificate.
05 · Amendment 4
Impact on Battery Storage Systems
Battery energy storage systems (BESS) create bidirectional power flow because the battery charges from the grid or PV system (consuming power) and discharges to supply loads or export to the grid (generating power). This makes every switching device in the battery circuit path subject to Regulation 530.3.201.
The battery storage system's AC connection to the consumer unit or distribution board carries current in both directions during normal operation — not just under fault conditions. This is a key distinction from some solar PV installations where reverse current flow occurs only during export. Battery systems routinely cycle between charge and discharge multiple times per day.
Devices Requiring Bidirectional Rating in BESS
AC isolator for the battery inverter
MCB or RCBO protecting the battery circuit
Main switch if the battery system exports to the grid
Any upstream RCD in the path of bidirectional current
Hybrid inverters that combine solar PV and battery storage in a single unit are particularly relevant — the single AC output circuit carries bidirectional current from both the PV generation and the battery discharge.
Try Elec-Mate free for 7 days
16 certificate types, 70+ calculators, RAMS, quoting, invoicing, AI agents, and 46+ training courses — from £6.99/mo.
Achieving compliance with Regulation 530.3.201 is straightforward in practice, but it requires awareness and a change in procurement habits. Here is a practical workflow:
Identify bidirectional circuits — determine which circuits in the installation carry bidirectional current. This includes any circuit connected to a solar PV inverter, battery storage inverter, V2G charger, or other embedded generation source.
Identify devices in the bidirectional path — trace the bidirectional current path from the generation source to the point of connection with the supply (typically the main switch or meter). Every switching and protective device in this path needs to be bidirectional.
Check existing devices — if adding PV or battery storage to an existing installation, check whether the existing MCBs, RCBOs, isolators, and main switch are rated for bidirectional operation. If not, replace them.
Specify bidirectional devices — when ordering new devices, explicitly request bidirectional-rated versions. Check the manufacturer datasheet before purchase.
Document compliance — record the bidirectional suitability of each device on the installation certificate, referencing Regulation 530.3.201.
A4:2026 Compliance on Certificates
Elec-Mate solar PV and battery storage certificates include fields for confirming bidirectional device selection per Regulation 530.3.201.
Major switchgear manufacturers now produce devices specified for prosumer (generation + storage) installations. Use the table below as a starting checklist, then confirm bidirectional suitability against the manufacturer's datasheet for the specific catalogue number before you order.
Device
What to check before specifying
Main switch
Choose a main switch suited to generation/prosumer applications and confirm the breaking capacity is rated for both directions of current flow.
MCBs & RCBOs
Some standard devices are already tested for bidirectional operation but not marketed as such — confirm with the manufacturer. Check for any in/out or line/load marking and observe it.
AC isolators
Rotary isolators for PV and battery circuits should be rated for the application and for current flow in the generation direction.
RCDs
If an RCD sits in the bidirectional path, confirm both its residual-current detection and its switching/breaking capability are suitable for current in either direction. See RCD types.
AFDDs
Per the NOTE to 530.3.201, AFDDs (BS EN 62606) may be marked for orientation. Where A4:2026 Reg 421.1.7 applies, place the AFDD at the origin of the circuit it protects.
Manufacturer names and ranges change frequently — always verify the current datasheet for the exact catalogue number rather than relying on a brand having a suitable device in the past.
08 · Amendment 4
Certification Requirements
When issuing an EIC for an installation with bidirectional power flow, the certificate should reference compliance with BS 7671:2018+A4:2026 (not just BS 7671:2018 or A2:2022). This confirms that the installation has been designed and installed in accordance with the latest amendment, including Regulation 530.3.201.
The certificate should specifically note:
The presence of embedded generation or storage
Which circuits carry bidirectional current
Confirmation that all devices in the bidirectional path are rated for bidirectional operation
The make and model of bidirectional devices installed
For EICRs on existing installations with solar PV or battery storage, check whether the installed devices are bidirectional-rated. If unidirectional devices are found in the bidirectional current path, raise a C3 observation recommending replacement with bidirectional-rated devices.
Certificates Reference A4:2026 Automatically
Elec-Mate certificates for solar PV, battery storage, and EV installations automatically reference BS 7671:2018+A4:2026.
Elec-Mate is my go to app for business and electrical work. It's feature rich without feeling cluttered. A true all in one app for quotes, certs, calculations, RAMS, EICRs, and more. I use it every day without fail, and it makes my workflow much smoother since I'm not jumping between apps anymore. The price-to-feature ratio is excellent. Any issues I've had, the developer responds within the hour and usually fixes them the same day. 100% recommend.
Fantastic app for electricians
I've used the app and the web based version for a while now and it's well worth the investment. If you're an apprentice or experienced Spark give it a go, you won't be disappointed.
Absolutely amazing
I've been using Elec-Mate for a while now, and honestly, it's one of the best apps I've ever downloaded. Every aspect of it feels thoughtfully designed, from the clean and intuitive interface to the powerful features that make everything so easy to manage. It's clear that a lot of care and attention went into building this app, and it shows in every detail.
Trusted by electricians across the UK
Real feedback from real sparks
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer
Sole Trader · DP Electrical
“I've won two contracts this month because I could turn quotes around same-day with the AI cost engineer.”
Nathan Perry
Electrician · NP Electrical Services
“The study centre got me through my AM2. Mock exams and flashcards are brilliant.”
Jake Pizey
3rd Year Apprentice · Apprentice
7-Day Free Trial — Cancel Anytime, No Hassle
Stay Current with BS 7671 Amendments
Elec-Mate certificates reference BS 7671:2018+A4:2026 automatically. Bidirectional device fields are built into solar PV and battery storage certificates. Join 1,000+ UK electricians. 7-day free trial.
“Replaced three separate apps with Elec-Mate. Certs, quotes, and scheduling all in one place.”
Daniel Palmer, DP Electrical
From £6.99/mo after trial — less than a coffee a week
or download the app
7 days free, then from £6.99/moCancel in one tap — no calls, no hassleiOS, Android & WebBS 7671 compliant
16
Certificate Types
70+
Calculators
46+
Training Courses
8
AI Agents
1,000+ electricians · From £6.99/mo after trial
We use cookies to improve the app and measure what works. Cookie Policy